background image

6.

The Model B Manual Emergency Station (see Fig. 3) is

also included in the Reliable Type D Double Interlock
Preaction System trim set. It consists of an aluminum
nameplate mechanically attached to a ball valve. The
valve handle in its OFF position is guarded against acci-
dental turning to the ON position (and system discharge)
by a nylon cable tie provided with each trim kit. The cable
tie is inserted, as shown in Fig. 3, after the system has
been restored for operation. The nylon cable tie is de-
signed to allow, in case of an emergency, forceful turning
of the valve handle to the ON position. As an alternative to
the Model B Hydraulic Manual Emergency Station, the
Model A Hydraulic Manual Emergency Pull Box (see Reli-
able Bulletin 506) is also available and can be provided as
an option.

Whenever ambient temperature conditions are high,

the water temperature in the Model DDX Deluge Valve’s
pushrod chamber could possibly increase, thereby in-
creasing the pressure in the chamber to values exceed-
ing the rated pressure of the system. In an indoor
installation where standard room temperatures are ex-
ceeded, a pressure relief kit may be needed. Pressure re-
lief kit, P/N 6503050001, can be installed into the pushrod
chamber’s releasing line to limit the pressure to 175 psi
(12,1 bar).

Pressurizing Line Connection

The water supply for the push-rod chamber must be

provided by connection of its inlet pressurizing line to the
water supply piping. Pressurizing lines for multiple Model
DDX Deluge Valve push-rod chambers must never be
manifolded together, having only a single tap on the water
supply piping. Each Model DDX Deluge Valve must have
its own push-rod chamber pressurizing line connection.
This connection must be made on the supply side of the
main water supply control valve. This can be accom-
plished by:

• Using a tapped connection directly below or next to

the main water supply control valve using a welded
outlet or the appropriate mechanical fittings. A
grooved-end outlet coupling is one way to achieve
this (see Fig. 2); or

• Using a water supply control valve that has an avail-

able threaded (NPT) supply-side tap design to allow
for a direct water supply connection to the Model DDX
Deluge Valve’s push-rod chamber.

Caution:

Reliable’s DDX valve is designed with an inlet

restriction built into the pushrod chamber. It is important
not to introduce additional restrictions into the direct wa-
ter supply connection or the discharge from the pushrod
chamber by installing additional valves or improperly in-
stalling the copper lines used in the trim of the valve.

Hydrostatic Testing of DDX Valves and DDX
Systems

As required by NFPA 13, fire sprinkler systems with

working pressures up to and including 150 psi are to be
hydrostatically tested at a water pressure of 200 psi and
maintain that pressure without loss for two hours. Fire
sprinkler systems with working pressures above 150 psi
are required to be hydrostatically tested at 50 psi above
the system working pressure and maintain that pressure
without loss for two hours. In addition to the hydrostatic
tests described above, dry pipe and double interlock
preaction systems require an additional low pressure air

test. In some cases, hydrostatic testing (in accordance
with the NFPA 13 requirements noted above) will result in
pressures that exceed the working pressure of the valve
and trim kit for the two-hour test period.

The valve and applicable trim kit have been tested, ap-

proved and listed under these conditions and as such, hy-
drostatic testing in accordance with NFPA 13 is
acceptable. In addition, the clapper can remain in the
closed position and the trim kit need not be isolated, as
each has been designed to withstand hydrostatic testing
as required by NFPA 13.

Hydrostatically testing the valve and trim to pressures

higher than their rating is limited to the hydrostatic test as
referenced by NFPA 13. It does not address the occur-
rence(s) of a “water hammer” effect, which can indeed
damage the valve. A “water hammer” in the water supply
piping of the valve can create pressures in excess of the
rated pressure and should be avoided by all necessary
means. This condition may be created from improper fire
pump settings, underground construction work, or an im-
proper venting of trapped air in the water supply piping.

System Design Considerations

The automatic sprinklers, air compressor, releasing

devices, electric releasing control equipment, fire detec-
tion devices, manual pull stations, and signaling devices
which are utilized with the Type D Double Interlock
Preaction System must be UL or ULC Listed or FM Ap-
proved, as applicable.

Factory Mutual requires that detection devices in re-

frigerated areas be of the fixed temperature type. In addi-
tion, they must have a temperature rating lower than that
of the sprinklers and preferably, as low as possible for the
given ambient conditions.

The Deluge Valve, and all interconnecting piping must

be located in a readily visible and accessible location and
in an area that can be maintained at a minimum tempera-
ture of 40°F (4°C).

Note:

Heat tracing is not permitted.

Pendent sprinklers, other than dry pendents, used on

preaction systems shall be installed on return bends per
NFPA 13.

The solenoid valve is operated and supervised by the

electrical releasing/control panel. Details on the electrical
portion of this system can be found in Reliable Bulletin
700, “Special Hazards & Special Systems.”

System Air Pressure Requirements

In accordance with NFPA 13, double interlock

preaction systems require a minimum of 7 psi (0,5 bar)
pneumatic pressure to supervise the sprinkler system.
The Model A-2 Pressure Maintenance Device is used to
maintain the system pneumatic pressure between 7 and
10 psi (0,5 and 0,7 bar) where a dry nitrogen gas supply or
a clean, dependable, and continuous (24 hours per day, 7
days per week) compressed air source is available.

To adjust the system pneumatic pressure between 7

and 10 psi (0,5 and 0,7 bar) refer to Reliable Bulletin 251.
The low air pressure alarm switch (Item #5, Fig. 2) is fac-
tory set to operate between 5 and 6 psi (0,3 and 0,4 bar)
with decreasing pressure. If necessary, adjustments can
be made by following the manufacturer’s adjustment pro-
cedure as described in the installation and maintenance
instructions enclosed with the switch.

Summary of Contents for Double Interlock Preaction System D

Page 1: ...mm 3 80mm 76mm Sizes Instructions for Installation Operation Care and Maintenance 10 PSI 0 7 bar Pneumatic Supervising Pressure With Electric Pneumatic Actuation Controlled by a Cross Zoned Releasing Control Panel Type D System Bulletin 737 Rev B Available with 175 psi 12 1 bar or 250 psi 17 2 bar Rated Solenoid Valve Externally Resettable Clapper One Main Drain ...

Page 2: ...rinkler is open Double interlock preaction sys tems are primarily used to protect refrigerated areas where accidental water release before a sprinkler is opened can cause ice blockage resulting in an inopera tive sprinkler system and substantial property damage At the heart of Reliable s Type D Double Interlock Preaction System is the Model DDX Deluge Valve This Deluge Valve is a hydraulically ope...

Page 3: ...Fig 2 3 ...

Page 4: ...odel B Manual Emergency Station 1 13 78653004 Valve Caution Station 1 14 98048015 Reducer 2 x 1 PVC 1 15 98048022 Bushing Reducer x 2 16 96816902 Valve Check In Line 1 17 92056705 Elbow Connector 3 8 Tube x NPT 1 18 6304000100 Pressure Maintenance Device Model A2 1 19 98050004 Drain Cup PVC 1 20 98174400 Street Elbow 2 21 98174408 Street Elbow 1 22 98174414 Elbow 1 1 23 98174403 Elbow 1 1 24 98174...

Page 5: ...tlet to the alarm devices After system shutdown resetting the Model DDX De lugeValveisquitesimple Doingsoonlyrequirespushing 5 in and turning the reset knob at the rear of the valve see Fig 1 The external reset feature of the Model DDX De luge Valve provides a means for simple economical sys tem testing which is one essential facet of a good maintenance program The external reset feature does not ...

Page 6: ...rs In addition to the hydrostatic tests described above dry pipe and double interlock preaction systems require an additional low pressure air test In some cases hydrostatic testing in accordance with the NFPA 13 requirements noted above will result in pressures that exceed the working pressure of the valve and trim kit for the two hour test period Thevalveandapplicabletrimkithavebeentested ap pro...

Page 7: ...Fig 4 7 ...

Page 8: ...ush rod and spring assembly with diaphragm seal secured to the casting through a push rod guide constructed of a syn thetic engineering plastic to resist corrosion Casting shall have a bleeder hole located on the pushrod chamber for air water leakage indication Trip ratio shall be approxi mately a 3 1 force differential Deluge valve shall be of the straight through design to minimize friction loss...

Page 9: ...ar System control valve shall be a 2 50 mm Nibco KG 505 w 8 Ball Valve 21 2 65 mm 3 80 mm Nibco GD 4765 8N Butterfly Valve Detection System To initiate actuation of the preaction system s deluge valve a supplemental electric detection system shall be provided Insert applicable product specification Releasing Control Panel A releasing control panel shall be used to operate the preaction system The ...

Page 10: ...losethe globevalvecontrollingsys tem air pressure in the Model A 2 Pressure Maintenance Device 2 Closethepushrodchambersupplyvalve valveA Fig 6 3 Openthemaindrainvalve valveB Fig 6 anddrainsys tem 4 Open all drain valves and vents at low points throughout thesystem closingthemwhenflowofwaterhasstopped Open valve D Fig 6 5 Note The above steps accomplish the relieving of pres sure in the pushrod ch...

Page 11: ...ke sure that valve G Fig 6 is open Push in on the plunger to be sure the ball check is off its seat If no water appears the Deluge Valve s water seat is tight Inspect the bleed hole see Fig 5 ontheundersideofthepushrodchamberforleak age 5 System pneumatic pressure check that system air pressure is between 7 and 10 psi 0 5 bar 0 7 bar Check the Model A 2 Pressure Maintenance Device for leakage and ...

Page 12: ...8 95276006 Diaphragm 1 19 95306268 Clip Retaining 3 8 Shaft 4 20 95406007 O Ring 114 1 21 95406024 O Ring 912 2 22 95406407 O Ring 014 1 23 95406410 O Ring 150 1 24 95406411 O Ring 147 1 25 95506003 Pushrod 1 26 95606114 Screw Socket Head Ø 20 x 5 8 6 27 95606127 Screw Ø 3 8 16 x Socket Cap Flat Head 1 28 95606133 Screw Cap 6 32 x SS 1 29 96016003 Seat Machined 1 30 96206003 Pin Hinge 1 31 9621600...

Page 13: ... ball drip valve E Fig 6 If system air is leaking out the ball drip valve the prob lem is either damage to the airside of the Model DDX DelugeValve ssealfaceplatesubassembly 8 Fig 5 seat 29 Fig 5 ortheupperseatO ring 23 Fig 5 If supply water is leaking out the ball drip valve the prob lemcouldbecausedbydamagetotheModelDDXDe luge Valve s seal faceplate sub assembly 8 Fig 5 seat 29 Fig 5 or lower se...

Page 14: ...14 Fig 6 ...

Page 15: ...stallationtorqueof15foot pounds Set uptheModelDDXDelugeValveasperthesection Re settingtheTypeDDoubleInterlock PreactionSystem 175 psi 12 1 bar Rated Solenoid Valve 250 psi 17 2 bar Rated Solenoid Valve 175 psi 12 1 bar Rated Solenoid Valve 250 psi 17 2 bar Rated Solenoid Valv UL FM Approved Pressure Switch ULC Listed Pressure Switch Ordering Information Specify Valve Model Size 2 50mm Model DDX De...

Page 16: ...sing Control Panel C Model PFC 4410 RC Potter 5403550 Reliable 700 Batteries 12 VDC 12 AMP Hours 90 Hours Backup FM 12 VDC 7 AMP Hours 60 Hours Backup Optional Accessories CA2Z Class A Wiring Module for Initiating Circuits CAM Class A Wiring Module for Indicating Circuits ARM 1 ARM 2 Auxiliary Relay Module RA 4410 RC Remote Annunciator 7 Alarm Annunciator A Model SSM24 8 24 VDC Polarized Bell Reli...

Page 17: ...17 Fig 7 ...

Page 18: ... K L M N P Q R 2 50mm 2 65mm 3 80mm 76mm 7 3 4 197 6 165 8 203 12 318 19 483 32 826 171 4 438 63 4 171 81 4 210 3 89 5 133 93 4 248 5 140 33 4 95 21 4 57 6 152 Total take out dimension for Fully Assembled to DDX Valve w Control Valve Configurations 2 207 32 21 2 3 1727 32 76 mm N A 18 ...

Page 19: ... be clear and clean at the proper flow rate When closed a total water shut off must be observed 3 The valve must be inspected at least monthly for cracks corrosion leakage etc and cleaned repaired or re placed or replaced as necessary 4 At least annually the valve diaphragms and seats must be inspected and if necessary repaired or replaced WARNING CLOSE SYSTEM CONTROL VALVE TURN OFF POWER SUPPLY A...

Page 20: ...ated or new data EG Printed in USA 03 10 P N 9999970333 Reliable For Complete Protection Reliable offers a wide selection of sprinkler components Following are some of the many precision madeReliableproductsthatguardlifeandpropertyfromfirearoundtheclock Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry a...

Reviews: