13
2. Factory tested to a hydrostatic pressure of 500 psi
(34.5 bar) for 2" (50 mm), 2-
1
/
2
" (65 mm), 3" (80 mm),
76 mm and 8" (200 mm) valve sizes and 600 psi
(41.7 bar) for 4" (100 mm), 6" (150 mm) and 165 mm
valve sizes. (Valve only)
3. End and trim connections:
• ANSI/AWWA C606 grooved inlet and outlet
Nominal
Pipe Size
Outlet
Diameter
Groove
Diameter
Groove Width Outlet Face
to Groove
2" (50 mm)
2.375"
(60 mm)
2.250"
(57 mm)
11
/
32
"
(9.0 mm)
5
/
8
" (16 mm)
2-
1
/
2
" (65 mm)
2.875"
(73 mm)
2.720"
(69 mm)
11
/
32
"
(9.0 mm)
5
/
8
" (16 mm)
76 mm
3.000"
(76 mm)
2.845"
(72 mm)
11
/
32
"
(9.0 mm)
5
/
8
" (16 mm)
3" (80 mm)
3.500"
(89 mm)
3.344"
(85 mm)
11
/
32
"
(9.0 mm)
5
/
8
" (16 mm)
4" (100 mm)
4.500"
(114 mm)
4.334"
(110 mm)
3
/
8
" (9.5 mm)
5
/
8
" (16 mm)
165 mm
6.500"
(165 mm)
6.330"
(161 mm)
3
/
8
" (9.5 mm)
5
/
8
" (16 mm)
6" (150 mm)
6.625"
(168 mm)
6.455"
(164 mm)
3
/
8
" (9.5 mm)
5
/
8
" (16 mm)
8" (200 mm)
8.625"
(219 mm)
8.441"
(214 mm)
7
/
16
" (11 mm)
3
/
4
" (19 mm)
• Threaded openings Per ANSI B 2.1
• Flange Dimensions
Flange
Type:
Nominal
Pipe Size
Bolt
Circle
Diameter
Bolt Hole
Diameter
Flange
Outside
Diameter
Flange
Thickness
Number
of Bolts
ASME
B16.5
Class 150
4"
(100 mm)
7-
1
/
2
"
(191 mm)
3
/
4
"
(19 mm)
9"
(229 mm)
15
/
16
"
(24 mm)
8
ISO 7005-
2 PN16
4"
(100 mm)
7-
3
/
32
"
(180 mm)
3
/
4
"
(19 mm)
9"
(229 mm)
15
/
16
"
(24 mm)
8
ASME
B16.5
Class 150
6"
(150 mm)
9-
1
/
2
"
(241 mm)
7
/
8
"
(22 mm)
11"
(279 mm)
15
/
16
"
(24 mm)
8
ISO 7005-
2 PN16
6"
(150 mm)
9-
7
/
16
"
(240 mm)
29
/
32
"
(23 mm)
11"
(279 mm)
15
/
16
"
(24 mm)
8
ASME
B16.5
Class 150
8"
(200 mm)
11-
3
/
4
"
(298 mm)
7
/
8
"
(22 mm)
13-
1
/
2
"
(343 mm)
1"
(25.4 mm)
8
ISO 7005-
2 PN16
8"
(200 mm)
1-
15
/
8
"
(295 mm)
29
/
32
"
(23 mm)
13-
1
/
2
"
(343 mm)
1"
(25.4 mm)
12
4. Valve Exterior Color:
Valve Size
Color
2" (50 mm)
Black or Red
2-
1
/
2
" (65 mm)
Black or Red
76 mm
Red
3" (80 mm)
Black or Red
4" (100 mm)
Black or Red
165 mm
Red
6" (150 mm)
Black or Red
8" (200 mm)
Black or Red
5. Face to face dimensions:
Valve Size:
End Connection:
End to End:
2" (50 mm), 2-
1
/
2
"
(65 mm), 76 mm
& 3" (80 mm)
Groove/ Groove
12-
1
/
2
" (318 mm)
4" (100 mm)
Groove/ Groove
14" (356 mm)
Flange/ Groove
16" (406 mm)
Flange/ Flange
16" (406 mm)
6" (150 mm) & 165 mm
Groove/ Groove
16" (406 mm)
Flange/ Groove
19" (483 mm)
Flange/ Flange
19" (483 mm)
8" (200 mm)
Groove/ Groove
19-
3
/
8
" (492 mm)
Flange/ Flange
21-
1
/
4
" (540 mm)
6. Valve shipping weight:
Valve Size:
End Connection:
Weight:
2" (50 mm), 2-
1
/
2
"
(65 mm), 76 mm
& 3" (80 mm)
Groove/ Groove
34 lb (15 kg)
4" (100 mm)
Groove/ Groove
64 lb (29 kg)
Flange/ Groove
79 lb (36 kg)
Flange/ Flange
92 lb (42 kg)
6" (150 mm) & 165 mm
Groove/ Groove
95 lb (43 kg)
Flange/ Groove
122 lb (56 kg)
Flange/ Flange
138 lb (69 kg)
8" (200 mm)
Groove/ Groove
148 lb (67 kg)
Flange/ Flange
197 lb (90 kg)
7. Trim shipping weight:
Trim Configuration
2" (50 mm),
2‑
1
/
2
" (65 mm),
3" (80 mm)
& 76 mm
4" (100 mm),
6" (150 mm),
8" (200 mm)
& 165 mm
Type D Double Interlock
47 lb (21 kg)
52 lb (24 kg)
8. Friction loss (Expressed in equivalent length of Schedule
40 pipe, based on Hazen & Williams formula:
Valve Size:
Equivalent Length:
Cv
C = 120
C = 100
2" (50 mm)
4.4 ft (1.3 m)
3.1 ft (1.0 m)
101
2-
1
/
2
" (65 mm)
6.0 ft (1.8 m)
4.3 ft (1.3 m)
236
76 mm
7.7 ft (2.3 m)
5.5 ft (1.7 m)
241
3" (80 mm)
12.6 ft (3.8 m)
9.0 ft (2.7 m)
254
4" (100 mm)
14 ft (4.3 m)
10 ft (3.0 m)
469
165 mm
29.4 ft (9.0 m)
20.9 ft (6.4 m)
886
6" (150 mm)
29.4 ft (9.0 m)
20.9 ft (6.4 m)
886
8" (200 mm)
53.5 ft (16.3 m)
38.1 ft (11.6 m)
1516
9. Installation position: Vertical
Trim Descriptions
The Type D Double Interlock Preaction Trims for the Reliable
Model DDX Deluge Valve are arranged for rapid, easy, and
compact attachment, and serve as connection points to
Reliable Model C Mechanical Alarms and other devices.
The Double Interlock Type D Preaction System trim
configurations can be ordered as individual parts, in time-
saving segmentally assembled kit forms, or fully assembled
to the Model DDX Deluge Valve (with or without a control
valve).
Maintenance
Reliable Double Interlock Type D Preaction Systems
and associated equipment shall periodically be given a
thorough inspection and test. NFPA 25, Inspection, Testing
and Maintenance of Water Based Fire Protection Systems,
provides minimum maintenance requirements. System
components shall be tested, operated, cleaned, and
inspected at least annually, and parts replaced as required.
Type D Double Interlock Preaction Trim
Type D Double Interlock Preaction trim (see Figures 2 and
3) utilizes a normally closed/powered-open solenoid valve for
releasing the Deluge Valve. The solenoid valve used in the
assembly is available in both a 175 psi (12.1 bar) or 300 psi
(20.7 bar) rating.
Note:
In order for the solenoid valve to maintain Reliable’s
warranty it must remain sealed as it came from the factory.
If there are concerns about the valve’s internal components,