Owner’s Air supply

Supervisory air supply shall be provided by an owner 

supplied air system in conjunction with a [cULus Listed] 
automatic pressure maintenance device, capable of 
maintaining a constant system pressure regardless of 
pressure fluctuations in the compressed air source. 

Compressed Air Supply

Supervisory air supply shall be provided by an 

automatic tank-mounted air compressor

 sized 

(appropriate hp (kW)) for the capacity (volume) of the double 
interlock preaction system piping, and be capable of 
restoring normal air pressure in the system within the time 
limits specified by NFPA 13. Tank mounted compressor 
shall be a motor mounted, oil-less, piston compressor, 
including gauge, pressure switch, check valve, drain valve 
and safety relief valve. Single-phase motor shall have 
internal thermal protection.

Nitrogen

Nitrogen cylinders provided by an approved source shall 

provide the nitrogen supply. The nitrogen cylinder pressure 
shall be regulated and supervised through the use of nitrogen 
regulating device and low-pressure trim kit. This device shall 
consist of a brass, single stage pressure regulator, equipped 
with high pressure inlet and low pressure outlet gauges, and 

1

/

4

" copper connection tubing with galvanized 

3

/

4

" x 

1

/

4

reducer bushing. Optional: Low-pressure trim kit shall be 
included to monitor the regulated nitrogen supply pressure 
to provide a low-pressure supervisory alarm. This kit shall 
include a low-pressure switch with associated galvanized 
connection trim. Assembly shall be a Reliable Nitrogen 
Regulating Device. This device is to be used in conjunction 
with the Reliable Model A-2 Pressure Maintenance Device.

Optional System Accessories

System Control Valve

Preaction system control valve shall be a slow close, 

[cULus Listed] indicating butterfly type valve with a pre-
wired supervisory tamper switch assembly. The valve shall 
be rated for a working pressure of [300 psi (20.6 bar)]. 
System control valve shall be for a [2" (50 mm)] Gruvlok 
AN7722-3A Butterfly Valve or [2-

1

/

2

" (65 mm)] [3" (80 mm)] 

[4" (100 mm)] [6" (150 mm] [8" (200 mm] – Nibco GD-4865-
8N Butterfly Valve. 

Detection System

To initiate actuation of the preaction system’s deluge valve, 

a supplemental electric detection system shall be provided 
[Insert applicable product specification].

Releasing/Control Panel

A releasing/control panel shall be used to operate the 

preaction system. The releasing/control panel shall be a 
conventional, microprocessor-controlled panel containing 
two initiating device circuits, and waterflow and supervisory 
inputs. Output circuits shall include alarm, waterflow, 
supervisory, and releasing circuits. Mode of operation shall 
be set for cross zoned operation, requiring both a detection 
device input and a low air pressure switch input (sprinkler 
operation) to energize the solenoid valve, causing the deluge 

valve to operate. Releasing/control panel shall be equipped 
with a local tone alarm to annunciate loss of AC power, 
system trouble, circuit trouble, and low auxiliary DC power 
supply. Panel shall be [cULus Listed] [FM Approved] and 
be capable of providing power for compatible detectors 
and auxiliary devices used. Audible alarms shall be able to 
be silenced at releasing panel. Auxiliary DC power supply 
shall consist of (2) 12-volt lead acid batteries of the same 
ampere-hour rating, providing [60 hours – cULus Listed] [90 
hours – FM Approved]. Dry contacts shall be provided for 
remote annunciation of alarm, trouble, and supervisory panel 
signals. Main power supply to be a dedicated a 120 V ac / 
60 Hz circuit.

Waterflow Alarm Pressure Switch

Alarm pressure switch shall be provided to indicate water 

flow and provide a water flow alarm. Pressure switch shall be 
[cULus Listed] and of the bellows activated type enclosed in 
a weatherproof, NEMA 4 /4X rated enclosure incorporating 
tamper-resistant screws. There shall be two sets of SPDT 
(Form C) contacts rated at 10.0 A @ 125 /250 V ac and 2.5 A 
@ 6 / 12 / 24 V dc. The pressure switch shall have a maximum 
service pressure rating of 250 psi (17.2 bar) and shall be 
factory adjusted to operate at a pressure of 4 to 8 psi (0.27 
to 0.55 bar) with adjustment up to 15 psi (1.03 bar). Switch 
shall be provided with a 

1

/

2

" NPT male pressure connection. 

Waterflow alarm pressure switch shall be Potter PS10-2.

Technical Data

Reliable Double Interlock Type D Preaction Systems, with 

associated trim, size 2" (50 mm), 2-

1

/

2

" (65 mm), 76 mm, 3" 

(80 mm), 4" (100 mm), 165 mm, 6" (150 mm), 8" (200 mm) 
are rated for use at minimum water supply pressure of 20 psi 
(1.4 bar) and maximum supply pressure of 250 psi (17.2 bar) 
for 2" (50 mm), 

21

/

2

" (65 mm), 3" (80 mm), 76 mm and 8" 

(200 mm) valve sizes and 300 psi (20.7 bar) for 4" (100 mm), 
6" (150 mm) and 165 mm valve sizes. Water supplied to 
the inlet of the valve and to the pushrod chamber must be 
maintained between 40 °F (4 °C) and 140 °F (60 °C).

The following list of technical bulletins pertains to valves 

and devices that may be used in this preaction system:

Deluge Valve 

Reliable 518 / 519

Hydraulic Emergency 

Station (Model A)

Reliable 506

Solenoid Valve

Reliable 718

Mechanical Sprinkler Alarm

Reliable 612 / 613

Pressure Maintenance Device 

Reliable 254

Nitrogen Regulating Device

Reliable 254

Air Compressor 

Gast F-30

Releasing/Control Panel

Potter #5403550

Low Air Pressure 

Supervisory Switch

Potter 5400928

Waterflow Pressure Alarm Switch 

Potter 5400928

Model DDX Deluge Valve Description

1.  Rated working pressure:

Valve & System – 250 psi (17.2 bar) for 2" (50 mm), 
2-

1

/

2

" (65 mm), 3" (80 mm), 76 mm and 8" (200 mm) 

valve sizes and 300 psi (20.7 bar) for 4" (100 mm), 6" 
(150 mm) and 165 mm valve sizes.

Summary of Contents for DDX Type D

Page 1: ...mm 76 mm 4 100 mm 6 150 mm 165 mm 8 200 mm Instructions for Installation Operation Care and Maintenance 7 to 10 psi 0 5 to 0 7 bar Pneumatic Supervising Pressure with Electric Electric Actuation Contr...

Page 2: ...and required pressure gauges This trim set is available in individual loose parts in time saving segmented assembled kit forms or fully assembled to the Model DDX Deluge Valve with or without a contr...

Page 3: ...PPER IN LATCHED POSITION CLAPPER IN CLOSED POSITION ALARM PORT TEST PORT DRAIN PORT FROM SUPPLY LEVER PUSH ROD PUSH ROD CHAMBER OUTLET PUSH ROD CHAMBER INLET RESTRICTION DDX EXTERNAL RESET KNOB PUSH R...

Page 4: ...ONTROL BUTTERFLY VALVE ADJOINING COUPLINGS REDUCING BUSHING AND TUBING CONNECTOR ARE INCLUDED IN THE FULLY ASSEMBLED TO MODEL DDX DELUGE VALVE WITH CONTROL VALVE TRIM CONFIGUARTION ONLY REFER TO PAGE...

Page 5: ...NPT 1 Item No Part No Description Qty Galvanized Brass Black Pipe 26 96686722 96686722 96686722 Copper Tubing 3 8 OD x 2 ft 1 27 94616918 94616918 94616918 Type D Double Interlock Nameplate 1 28 98050...

Page 6: ...RFLY VALVE ADJOINING COUPLINGS REDUCING BUSHING AND TUBING CONNECTOR ARE INCLUDED IN THE FULLY ASSEMBLED TO MODEL DDX DELUGE VALVE WITH CONTROL VALVE TRIM CONFIGUARTION ONLY REFER TO PAGE 26 27 OF THI...

Page 7: ...1 4 NPT 1 25 92056704 92056704 92056704 Connector Elbow 3 8 ID Tube x 1 2 NPT 1 Item No Part No Description Qty Galvanized Brass Black Pipe 26 96686722 96686722 96686722 Copper Tubing 3 8 OD x 2 ft 1...

Page 8: ...mm 6 150 mm and 8 200 mm are rated for use at a minimum water supply pressure of 20 psi 1 4 bar and a maximum water supply pressure of 250 psi 17 2 bar for 2 50 mm 2 1 2 65 mm 3 80 mm 76 mm and 8 200...

Page 9: ...a clean dependable and continuous 24 hours a day 7 days a week compressed air source is available To adjust the system pneumatic pressure between 7 and 10 psi 0 5 and 0 7 bar refer to Reliable Bullet...

Page 10: ...mm 4 100 mm 165 mm 6 150 mm 8 200 mm Reliable Model DDX Deluge Valve Bulletin 519 Valve trim shall be Type D electric electric release trim consisting of the following components Hydraulic trim to be...

Page 11: ...W MANUAL EMERGENCY STATION MODEL BNG 1 SUPERVISORY CIRCUIT AUXILIARY DRY ALARM CONTACTS AUXILIARY DRY TROUBLE CONTACTS AUXILIARY DRY SUPERVISORY CONTACTS MANUAL DUMP CIRCUIT EOL RESISTOR 5 1K 1 2 W E...

Page 12: ...oned operation requiring both a detection device input and a low air pressure switch input sprinkler operation to energize the solenoid valve causing the deluge valve to operate Releasing control pane...

Page 13: ...Groove Groove 34 lb 15 kg 4 100 mm Groove Groove 64 lb 29 kg Flange Groove 79 lb 36 kg Flange Flange 92 lb 42 kg 6 150 mm 165 mm Groove Groove 95 lb 43 kg Flange Groove 122 lb 56 kg Flange Flange 138...

Page 14: ...73 Fig 2 for the 2 50 mm 2 1 2 65 mm 76 mm and 3 80 mm valve sizes 1 4 nipple 36 Fig 3 1 4 elbow 27 Fig 3 1 4 nipple 37 Fig 3 3 way valve 70 Fig 3 and the gauge 72 Fig 3 for the 4 100 mm 165 mm and 6...

Page 15: ...that the Model B Manual Emergency Station valve D Fig 9 is secured in the OFF position with the appropriate nylon tie 56 Fig 2 OR 56 Fig 3 see Fig 4 Inspection and Testing Refer to Figs 2 3 7 8 9 1 Wa...

Page 16: ...80 mm valve sizes or the 2 main drain valve on the 4 100 mm 165 mm 6 150 mm and 8 200 mm valve sizes valve B Fig 9 Open the water column drain valve H Fig 9 Close the pushrod chamber supply valve A Fi...

Page 17: ...SCREW IN SEAT CONFIGURATION EXTERNAL RESET ASSEMBLY 24 42 UPPER SEAT O RING 25 42 LOWER SEAT O RING GAUGE PORT BLEED HOLE FROM SUPPLY ORIFICE TO RELEASING DEVICE SYSTEM AIR PORT ALARM PORT TEST PORT...

Page 18: ...Steel UNS S17400 16 95006414 94006412 95006410 95006410 Striker 1 Aluminum Bronze C95400 17 95106006 Piston 1 Stainless Steel CF8M 18 95276006 Diaphragm 1 EPDM Polyester 19 95306267 N A N A N A Retain...

Page 19: ...et Cap Screw 1 2 13x3 4 Stainless Steel UNS S31600 38 98604402 Plug 1 2 NPT 1 Steel 39 94616921 Knob Caution Label Not Shown 1 Polystyrene 40 91556922 Ball Chain 1 8 Not Shown Length is in inches 6 Ni...

Page 20: ...S44000 18 95106006 Piston 1 Stainless Steel CF8M 19 95200038 Socket Plug 3 8 18 NPT not shown 2 Steel 20 95506006 Pushrod 1 Stainless Steel UNS S30300 21 93916006 Pushrod Guide 1 Acetal 22 95306267 R...

Page 21: ...des Making sure the clapper is in the closed position see Fig 1 lift up and rotate the clapper seat sub assembly clockwise 90 degrees so that the lever side of the assembly is facing up towards the ou...

Page 22: ...t pressure by opening the 1 1 4 main drain valve on the 2 50 mm 2 1 2 65 mm 76 mm and 3 80 mm valve sizes or the 2 main drain valve on the 4 100 mm 165 mm 6 150 mm and 8 200 mm valve sizes valve B Fig...

Page 23: ...DRIP CUP MODEL DDX DELUGE VALVE ALARM TEST TO NON SILENCEABLE ALARM PRESSURE SWITCH REF NFPA 72 OUT IN WATER SUPPLY PRESSURE GAUGE WATER SUPPLY CONTROL VALVE FROM SUPPLY MODEL A 2 PRESSURE MAINTENANCE...

Page 24: ...DOUBLE INTERLOCK PREACTION SYSTEM AS THESE ARE NOT COMPATIBLE WITH THE MODEL A 2 PRESSURE MAINTENANCE DEVICE MODEL DDX DELUGE VALVE SOLENOID VALVE MODEL B HYDRAULIC EMERGENCY STATION TROUBLE ALARM ANU...

Page 25: ...03060049 6 168 mm Flg Flg ASME Class 150 Black 6103060046 ASME Class 150 Red 6103060047 ISO PN16 Red 6103060050 165 mm Grv Grv N A Red 6103060028 165 mm Flg Grv ASME Class 150 Red 6103060051 ISO PN16...

Page 26: ...Class 150 Red 6505A66226 N A ISO PN16 Red 6505A69226 8 200 mm Grv Grv N A Black 6505080226 6505080225 Red 6505A80226 6505A80225 8 200 mm Flg Flg ASME Class 150 Black 6505083226 N A ASME Class 150 Red...

Page 27: ...onal Accessories CA2Z Class A Wiring Module for Initiating Circuits CAM Class A Wiring Module for Indicating Circuits ARM 1 ARM 2 Auxiliary Relay Module RA 4410 RC Remote Annunciator 7 Alarm Annunciat...

Page 28: ...432 6 150 mm 165 mm 8 1 2 215 9 229 11 1 2 292 16 406 26 3 4 679 19 483 19 483 22 559 37 1 2 952 8 203 7 178 5 1 2 140 8 1 4 210 13 3 4 349 4 3 4 121 6 1 2 165 8 3 4 222 12 305 17 432 8 200 mm 8 1 2 2...

Page 29: ...RE TO CLOSE THE SYSTEM CONTROL VALVE TO AVOID UNINTENTIONAL OPERATION OF THE DELUGE VALVE 1 Inspections It is imperative that the system be inspected and tested in accordance with NFPA 25 on a regular...

Page 30: ...ing are some of the many precision made Reliable products that guard life and property from fire around the clock Reliable For Complete Protection Automatic sprinklers Flush automatic sprinklers Reces...

Reviews: