pressure range of 5 to 50 psi (0,34 to 3,4 bar). The
pressure maintenance device shall have aworking
pressure rating of 175 psi (12,1 bar). Recom-
mended pneumatic supervisory pressure shall be
10 psi (0,70 bar). Pressure maintenance device
shall be Reliable Model A-2.

Double Interlock Preaction System shall be a Reliable

Double Interlock Type D Preaction System, Bulletin 737.

Pneumatic Supervisory Pressure Supply Options

Owner’s Air supply

Air supply shall be provided by an owner-supplied air

system.

Compressed Air Supply

Air supply shall be provided by an automatic

tank-mounted air compressor sized (appropriate hp) for
the capacity (volume) of the sprinkler system piping, and
be capable of restoring normal air pressure in the system
within 30 minutes. Tank mounted compressor shall be a
motor mounted, oil-less, piston compressor, including
gauge, pressure switch, check valve, drain valve, and
safety relief valve. Single-phase motor shall have internal
thermal protection.

Nitrogen

Nitrogen cylinders provided by an approved source

shall provide the nitrogen supply. The nitrogen cylinder
pressure shall be regulated and supervised through the
use of nitrogen regulating device and low-pressure trim
kit. This device shall consist of a brass, single stage pres-
sure regulator, equipped with high pressure inlet and low
pressure outlet gauges, and ¼” copper connection tub-
ing with galvanized ¾” x ¼” reducer bushing. Optional:
Low-pressure trim kit shall be included to monitor the reg-
ulated nitrogen supply pressure to provide a low-pressure
supervisory alarm. This kit shall include a low-pressure
switch with associated galvanized connection trim. As-
sembly shall be a Reliable Nitrogen Regulating Device
This device is to be used in conjunction with the Reliable
Model A-2 Pressure Maintenance Device.

Optional System Accessories

System Control Valve

Preaction system control valve shall be a slow close,

[cULus Listed] [FM Approved] indicating butterfly type
valve with a pre-wired supervisory tamper switch assem-
bly. The valve shall be rated for a working pressure of
[175 psi (12,1 bar)] [250 psi (17,2 bar)]. System control
valve shall be a [2” (50 mm)] Nibco KG-505-w-8 Ball
Valve, [2

1

2

” (65 mm)] [3” (80 mm)] Nibco GD-4765-8N

Butterfly Valve.

Detection System

To initiate actuation of the preaction system’s deluge

valve, a supplemental electric detection system shall be
provided [Insert applicable product specification].

Releasing/Control Panel

A releasing/control panel shall be used to operate the

preaction system. The releasing/control panel shall be a
conventional, microprocessor-controlled panel contain-
ing two initiating device circuits, and waterflow and super-
visory inputs. Output circuits shall include alarm,
waterflow, supervisory, and releasing circuits. Mode of
operation shall be set for cross-zoned operation, requiring
both a detection device input and a low air pressure
switch input (sprinkler operation) to energize the solenoid
valve, causing the deluge valve to actuate. Releas-
ing/control panel shall be equipped with a local tone
alarm to annunciate loss of AC power, system trouble, cir-
cuit trouble, and low auxiliary DC power supply. Panel
shall be [cULus Listed] [FMApproved] and be capable of
providing power for compatible detectors and auxiliary
devices used. Audible alarms shall be able to be silenced
at releasing panel. Auxiliary DC power supply shall con-
sist of (2) 12-volt lead acid batteries of the same ampere-
hour rating, providing [60 hours – cULus Listed] [90 hours
– FM Approved]. Dry contacts shall be provided for re-
mote annunciation of alarm, trouble, and supervisory
panel signals. Main power supply to be a dedicated 120
VAC / 60Hz circuit.

Waterflow Alarm Pressure Switch

Alarm pressure switch shall be provided to indicate

water flow and provide a water flow alarm. Pressure
switch shall be [cULus Listed] [FM Approved] and of the
bellows activated type enclosed in a weatherproof, 4x,
NEMA 4-rated enclosure incorporating tamper-resistant
screws. There shall be two sets of SPDT (Form C) con-
tacts rated at 10.0 A @ 125/250 VAC and 2.5 A @ 6/12/24
VDC. The pressure switch shall have a maximum service
pressure rating of 250 psi (17,2 bar) and shall be factory
adjusted to operate at a pressure of 4 to 8 psi (0,27 to 0,55
bar) with adjustment up to 20 psi (1,3bar). Switch shall be
provided with a ½” NPT male pressure connection.
Waterflow alarm pressure switch shall be System Sensor
EPS10-2.

Summary of Contents for Double Interlock Preaction System D

Page 1: ...mm 3 80mm 76mm Sizes Instructions for Installation Operation Care and Maintenance 10 PSI 0 7 bar Pneumatic Supervising Pressure With Electric Pneumatic Actuation Controlled by a Cross Zoned Releasing Control Panel Type D System Bulletin 737 Rev B Available with 175 psi 12 1 bar or 250 psi 17 2 bar Rated Solenoid Valve Externally Resettable Clapper One Main Drain ...

Page 2: ...rinkler is open Double interlock preaction sys tems are primarily used to protect refrigerated areas where accidental water release before a sprinkler is opened can cause ice blockage resulting in an inopera tive sprinkler system and substantial property damage At the heart of Reliable s Type D Double Interlock Preaction System is the Model DDX Deluge Valve This Deluge Valve is a hydraulically ope...

Page 3: ...Fig 2 3 ...

Page 4: ...odel B Manual Emergency Station 1 13 78653004 Valve Caution Station 1 14 98048015 Reducer 2 x 1 PVC 1 15 98048022 Bushing Reducer x 2 16 96816902 Valve Check In Line 1 17 92056705 Elbow Connector 3 8 Tube x NPT 1 18 6304000100 Pressure Maintenance Device Model A2 1 19 98050004 Drain Cup PVC 1 20 98174400 Street Elbow 2 21 98174408 Street Elbow 1 22 98174414 Elbow 1 1 23 98174403 Elbow 1 1 24 98174...

Page 5: ...tlet to the alarm devices After system shutdown resetting the Model DDX De lugeValveisquitesimple Doingsoonlyrequirespushing 5 in and turning the reset knob at the rear of the valve see Fig 1 The external reset feature of the Model DDX De luge Valve provides a means for simple economical sys tem testing which is one essential facet of a good maintenance program The external reset feature does not ...

Page 6: ...rs In addition to the hydrostatic tests described above dry pipe and double interlock preaction systems require an additional low pressure air test In some cases hydrostatic testing in accordance with the NFPA 13 requirements noted above will result in pressures that exceed the working pressure of the valve and trim kit for the two hour test period Thevalveandapplicabletrimkithavebeentested ap pro...

Page 7: ...Fig 4 7 ...

Page 8: ...ush rod and spring assembly with diaphragm seal secured to the casting through a push rod guide constructed of a syn thetic engineering plastic to resist corrosion Casting shall have a bleeder hole located on the pushrod chamber for air water leakage indication Trip ratio shall be approxi mately a 3 1 force differential Deluge valve shall be of the straight through design to minimize friction loss...

Page 9: ...ar System control valve shall be a 2 50 mm Nibco KG 505 w 8 Ball Valve 21 2 65 mm 3 80 mm Nibco GD 4765 8N Butterfly Valve Detection System To initiate actuation of the preaction system s deluge valve a supplemental electric detection system shall be provided Insert applicable product specification Releasing Control Panel A releasing control panel shall be used to operate the preaction system The ...

Page 10: ...losethe globevalvecontrollingsys tem air pressure in the Model A 2 Pressure Maintenance Device 2 Closethepushrodchambersupplyvalve valveA Fig 6 3 Openthemaindrainvalve valveB Fig 6 anddrainsys tem 4 Open all drain valves and vents at low points throughout thesystem closingthemwhenflowofwaterhasstopped Open valve D Fig 6 5 Note The above steps accomplish the relieving of pres sure in the pushrod ch...

Page 11: ...ke sure that valve G Fig 6 is open Push in on the plunger to be sure the ball check is off its seat If no water appears the Deluge Valve s water seat is tight Inspect the bleed hole see Fig 5 ontheundersideofthepushrodchamberforleak age 5 System pneumatic pressure check that system air pressure is between 7 and 10 psi 0 5 bar 0 7 bar Check the Model A 2 Pressure Maintenance Device for leakage and ...

Page 12: ...8 95276006 Diaphragm 1 19 95306268 Clip Retaining 3 8 Shaft 4 20 95406007 O Ring 114 1 21 95406024 O Ring 912 2 22 95406407 O Ring 014 1 23 95406410 O Ring 150 1 24 95406411 O Ring 147 1 25 95506003 Pushrod 1 26 95606114 Screw Socket Head Ø 20 x 5 8 6 27 95606127 Screw Ø 3 8 16 x Socket Cap Flat Head 1 28 95606133 Screw Cap 6 32 x SS 1 29 96016003 Seat Machined 1 30 96206003 Pin Hinge 1 31 9621600...

Page 13: ... ball drip valve E Fig 6 If system air is leaking out the ball drip valve the prob lem is either damage to the airside of the Model DDX DelugeValve ssealfaceplatesubassembly 8 Fig 5 seat 29 Fig 5 ortheupperseatO ring 23 Fig 5 If supply water is leaking out the ball drip valve the prob lemcouldbecausedbydamagetotheModelDDXDe luge Valve s seal faceplate sub assembly 8 Fig 5 seat 29 Fig 5 or lower se...

Page 14: ...14 Fig 6 ...

Page 15: ...stallationtorqueof15foot pounds Set uptheModelDDXDelugeValveasperthesection Re settingtheTypeDDoubleInterlock PreactionSystem 175 psi 12 1 bar Rated Solenoid Valve 250 psi 17 2 bar Rated Solenoid Valve 175 psi 12 1 bar Rated Solenoid Valve 250 psi 17 2 bar Rated Solenoid Valv UL FM Approved Pressure Switch ULC Listed Pressure Switch Ordering Information Specify Valve Model Size 2 50mm Model DDX De...

Page 16: ...sing Control Panel C Model PFC 4410 RC Potter 5403550 Reliable 700 Batteries 12 VDC 12 AMP Hours 90 Hours Backup FM 12 VDC 7 AMP Hours 60 Hours Backup Optional Accessories CA2Z Class A Wiring Module for Initiating Circuits CAM Class A Wiring Module for Indicating Circuits ARM 1 ARM 2 Auxiliary Relay Module RA 4410 RC Remote Annunciator 7 Alarm Annunciator A Model SSM24 8 24 VDC Polarized Bell Reli...

Page 17: ...17 Fig 7 ...

Page 18: ... K L M N P Q R 2 50mm 2 65mm 3 80mm 76mm 7 3 4 197 6 165 8 203 12 318 19 483 32 826 171 4 438 63 4 171 81 4 210 3 89 5 133 93 4 248 5 140 33 4 95 21 4 57 6 152 Total take out dimension for Fully Assembled to DDX Valve w Control Valve Configurations 2 207 32 21 2 3 1727 32 76 mm N A 18 ...

Page 19: ... be clear and clean at the proper flow rate When closed a total water shut off must be observed 3 The valve must be inspected at least monthly for cracks corrosion leakage etc and cleaned repaired or re placed or replaced as necessary 4 At least annually the valve diaphragms and seats must be inspected and if necessary repaired or replaced WARNING CLOSE SYSTEM CONTROL VALVE TURN OFF POWER SUPPLY A...

Page 20: ...ated or new data EG Printed in USA 03 10 P N 9999970333 Reliable For Complete Protection Reliable offers a wide selection of sprinkler components Following are some of the many precision madeReliableproductsthatguardlifeandpropertyfromfirearoundtheclock Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry a...

Reviews: