background image

13

2.  Factory tested to a hydrostatic pressure of 500 psi 

(34.5 bar) for 2" (50 mm), 2-

1

/

2

" (65 mm), 3" (80 mm), 

76 mm and 8" (200 mm) valve sizes and 600 psi 
(41.7 bar) for 4" (100 mm), 6" (150 mm) and 165 mm 
valve sizes. (Valve only)

3.  End and trim connections:

•  ANSI/AWWA C606 grooved inlet and outlet

Nominal 

Pipe Size

Outlet 

Diameter

Groove 

Diameter

Groove Width Outlet Face 

to Groove

2" (50 mm)

2.375" 

(60 mm)

2.250" 

(57 mm)

11

/

32

(9.0 mm)

5

/

8

" (16 mm)

2-

1

/

2

" (65 mm)

2.875" 

(73 mm)

2.720" 

(69 mm)

11

/

32

(9.0 mm)

5

/

8

" (16 mm)

76 mm

3.000" 

(76 mm)

2.845" 

(72 mm)

11

/

32

(9.0 mm)

5

/

8

" (16 mm)

3" (80 mm)

3.500" 

(89 mm)

3.344" 

(85 mm)

11

/

32

(9.0 mm)

5

/

8

" (16 mm)

4" (100 mm)

4.500" 

(114 mm)

4.334" 

(110 mm)

3

/

8

" (9.5 mm)

5

/

8

" (16 mm)

165 mm

6.500" 

(165 mm)

6.330" 

(161 mm)

3

/

8

" (9.5 mm)

5

/

8

" (16 mm)

6" (150 mm)

6.625" 

(168 mm)

6.455" 

(164 mm)

3

/

8

" (9.5 mm)

5

/

8

" (16 mm)

8" (200 mm)

8.625" 

(219 mm)

8.441" 

(214 mm)

7

/

16

" (11 mm)

3

/

4

" (19 mm)

•  Threaded openings Per ANSI B 2.1
•  Flange Dimensions

Flange 

Type:

Nominal 

Pipe Size

Bolt 

Circle 

Diameter

Bolt Hole 

Diameter

Flange 

Outside 

Diameter

Flange 

Thickness

Number 

of Bolts

ASME 

B16.5 

Class 150

4" 

(100 mm)

7-

1

/

2

(191 mm)

3

/

4

(19 mm)

9" 

(229 mm)

15

/

16

(24 mm)

8

ISO 7005-

2 PN16

4" 

(100 mm)

7-

3

/

32

(180 mm)

3

/

4

(19 mm)

9" 

(229 mm)

15

/

16

(24 mm)

8

ASME 

B16.5 

Class 150

6" 

(150 mm)

9-

1

/

2

(241 mm)

7

/

8

(22 mm)

11" 

(279 mm)

15

/

16

(24 mm)

8

ISO 7005-

2 PN16

6" 

(150 mm)

9-

7

/

16

(240 mm)

29

/

32

(23 mm)

11" 

(279 mm)

15

/

16

(24 mm)

8

ASME 

B16.5 

Class 150

8" 

(200 mm)

11-

3

/

4

(298 mm)

7

/

8

(22 mm)

13-

1

/

2

(343 mm)

1" 

(25.4 mm)

8

ISO 7005-

2 PN16

8" 

(200 mm)

1-

15

/

8

(295 mm)

29

/

32

(23 mm)

13-

1

/

2

(343 mm)

1" 

(25.4 mm)

12

4.  Valve Exterior Color:

Valve Size

Color

2" (50 mm)

Black or Red

2-

1

/

2

" (65 mm)

Black or Red

76 mm

Red

3" (80 mm)

Black or Red

4" (100 mm)

Black or Red

165 mm

Red

6" (150 mm)

Black or Red

8" (200 mm)

Black or Red

5.  Face to face dimensions:

Valve Size:

End Connection:

End to End:

2" (50 mm), 2-

1

/

2

(65 mm), 76 mm 

& 3" (80 mm)

Groove/ Groove

12-

1

/

2

" (318 mm)

4" (100 mm)

Groove/ Groove

14" (356 mm)

Flange/ Groove

16" (406 mm)

Flange/ Flange

16" (406 mm)

6" (150 mm) & 165 mm

Groove/ Groove

16" (406 mm)

Flange/ Groove

19" (483 mm)

Flange/ Flange

19" (483 mm)

8" (200 mm)

Groove/ Groove

19-

3

/

8

" (492 mm)

Flange/ Flange

21-

1

/

4

" (540 mm)

6.  Valve shipping weight:

Valve Size:

End Connection:

Weight:

2" (50 mm), 2-

1

/

2

(65 mm), 76 mm 

& 3" (80 mm)

Groove/ Groove

34 lb (15 kg)

4" (100 mm)

Groove/ Groove

64 lb (29 kg)

Flange/ Groove

79 lb (36 kg)

Flange/ Flange

92 lb (42 kg)

6" (150 mm) & 165 mm

Groove/ Groove

95 lb (43 kg)

Flange/ Groove

122 lb (56 kg)

Flange/ Flange

138 lb (69 kg)

8" (200 mm)

Groove/ Groove

148 lb (67 kg)

Flange/ Flange

197 lb (90 kg)

7.  Trim shipping weight:

Trim Configuration

2" (50 mm),

2‑

1

/

2

" (65 mm),

3" (80 mm)

& 76 mm

4" (100 mm),

6" (150 mm),

8" (200 mm)

& 165 mm

Type D Double Interlock

47 lb (21 kg)

52 lb (24 kg)

8.  Friction loss (Expressed in equivalent length of Schedule 

40 pipe, based on Hazen & Williams formula:

Valve Size:

Equivalent Length:

Cv

C = 120

C = 100

2" (50 mm)

4.4 ft (1.3 m)

3.1 ft (1.0 m)

101

2-

1

/

2

" (65 mm)

6.0 ft (1.8 m)

4.3 ft (1.3 m)

236

76 mm

7.7 ft (2.3 m)

5.5 ft (1.7 m)

241

3" (80 mm)

12.6 ft (3.8 m)

9.0 ft (2.7 m)

254

4" (100 mm)

14 ft (4.3 m)

10 ft (3.0 m)

469

165 mm

29.4 ft (9.0 m)

20.9 ft (6.4 m)

886

6" (150 mm)

29.4 ft (9.0 m)

20.9 ft (6.4 m)

886

8" (200 mm)

53.5 ft (16.3 m)

38.1 ft (11.6 m)

1516

9.  Installation position: Vertical

Trim Descriptions

The Type D Double Interlock Preaction Trims for the Reliable 

Model DDX Deluge Valve are arranged for rapid, easy, and 
compact attachment, and serve as connection points to 
Reliable Model C Mechanical Alarms and other devices. 

The Double Interlock Type D Preaction System trim 

configurations can be ordered as individual parts, in time-
saving segmentally assembled kit forms, or fully assembled 
to the Model DDX Deluge Valve (with or without a control 
valve). 

Maintenance

Reliable Double Interlock Type D Preaction Systems 

and associated equipment shall periodically be given a 
thorough inspection and test. NFPA 25, Inspection, Testing 
and Maintenance of Water Based Fire Protection Systems, 
provides minimum maintenance requirements. System 
components shall be tested, operated, cleaned, and 
inspected at least annually, and parts replaced as required.

Type D Double Interlock Preaction Trim

Type D Double Interlock Preaction trim (see Figures 2 and 

3) utilizes a normally closed/powered-open solenoid valve for 
releasing the Deluge Valve. The solenoid valve used in the 
assembly is available in both a 175 psi (12.1 bar) or 300 psi 
(20.7 bar) rating.

Note:

 In order for the solenoid valve to maintain Reliable’s 

warranty it must remain sealed as it came from the factory. 
If there are concerns about the valve’s internal components, 
immediate replacement is recommended.

Summary of Contents for DDX Type D

Page 1: ...mm 76 mm 4 100 mm 6 150 mm 165 mm 8 200 mm Instructions for Installation Operation Care and Maintenance 7 to 10 psi 0 5 to 0 7 bar Pneumatic Supervising Pressure with Electric Electric Actuation Contr...

Page 2: ...and required pressure gauges This trim set is available in individual loose parts in time saving segmented assembled kit forms or fully assembled to the Model DDX Deluge Valve with or without a contr...

Page 3: ...PPER IN LATCHED POSITION CLAPPER IN CLOSED POSITION ALARM PORT TEST PORT DRAIN PORT FROM SUPPLY LEVER PUSH ROD PUSH ROD CHAMBER OUTLET PUSH ROD CHAMBER INLET RESTRICTION DDX EXTERNAL RESET KNOB PUSH R...

Page 4: ...ONTROL BUTTERFLY VALVE ADJOINING COUPLINGS REDUCING BUSHING AND TUBING CONNECTOR ARE INCLUDED IN THE FULLY ASSEMBLED TO MODEL DDX DELUGE VALVE WITH CONTROL VALVE TRIM CONFIGUARTION ONLY REFER TO PAGE...

Page 5: ...NPT 1 Item No Part No Description Qty Galvanized Brass Black Pipe 26 96686722 96686722 96686722 Copper Tubing 3 8 OD x 2 ft 1 27 94616918 94616918 94616918 Type D Double Interlock Nameplate 1 28 98050...

Page 6: ...RFLY VALVE ADJOINING COUPLINGS REDUCING BUSHING AND TUBING CONNECTOR ARE INCLUDED IN THE FULLY ASSEMBLED TO MODEL DDX DELUGE VALVE WITH CONTROL VALVE TRIM CONFIGUARTION ONLY REFER TO PAGE 26 27 OF THI...

Page 7: ...1 4 NPT 1 25 92056704 92056704 92056704 Connector Elbow 3 8 ID Tube x 1 2 NPT 1 Item No Part No Description Qty Galvanized Brass Black Pipe 26 96686722 96686722 96686722 Copper Tubing 3 8 OD x 2 ft 1...

Page 8: ...mm 6 150 mm and 8 200 mm are rated for use at a minimum water supply pressure of 20 psi 1 4 bar and a maximum water supply pressure of 250 psi 17 2 bar for 2 50 mm 2 1 2 65 mm 3 80 mm 76 mm and 8 200...

Page 9: ...a clean dependable and continuous 24 hours a day 7 days a week compressed air source is available To adjust the system pneumatic pressure between 7 and 10 psi 0 5 and 0 7 bar refer to Reliable Bullet...

Page 10: ...mm 4 100 mm 165 mm 6 150 mm 8 200 mm Reliable Model DDX Deluge Valve Bulletin 519 Valve trim shall be Type D electric electric release trim consisting of the following components Hydraulic trim to be...

Page 11: ...W MANUAL EMERGENCY STATION MODEL BNG 1 SUPERVISORY CIRCUIT AUXILIARY DRY ALARM CONTACTS AUXILIARY DRY TROUBLE CONTACTS AUXILIARY DRY SUPERVISORY CONTACTS MANUAL DUMP CIRCUIT EOL RESISTOR 5 1K 1 2 W E...

Page 12: ...oned operation requiring both a detection device input and a low air pressure switch input sprinkler operation to energize the solenoid valve causing the deluge valve to operate Releasing control pane...

Page 13: ...Groove Groove 34 lb 15 kg 4 100 mm Groove Groove 64 lb 29 kg Flange Groove 79 lb 36 kg Flange Flange 92 lb 42 kg 6 150 mm 165 mm Groove Groove 95 lb 43 kg Flange Groove 122 lb 56 kg Flange Flange 138...

Page 14: ...73 Fig 2 for the 2 50 mm 2 1 2 65 mm 76 mm and 3 80 mm valve sizes 1 4 nipple 36 Fig 3 1 4 elbow 27 Fig 3 1 4 nipple 37 Fig 3 3 way valve 70 Fig 3 and the gauge 72 Fig 3 for the 4 100 mm 165 mm and 6...

Page 15: ...that the Model B Manual Emergency Station valve D Fig 9 is secured in the OFF position with the appropriate nylon tie 56 Fig 2 OR 56 Fig 3 see Fig 4 Inspection and Testing Refer to Figs 2 3 7 8 9 1 Wa...

Page 16: ...80 mm valve sizes or the 2 main drain valve on the 4 100 mm 165 mm 6 150 mm and 8 200 mm valve sizes valve B Fig 9 Open the water column drain valve H Fig 9 Close the pushrod chamber supply valve A Fi...

Page 17: ...SCREW IN SEAT CONFIGURATION EXTERNAL RESET ASSEMBLY 24 42 UPPER SEAT O RING 25 42 LOWER SEAT O RING GAUGE PORT BLEED HOLE FROM SUPPLY ORIFICE TO RELEASING DEVICE SYSTEM AIR PORT ALARM PORT TEST PORT...

Page 18: ...Steel UNS S17400 16 95006414 94006412 95006410 95006410 Striker 1 Aluminum Bronze C95400 17 95106006 Piston 1 Stainless Steel CF8M 18 95276006 Diaphragm 1 EPDM Polyester 19 95306267 N A N A N A Retain...

Page 19: ...et Cap Screw 1 2 13x3 4 Stainless Steel UNS S31600 38 98604402 Plug 1 2 NPT 1 Steel 39 94616921 Knob Caution Label Not Shown 1 Polystyrene 40 91556922 Ball Chain 1 8 Not Shown Length is in inches 6 Ni...

Page 20: ...S44000 18 95106006 Piston 1 Stainless Steel CF8M 19 95200038 Socket Plug 3 8 18 NPT not shown 2 Steel 20 95506006 Pushrod 1 Stainless Steel UNS S30300 21 93916006 Pushrod Guide 1 Acetal 22 95306267 R...

Page 21: ...des Making sure the clapper is in the closed position see Fig 1 lift up and rotate the clapper seat sub assembly clockwise 90 degrees so that the lever side of the assembly is facing up towards the ou...

Page 22: ...t pressure by opening the 1 1 4 main drain valve on the 2 50 mm 2 1 2 65 mm 76 mm and 3 80 mm valve sizes or the 2 main drain valve on the 4 100 mm 165 mm 6 150 mm and 8 200 mm valve sizes valve B Fig...

Page 23: ...DRIP CUP MODEL DDX DELUGE VALVE ALARM TEST TO NON SILENCEABLE ALARM PRESSURE SWITCH REF NFPA 72 OUT IN WATER SUPPLY PRESSURE GAUGE WATER SUPPLY CONTROL VALVE FROM SUPPLY MODEL A 2 PRESSURE MAINTENANCE...

Page 24: ...DOUBLE INTERLOCK PREACTION SYSTEM AS THESE ARE NOT COMPATIBLE WITH THE MODEL A 2 PRESSURE MAINTENANCE DEVICE MODEL DDX DELUGE VALVE SOLENOID VALVE MODEL B HYDRAULIC EMERGENCY STATION TROUBLE ALARM ANU...

Page 25: ...03060049 6 168 mm Flg Flg ASME Class 150 Black 6103060046 ASME Class 150 Red 6103060047 ISO PN16 Red 6103060050 165 mm Grv Grv N A Red 6103060028 165 mm Flg Grv ASME Class 150 Red 6103060051 ISO PN16...

Page 26: ...Class 150 Red 6505A66226 N A ISO PN16 Red 6505A69226 8 200 mm Grv Grv N A Black 6505080226 6505080225 Red 6505A80226 6505A80225 8 200 mm Flg Flg ASME Class 150 Black 6505083226 N A ASME Class 150 Red...

Page 27: ...onal Accessories CA2Z Class A Wiring Module for Initiating Circuits CAM Class A Wiring Module for Indicating Circuits ARM 1 ARM 2 Auxiliary Relay Module RA 4410 RC Remote Annunciator 7 Alarm Annunciat...

Page 28: ...432 6 150 mm 165 mm 8 1 2 215 9 229 11 1 2 292 16 406 26 3 4 679 19 483 19 483 22 559 37 1 2 952 8 203 7 178 5 1 2 140 8 1 4 210 13 3 4 349 4 3 4 121 6 1 2 165 8 3 4 222 12 305 17 432 8 200 mm 8 1 2 2...

Page 29: ...RE TO CLOSE THE SYSTEM CONTROL VALVE TO AVOID UNINTENTIONAL OPERATION OF THE DELUGE VALVE 1 Inspections It is imperative that the system be inspected and tested in accordance with NFPA 25 on a regular...

Page 30: ...ing are some of the many precision made Reliable products that guard life and property from fire around the clock Reliable For Complete Protection Automatic sprinklers Flush automatic sprinklers Reces...

Reviews: