General Description

Double Interlock Preaction Systems are designed for

water-sensitive areas that require the maximum protec-
tion from inadvertent water flow into the sprinkler system
piping. A refrigerated area is an example of this type of
water sensitive environment.

To flow water into a Type D Double Interlock Preaction

System, two events must take place. A fire detection de-
vice must operate, and the low air pressure switch must
be operated by the loss of system air pressure (sprinkler
operation). These two signals must coexist at the releas-
ing control panel, which only then will energize the nor-
mally closed solenoid valve (175 psi (12,1 bar) or 250 psi
(17,2 bar) rated), causing water flow into the system.

These Systems utilize fire detection devices and sys-

tem air pressure as separate zones (inputs) to a
cross-zoned releasing control panel. The solenoid re-
leasing valve remains closed until energized by the re-
leasing control panel. This will occur only when both a fire
detection device is operated and the low air pressure
switch has detected sufficient loss of system air pressure
(sprinkler operation).

In the event that the system piping is ruptured, or a

sprinkler head is accidentally opened, the low air pres-
sure switch will operate and an alarm will sound. The
Model DDX Deluge Valve, however, will not be released to
flow water since the solenoid valve remains closed due to
the cross-zoned control panel configuration. The same
end result would occur if a fire detection device were
falsely operated. The control panel will activate an alarm,
however again, the Model DDX Deluge Valve will not flow
water due to the cross-zoned control panel configuration.

This requirement for both a detector to operate and the

loss of system air pressure before the Model DDX Deluge
Valve releases water into a preaction system assures
maximum protection against inadvertent water flow be-
fore a sprinkler is open. Double interlock preaction sys-
tems are primarily used to protect refrigerated areas
where accidental water release before a sprinkler is

opened can cause ice blockage, resulting in an inopera-
tive sprinkler system and substantial property damage.

At the heart of Reliable’s Type D Double Interlock

Preaction System is the Model DDX Deluge Valve. This
Deluge

Valve

is

a

hydraulically

operated,

straight-through-design, differential-type valve (see Fig.
1). System maintenance is simplified since priming water
is not required and the Deluge Valve can be reset exter-
nally without cover removal. This is accomplished by
pushing in and turning the external reset knob at the rear
of the Deluge Valve (see Fig. 1). This feature provides a
significant system-restoration time advantage

The Reliable Type D Double Interlock Preaction Sys-

tem trim set (see Fig. 2) provides all of the necessary
equipment for connections to the Model DDX Deluge
Valve’s pushrod chamber inlet and outlet ports, the 1

1

4

(30mm) main drain, alarm devices, air supply, water sup-
ply, and required pressure gauges. This trim set is avail-
able in individual parts, in time-saving, segmentally
assembled kit forms, or fully assembled to the Model DDX
Deluge Valve (with or without a control valve).

Listings & Approvals

Reliable Type D 2” (50mm), 2

1

2

” (65mm), 3" (80mm)

and 76mm Double Interlock Preaction Systems are Fac-
tory Mutual Approved Refrigerated Area Sprinkler Sys-
tems for use in refrigerated rooms or buildings.
Refrigerated area sprinkler systems are FM Approved as
complete systems. Systems are FM approved for use
with thermal detectors and Class A detector wiring only.

Reliable Type D 2” (50mm), 2

1

2

” (65mm), 3" (80mm)

and 76mm Double Interlock Preaction Systems are Listed
by Underwriters Laboratories, Inc. and UL certified for
Canada (cULus) as Special System Water Control Valves
– Double Interlock Type (VLJH) category.

The NYC acceptance number for this system is MEA

258-93-E.

The Reliable Type D Double Interlock Preaction Sys-

tem is UL Listed and FM Approved only when used with
the trim components shown in Fig. 2.

2.

Fig. 1

Summary of Contents for Double Interlock Preaction System D

Page 1: ...mm 3 80mm 76mm Sizes Instructions for Installation Operation Care and Maintenance 10 PSI 0 7 bar Pneumatic Supervising Pressure With Electric Pneumatic Actuation Controlled by a Cross Zoned Releasing Control Panel Type D System Bulletin 737 Rev B Available with 175 psi 12 1 bar or 250 psi 17 2 bar Rated Solenoid Valve Externally Resettable Clapper One Main Drain ...

Page 2: ...rinkler is open Double interlock preaction sys tems are primarily used to protect refrigerated areas where accidental water release before a sprinkler is opened can cause ice blockage resulting in an inopera tive sprinkler system and substantial property damage At the heart of Reliable s Type D Double Interlock Preaction System is the Model DDX Deluge Valve This Deluge Valve is a hydraulically ope...

Page 3: ...Fig 2 3 ...

Page 4: ...odel B Manual Emergency Station 1 13 78653004 Valve Caution Station 1 14 98048015 Reducer 2 x 1 PVC 1 15 98048022 Bushing Reducer x 2 16 96816902 Valve Check In Line 1 17 92056705 Elbow Connector 3 8 Tube x NPT 1 18 6304000100 Pressure Maintenance Device Model A2 1 19 98050004 Drain Cup PVC 1 20 98174400 Street Elbow 2 21 98174408 Street Elbow 1 22 98174414 Elbow 1 1 23 98174403 Elbow 1 1 24 98174...

Page 5: ...tlet to the alarm devices After system shutdown resetting the Model DDX De lugeValveisquitesimple Doingsoonlyrequirespushing 5 in and turning the reset knob at the rear of the valve see Fig 1 The external reset feature of the Model DDX De luge Valve provides a means for simple economical sys tem testing which is one essential facet of a good maintenance program The external reset feature does not ...

Page 6: ...rs In addition to the hydrostatic tests described above dry pipe and double interlock preaction systems require an additional low pressure air test In some cases hydrostatic testing in accordance with the NFPA 13 requirements noted above will result in pressures that exceed the working pressure of the valve and trim kit for the two hour test period Thevalveandapplicabletrimkithavebeentested ap pro...

Page 7: ...Fig 4 7 ...

Page 8: ...ush rod and spring assembly with diaphragm seal secured to the casting through a push rod guide constructed of a syn thetic engineering plastic to resist corrosion Casting shall have a bleeder hole located on the pushrod chamber for air water leakage indication Trip ratio shall be approxi mately a 3 1 force differential Deluge valve shall be of the straight through design to minimize friction loss...

Page 9: ...ar System control valve shall be a 2 50 mm Nibco KG 505 w 8 Ball Valve 21 2 65 mm 3 80 mm Nibco GD 4765 8N Butterfly Valve Detection System To initiate actuation of the preaction system s deluge valve a supplemental electric detection system shall be provided Insert applicable product specification Releasing Control Panel A releasing control panel shall be used to operate the preaction system The ...

Page 10: ...losethe globevalvecontrollingsys tem air pressure in the Model A 2 Pressure Maintenance Device 2 Closethepushrodchambersupplyvalve valveA Fig 6 3 Openthemaindrainvalve valveB Fig 6 anddrainsys tem 4 Open all drain valves and vents at low points throughout thesystem closingthemwhenflowofwaterhasstopped Open valve D Fig 6 5 Note The above steps accomplish the relieving of pres sure in the pushrod ch...

Page 11: ...ke sure that valve G Fig 6 is open Push in on the plunger to be sure the ball check is off its seat If no water appears the Deluge Valve s water seat is tight Inspect the bleed hole see Fig 5 ontheundersideofthepushrodchamberforleak age 5 System pneumatic pressure check that system air pressure is between 7 and 10 psi 0 5 bar 0 7 bar Check the Model A 2 Pressure Maintenance Device for leakage and ...

Page 12: ...8 95276006 Diaphragm 1 19 95306268 Clip Retaining 3 8 Shaft 4 20 95406007 O Ring 114 1 21 95406024 O Ring 912 2 22 95406407 O Ring 014 1 23 95406410 O Ring 150 1 24 95406411 O Ring 147 1 25 95506003 Pushrod 1 26 95606114 Screw Socket Head Ø 20 x 5 8 6 27 95606127 Screw Ø 3 8 16 x Socket Cap Flat Head 1 28 95606133 Screw Cap 6 32 x SS 1 29 96016003 Seat Machined 1 30 96206003 Pin Hinge 1 31 9621600...

Page 13: ... ball drip valve E Fig 6 If system air is leaking out the ball drip valve the prob lem is either damage to the airside of the Model DDX DelugeValve ssealfaceplatesubassembly 8 Fig 5 seat 29 Fig 5 ortheupperseatO ring 23 Fig 5 If supply water is leaking out the ball drip valve the prob lemcouldbecausedbydamagetotheModelDDXDe luge Valve s seal faceplate sub assembly 8 Fig 5 seat 29 Fig 5 or lower se...

Page 14: ...14 Fig 6 ...

Page 15: ...stallationtorqueof15foot pounds Set uptheModelDDXDelugeValveasperthesection Re settingtheTypeDDoubleInterlock PreactionSystem 175 psi 12 1 bar Rated Solenoid Valve 250 psi 17 2 bar Rated Solenoid Valve 175 psi 12 1 bar Rated Solenoid Valve 250 psi 17 2 bar Rated Solenoid Valv UL FM Approved Pressure Switch ULC Listed Pressure Switch Ordering Information Specify Valve Model Size 2 50mm Model DDX De...

Page 16: ...sing Control Panel C Model PFC 4410 RC Potter 5403550 Reliable 700 Batteries 12 VDC 12 AMP Hours 90 Hours Backup FM 12 VDC 7 AMP Hours 60 Hours Backup Optional Accessories CA2Z Class A Wiring Module for Initiating Circuits CAM Class A Wiring Module for Indicating Circuits ARM 1 ARM 2 Auxiliary Relay Module RA 4410 RC Remote Annunciator 7 Alarm Annunciator A Model SSM24 8 24 VDC Polarized Bell Reli...

Page 17: ...17 Fig 7 ...

Page 18: ... K L M N P Q R 2 50mm 2 65mm 3 80mm 76mm 7 3 4 197 6 165 8 203 12 318 19 483 32 826 171 4 438 63 4 171 81 4 210 3 89 5 133 93 4 248 5 140 33 4 95 21 4 57 6 152 Total take out dimension for Fully Assembled to DDX Valve w Control Valve Configurations 2 207 32 21 2 3 1727 32 76 mm N A 18 ...

Page 19: ... be clear and clean at the proper flow rate When closed a total water shut off must be observed 3 The valve must be inspected at least monthly for cracks corrosion leakage etc and cleaned repaired or re placed or replaced as necessary 4 At least annually the valve diaphragms and seats must be inspected and if necessary repaired or replaced WARNING CLOSE SYSTEM CONTROL VALVE TURN OFF POWER SUPPLY A...

Page 20: ...ated or new data EG Printed in USA 03 10 P N 9999970333 Reliable For Complete Protection Reliable offers a wide selection of sprinkler components Following are some of the many precision madeReliableproductsthatguardlifeandpropertyfromfirearoundtheclock Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry a...

Reviews: