background image

8

519FG09A

reset feature does not, however, eliminate another important 
facet of good maintenance, namely, periodic cleaning and 
inspection of the internal valve parts.

In the event that water builds up inside the valve due to 

condensate from the air supply system or water left inside 
from valve system testing, a drain is available for venting. 
After closing the main supply valve, a small valve over the 
drain cup can be opened slightly until the water inside the 
valve body and the main pipe column has drained. See the 
section titled “Draining Excess/Condensate Water From 
System” in this bulletin for the detailed procedure.

The Model B Manual Emergency Station (see Fig. 4) is also 

included in the Reliable Type D Double Interlock Preaction 
System trim sets. It consists of an aluminum nameplate 
mechanically attached to a ball valve. The valve handle in its 
OFF position is guarded against accidental turning to the ON 
position (and system discharge) by a nylon cable tie provided 
with each trim kit. The cable tie is inserted, as shown in 
Fig. 4, after the system has been restored for operation. The 
nylon cable tie is designed to allow, in case of an emergency, 
forceful turning of the valve handle to the ON position. As 
an alternative to the Model B Hydraulic Manual Emergency 
Station, the Model A Hydraulic Manual Emergency Pull 
Box (see Reliable Bulletin 506) is also available and can be 
provided as an option.

Whenever ambient temperature conditions are high, the 

water temperature in the Model DDX Deluge Valve’s pushrod 
chamber could possibly increase, thereby increasing the 
pressure in the chamber to values exceeding the rated 
pressure of the system. In an indoor installation where 
standard room temperatures are exceeded, a pressure relief 
kit may be needed. Pressure relief kit, P/N 6503050001, can 
be installed into the pushrod chamber’s releasing line to limit 
the pressure to 250 psi (17.2 bar).

Reliable Model DDX Deluge Valve with associated Type 

D Double Interlock Preaction Trims sizes 2" (50 mm), 2-

1

/

2

(65 mm), 76 mm, 3" (80 mm), 4" (100 mm), 165 mm, 6" 
(150 mm) and 8" (200 mm) are rated for use at a minimum 
water supply pressure of 20 psi (1.4 bar) and a maximum 
water supply pressure of 250 psi (17.2 bar) for 2" (50 mm), 
2-

1

/

2

" (65 mm), 3" (80 mm), 76 mm and 8" (200 mm) valve 

sizes and 300 psi (20.7 bar) for 4" (100 mm), 6" (150 mm) 
and 165 mm valve sizes. Water supplied to the inlet of the 
valve and to the push rod chamber must be maintained 
between 40 °F (4 °C) and 140 °F(60 °C).

Pressurizing Line Connection

The water supply for the push-rod chamber must be 

provided by connection of its inlet pressurizing line to the 
water supply piping. 

Pressurizing lines for multiple Model 

DDX Deluge Valve push-rod chambers must never be 
manifolded together, having only a single tap on the 
water supply piping. 

Each Model DDX Deluge Valve must 

have its own push-rod chamber pressurizing line connection.

This connection must be made on the supply side of the 

water supply control valve (see Fig. 2 or Fig. 3). This can be 
accomplished by:

•  Using a tapped connection directly below or next to 

the main water supply control valve using a welded 
outlet or the appropriate mechanical fittings. A 
grooved-end outlet coupling is one way to achieve 
this; or

•  Using a water supply control valve that has an 

available threaded (NPT) supply-side tap design to 
allow for a direct water supply connection to the 
Model DDX Deluge Valve’s push-rod chamber.

Caution:

 

Reliable’s DDX valve is designed with an inlet 

restriction built into the pushrod chamber. It is important 
not to introduce additional restrictions into the direct 
water supply connection or the discharge from the 
pushrod chamber by installing additional valves or 
improperly installing the copper lines used in the trim of 
the valve.

Hydrostatic Testing of DDX 

Valves and DDX Systems

As required by NFPA 13, fire sprinkler systems with working 

pressures up to and including 150 psi are to be hydrostatically 
tested at a water pressure of 200 psi and maintain that 
pressure without loss for two hours. Fire sprinkler systems 
with working pressures above 150 psi are required to be 
hydrostatically tested at 50 psi above the system working 
pressure and maintain that pressure without loss for two 

Fig. 4

MODEL B HYDRAULIC MANUAL 

EMERGENCY STATION

PLASTIC TUBING

NYLON TIE

TO DRIP CUP

Summary of Contents for DDX Type D

Page 1: ...mm 76 mm 4 100 mm 6 150 mm 165 mm 8 200 mm Instructions for Installation Operation Care and Maintenance 7 to 10 psi 0 5 to 0 7 bar Pneumatic Supervising Pressure with Electric Electric Actuation Contr...

Page 2: ...and required pressure gauges This trim set is available in individual loose parts in time saving segmented assembled kit forms or fully assembled to the Model DDX Deluge Valve with or without a contr...

Page 3: ...PPER IN LATCHED POSITION CLAPPER IN CLOSED POSITION ALARM PORT TEST PORT DRAIN PORT FROM SUPPLY LEVER PUSH ROD PUSH ROD CHAMBER OUTLET PUSH ROD CHAMBER INLET RESTRICTION DDX EXTERNAL RESET KNOB PUSH R...

Page 4: ...ONTROL BUTTERFLY VALVE ADJOINING COUPLINGS REDUCING BUSHING AND TUBING CONNECTOR ARE INCLUDED IN THE FULLY ASSEMBLED TO MODEL DDX DELUGE VALVE WITH CONTROL VALVE TRIM CONFIGUARTION ONLY REFER TO PAGE...

Page 5: ...NPT 1 Item No Part No Description Qty Galvanized Brass Black Pipe 26 96686722 96686722 96686722 Copper Tubing 3 8 OD x 2 ft 1 27 94616918 94616918 94616918 Type D Double Interlock Nameplate 1 28 98050...

Page 6: ...RFLY VALVE ADJOINING COUPLINGS REDUCING BUSHING AND TUBING CONNECTOR ARE INCLUDED IN THE FULLY ASSEMBLED TO MODEL DDX DELUGE VALVE WITH CONTROL VALVE TRIM CONFIGUARTION ONLY REFER TO PAGE 26 27 OF THI...

Page 7: ...1 4 NPT 1 25 92056704 92056704 92056704 Connector Elbow 3 8 ID Tube x 1 2 NPT 1 Item No Part No Description Qty Galvanized Brass Black Pipe 26 96686722 96686722 96686722 Copper Tubing 3 8 OD x 2 ft 1...

Page 8: ...mm 6 150 mm and 8 200 mm are rated for use at a minimum water supply pressure of 20 psi 1 4 bar and a maximum water supply pressure of 250 psi 17 2 bar for 2 50 mm 2 1 2 65 mm 3 80 mm 76 mm and 8 200...

Page 9: ...a clean dependable and continuous 24 hours a day 7 days a week compressed air source is available To adjust the system pneumatic pressure between 7 and 10 psi 0 5 and 0 7 bar refer to Reliable Bullet...

Page 10: ...mm 4 100 mm 165 mm 6 150 mm 8 200 mm Reliable Model DDX Deluge Valve Bulletin 519 Valve trim shall be Type D electric electric release trim consisting of the following components Hydraulic trim to be...

Page 11: ...W MANUAL EMERGENCY STATION MODEL BNG 1 SUPERVISORY CIRCUIT AUXILIARY DRY ALARM CONTACTS AUXILIARY DRY TROUBLE CONTACTS AUXILIARY DRY SUPERVISORY CONTACTS MANUAL DUMP CIRCUIT EOL RESISTOR 5 1K 1 2 W E...

Page 12: ...oned operation requiring both a detection device input and a low air pressure switch input sprinkler operation to energize the solenoid valve causing the deluge valve to operate Releasing control pane...

Page 13: ...Groove Groove 34 lb 15 kg 4 100 mm Groove Groove 64 lb 29 kg Flange Groove 79 lb 36 kg Flange Flange 92 lb 42 kg 6 150 mm 165 mm Groove Groove 95 lb 43 kg Flange Groove 122 lb 56 kg Flange Flange 138...

Page 14: ...73 Fig 2 for the 2 50 mm 2 1 2 65 mm 76 mm and 3 80 mm valve sizes 1 4 nipple 36 Fig 3 1 4 elbow 27 Fig 3 1 4 nipple 37 Fig 3 3 way valve 70 Fig 3 and the gauge 72 Fig 3 for the 4 100 mm 165 mm and 6...

Page 15: ...that the Model B Manual Emergency Station valve D Fig 9 is secured in the OFF position with the appropriate nylon tie 56 Fig 2 OR 56 Fig 3 see Fig 4 Inspection and Testing Refer to Figs 2 3 7 8 9 1 Wa...

Page 16: ...80 mm valve sizes or the 2 main drain valve on the 4 100 mm 165 mm 6 150 mm and 8 200 mm valve sizes valve B Fig 9 Open the water column drain valve H Fig 9 Close the pushrod chamber supply valve A Fi...

Page 17: ...SCREW IN SEAT CONFIGURATION EXTERNAL RESET ASSEMBLY 24 42 UPPER SEAT O RING 25 42 LOWER SEAT O RING GAUGE PORT BLEED HOLE FROM SUPPLY ORIFICE TO RELEASING DEVICE SYSTEM AIR PORT ALARM PORT TEST PORT...

Page 18: ...Steel UNS S17400 16 95006414 94006412 95006410 95006410 Striker 1 Aluminum Bronze C95400 17 95106006 Piston 1 Stainless Steel CF8M 18 95276006 Diaphragm 1 EPDM Polyester 19 95306267 N A N A N A Retain...

Page 19: ...et Cap Screw 1 2 13x3 4 Stainless Steel UNS S31600 38 98604402 Plug 1 2 NPT 1 Steel 39 94616921 Knob Caution Label Not Shown 1 Polystyrene 40 91556922 Ball Chain 1 8 Not Shown Length is in inches 6 Ni...

Page 20: ...S44000 18 95106006 Piston 1 Stainless Steel CF8M 19 95200038 Socket Plug 3 8 18 NPT not shown 2 Steel 20 95506006 Pushrod 1 Stainless Steel UNS S30300 21 93916006 Pushrod Guide 1 Acetal 22 95306267 R...

Page 21: ...des Making sure the clapper is in the closed position see Fig 1 lift up and rotate the clapper seat sub assembly clockwise 90 degrees so that the lever side of the assembly is facing up towards the ou...

Page 22: ...t pressure by opening the 1 1 4 main drain valve on the 2 50 mm 2 1 2 65 mm 76 mm and 3 80 mm valve sizes or the 2 main drain valve on the 4 100 mm 165 mm 6 150 mm and 8 200 mm valve sizes valve B Fig...

Page 23: ...DRIP CUP MODEL DDX DELUGE VALVE ALARM TEST TO NON SILENCEABLE ALARM PRESSURE SWITCH REF NFPA 72 OUT IN WATER SUPPLY PRESSURE GAUGE WATER SUPPLY CONTROL VALVE FROM SUPPLY MODEL A 2 PRESSURE MAINTENANCE...

Page 24: ...DOUBLE INTERLOCK PREACTION SYSTEM AS THESE ARE NOT COMPATIBLE WITH THE MODEL A 2 PRESSURE MAINTENANCE DEVICE MODEL DDX DELUGE VALVE SOLENOID VALVE MODEL B HYDRAULIC EMERGENCY STATION TROUBLE ALARM ANU...

Page 25: ...03060049 6 168 mm Flg Flg ASME Class 150 Black 6103060046 ASME Class 150 Red 6103060047 ISO PN16 Red 6103060050 165 mm Grv Grv N A Red 6103060028 165 mm Flg Grv ASME Class 150 Red 6103060051 ISO PN16...

Page 26: ...Class 150 Red 6505A66226 N A ISO PN16 Red 6505A69226 8 200 mm Grv Grv N A Black 6505080226 6505080225 Red 6505A80226 6505A80225 8 200 mm Flg Flg ASME Class 150 Black 6505083226 N A ASME Class 150 Red...

Page 27: ...onal Accessories CA2Z Class A Wiring Module for Initiating Circuits CAM Class A Wiring Module for Indicating Circuits ARM 1 ARM 2 Auxiliary Relay Module RA 4410 RC Remote Annunciator 7 Alarm Annunciat...

Page 28: ...432 6 150 mm 165 mm 8 1 2 215 9 229 11 1 2 292 16 406 26 3 4 679 19 483 19 483 22 559 37 1 2 952 8 203 7 178 5 1 2 140 8 1 4 210 13 3 4 349 4 3 4 121 6 1 2 165 8 3 4 222 12 305 17 432 8 200 mm 8 1 2 2...

Page 29: ...RE TO CLOSE THE SYSTEM CONTROL VALVE TO AVOID UNINTENTIONAL OPERATION OF THE DELUGE VALVE 1 Inspections It is imperative that the system be inspected and tested in accordance with NFPA 25 on a regular...

Page 30: ...ing are some of the many precision made Reliable products that guard life and property from fire around the clock Reliable For Complete Protection Automatic sprinklers Flush automatic sprinklers Reces...

Reviews: