background image

2

General

Type D Double Interlock Preaction Systems are designed 

for water sensitive areas that require protection from 
inadvertent water flow into the sprinkler system piping, but 
where a mechanical backup for the electric release is not 
required. Typical applications for this type of trim are libraries 
and computer server rooms.

To flow water into a Type D Double Interlock Preaction 

System, two events must take place. A fire detection device 
must operate, and the low pressure switch must be operated 
by the loss of system air or nitrogen pressure due to sprinkler 
operation (see note 1 below). These two signals must coexist 
at the releasing control panel, which only then will energize 
the normally closed solenoid valve (175 psi (12.1 bar) or 
300 psi (20.7 bar) rated), causing the water flow into the 
system.

These systems utilize fire detection devices and system 

air pressure as separate zones (inputs) to a cross-zoned 
releasing control panel. The solenoid releasing valve remains 
closed until energized by the releasing control panel. This will 
occur only when both a fire detection device is operated and 
the low air pressure switch has detected sufficient loss of 
system air pressure (sprinkler operation).

In the event that the system piping is ruptured, or a sprinkler 

head is accidentally opened, the low air pressure switch will 
operate and an alarm will sound. The Model DDX Deluge 
Valve, however, will not be released to flow water since 
the solenoid valve remains closed due to the cross-zoned 
control panel configuration. The same result would occur if a 
fire detection device were falsely operated. The control panel 
will activate an alarm, however again, the Model DDX Deluge 
Valve will not flow water due to the cross-zoned control panel 
configuration.

This requirement for both a detector to operate and the loss 

of system air pressure before the Model DDX Deluge Valve 
releases water into a preaction system assures maximum 
protection against inadvertent water flow before a sprinkler 
is open.

At the heart of Reliable’s Type D Double Interlock Preaction 

System is the Model DDX Deluge Valve. This Deluge Valve 
is a hydraulically operated, straight through design, latching 
type valve (see Fig. 1). System maintenance is simplified 
since the Model DDX Deluge Valve can be reset externally 
without cover removal. This is accomplished by pushing in 
and turning the external reset knob at the rear of the Deluge 
Valve (see Fig. 1). This feature provides a significant system 
restoration time advantage.

The Reliable Model DDX Type D Double Interlock Preaction 

System trim set (see Fig. 2 & Fig. 3) provides all of the 
necessary equipment for connections to the Model DDX 
Deluge Valve’s pushrod chamber inlet and outlet ports, a 1-

1

/

4

(30 mm) main drain on 2" (50 mm), 2-

1

/

2

" (65 mm), 76 mm 

and 3" (80 mm) valve sizes or a 2" (50 mm) main drain on 
4" (100 mm), 165 mm, 6" (150 mm) and 8" (200 mm) valve 
sizes, alarm devices, air supply, water supply and required 
pressure gauges. This trim set is available in individual (loose) 
parts, in time-saving, segmented assembled kit forms or fully 
assembled to the Model DDX Deluge Valve (with or without 
a control valve).

Listings & Approvals:

(Only when used with Reliable’s Trim Sets.)
1.  Reliable’s Type D Double Interlock Preaction Systems 

2" (50 mm), 2-

1

/

2

" (65 mm), 76 mm and 3" (80 mm), 4" 

(100 mm), 165 mm, 6" (150 mm) and 8" (200 mm) are 
Factory Mutual Approved Refrigerated Area Sprinkler 
Systems for use in refrigerated rooms or buildings. 
Refrigerated area sprinkler systems are FM Approved as 
complete systems. Systems are FM Approved for use 
with thermal detectors and Class A detector wiring only. 

2.  Reliable’s Type D Double Interlock Preaction Systems 

2" (50 mm), 2-

1

/

2

" (65 mm), 76 mm, 3" (80 mm), 4" 

(100 mm), 165 mm, 6" (150 mm) and 8" (200 mm) are 
Underwriters Laboratories, Inc. Listed and UL certified 
for Canada (cULus) in the Special System Water Control 
Valve-Double Interlock Type (VLJH) category.

3.  The NYC acceptance number for this system is MEA 

258-93-E.

The Reliable Model DDX Type D Double Interlock Preaction 

System is UL Listed and FM Approved only when used with 
the trim components shown in Fig. 2 & 3.

Note 1:

 Wherever the word “air” is used in this bulletin 

as a reference to the pneumatic pressure source it shall 
also mean “air or nitrogen.”

System Operation

When set correctly for service, the Model DDX Deluge 

Valve is hydraulically established to withhold the supply water 
from the sprinkler system piping. The Reliable Model DDX 
Deluge Valve is shown in both closed and open positions in 
Fig. 1. In the closed position, the supply pressure acts on the 
underside of the clapper and also on the push rod through the 
push rod chamber’s inlet restriction. The resultant force due 
to the supply pressure acting on the push rod is multiplied 
by the mechanical advantage of the lever and is more than 
sufficient to hold the clapper closed against normal supply 
pressure surges.

Whenever a fire and a low system air pressure condition 

are detected, the energized solenoid valve vents the push 
rod chamber to atmosphere through the chamber’s outlet. 
Since the pressure can not be replenished through the inlet 
restriction as rapidly as it is vented, the pushrod chamber 
pressure falls instantaneously. When the pushrod chamber 
pressure approaches approximately on-third of the supply 
pressure, the upward force of the supply pressure acting 
beneath the clapper overcomes the lever applied force, 
thereby opening the clapper.

Once the clapper has opened, the lever acts as a latch, 

preventing the clapper from returning to the closed position. 
Water from the supply flows through the Deluge Valve into 
the sprinkler system piping. Water also flows through the 
Deluge Valve alarm outlet to the alarm devices.

After system shutdown, resetting the Model DDX Deluge 

Valve is quite simple. Doing so only requires pushing in and 
turning the reset knob at the rear of the valve (see Fig. 1). The 
external reset feature of the Model DDX Deluge Valve provides 
a means for simple, economical system testing, which is one 
essential facet of a good maintenance program. The external 

Summary of Contents for DDX Type D

Page 1: ...mm 76 mm 4 100 mm 6 150 mm 165 mm 8 200 mm Instructions for Installation Operation Care and Maintenance 7 to 10 psi 0 5 to 0 7 bar Pneumatic Supervising Pressure with Electric Electric Actuation Contr...

Page 2: ...and required pressure gauges This trim set is available in individual loose parts in time saving segmented assembled kit forms or fully assembled to the Model DDX Deluge Valve with or without a contr...

Page 3: ...PPER IN LATCHED POSITION CLAPPER IN CLOSED POSITION ALARM PORT TEST PORT DRAIN PORT FROM SUPPLY LEVER PUSH ROD PUSH ROD CHAMBER OUTLET PUSH ROD CHAMBER INLET RESTRICTION DDX EXTERNAL RESET KNOB PUSH R...

Page 4: ...ONTROL BUTTERFLY VALVE ADJOINING COUPLINGS REDUCING BUSHING AND TUBING CONNECTOR ARE INCLUDED IN THE FULLY ASSEMBLED TO MODEL DDX DELUGE VALVE WITH CONTROL VALVE TRIM CONFIGUARTION ONLY REFER TO PAGE...

Page 5: ...NPT 1 Item No Part No Description Qty Galvanized Brass Black Pipe 26 96686722 96686722 96686722 Copper Tubing 3 8 OD x 2 ft 1 27 94616918 94616918 94616918 Type D Double Interlock Nameplate 1 28 98050...

Page 6: ...RFLY VALVE ADJOINING COUPLINGS REDUCING BUSHING AND TUBING CONNECTOR ARE INCLUDED IN THE FULLY ASSEMBLED TO MODEL DDX DELUGE VALVE WITH CONTROL VALVE TRIM CONFIGUARTION ONLY REFER TO PAGE 26 27 OF THI...

Page 7: ...1 4 NPT 1 25 92056704 92056704 92056704 Connector Elbow 3 8 ID Tube x 1 2 NPT 1 Item No Part No Description Qty Galvanized Brass Black Pipe 26 96686722 96686722 96686722 Copper Tubing 3 8 OD x 2 ft 1...

Page 8: ...mm 6 150 mm and 8 200 mm are rated for use at a minimum water supply pressure of 20 psi 1 4 bar and a maximum water supply pressure of 250 psi 17 2 bar for 2 50 mm 2 1 2 65 mm 3 80 mm 76 mm and 8 200...

Page 9: ...a clean dependable and continuous 24 hours a day 7 days a week compressed air source is available To adjust the system pneumatic pressure between 7 and 10 psi 0 5 and 0 7 bar refer to Reliable Bullet...

Page 10: ...mm 4 100 mm 165 mm 6 150 mm 8 200 mm Reliable Model DDX Deluge Valve Bulletin 519 Valve trim shall be Type D electric electric release trim consisting of the following components Hydraulic trim to be...

Page 11: ...W MANUAL EMERGENCY STATION MODEL BNG 1 SUPERVISORY CIRCUIT AUXILIARY DRY ALARM CONTACTS AUXILIARY DRY TROUBLE CONTACTS AUXILIARY DRY SUPERVISORY CONTACTS MANUAL DUMP CIRCUIT EOL RESISTOR 5 1K 1 2 W E...

Page 12: ...oned operation requiring both a detection device input and a low air pressure switch input sprinkler operation to energize the solenoid valve causing the deluge valve to operate Releasing control pane...

Page 13: ...Groove Groove 34 lb 15 kg 4 100 mm Groove Groove 64 lb 29 kg Flange Groove 79 lb 36 kg Flange Flange 92 lb 42 kg 6 150 mm 165 mm Groove Groove 95 lb 43 kg Flange Groove 122 lb 56 kg Flange Flange 138...

Page 14: ...73 Fig 2 for the 2 50 mm 2 1 2 65 mm 76 mm and 3 80 mm valve sizes 1 4 nipple 36 Fig 3 1 4 elbow 27 Fig 3 1 4 nipple 37 Fig 3 3 way valve 70 Fig 3 and the gauge 72 Fig 3 for the 4 100 mm 165 mm and 6...

Page 15: ...that the Model B Manual Emergency Station valve D Fig 9 is secured in the OFF position with the appropriate nylon tie 56 Fig 2 OR 56 Fig 3 see Fig 4 Inspection and Testing Refer to Figs 2 3 7 8 9 1 Wa...

Page 16: ...80 mm valve sizes or the 2 main drain valve on the 4 100 mm 165 mm 6 150 mm and 8 200 mm valve sizes valve B Fig 9 Open the water column drain valve H Fig 9 Close the pushrod chamber supply valve A Fi...

Page 17: ...SCREW IN SEAT CONFIGURATION EXTERNAL RESET ASSEMBLY 24 42 UPPER SEAT O RING 25 42 LOWER SEAT O RING GAUGE PORT BLEED HOLE FROM SUPPLY ORIFICE TO RELEASING DEVICE SYSTEM AIR PORT ALARM PORT TEST PORT...

Page 18: ...Steel UNS S17400 16 95006414 94006412 95006410 95006410 Striker 1 Aluminum Bronze C95400 17 95106006 Piston 1 Stainless Steel CF8M 18 95276006 Diaphragm 1 EPDM Polyester 19 95306267 N A N A N A Retain...

Page 19: ...et Cap Screw 1 2 13x3 4 Stainless Steel UNS S31600 38 98604402 Plug 1 2 NPT 1 Steel 39 94616921 Knob Caution Label Not Shown 1 Polystyrene 40 91556922 Ball Chain 1 8 Not Shown Length is in inches 6 Ni...

Page 20: ...S44000 18 95106006 Piston 1 Stainless Steel CF8M 19 95200038 Socket Plug 3 8 18 NPT not shown 2 Steel 20 95506006 Pushrod 1 Stainless Steel UNS S30300 21 93916006 Pushrod Guide 1 Acetal 22 95306267 R...

Page 21: ...des Making sure the clapper is in the closed position see Fig 1 lift up and rotate the clapper seat sub assembly clockwise 90 degrees so that the lever side of the assembly is facing up towards the ou...

Page 22: ...t pressure by opening the 1 1 4 main drain valve on the 2 50 mm 2 1 2 65 mm 76 mm and 3 80 mm valve sizes or the 2 main drain valve on the 4 100 mm 165 mm 6 150 mm and 8 200 mm valve sizes valve B Fig...

Page 23: ...DRIP CUP MODEL DDX DELUGE VALVE ALARM TEST TO NON SILENCEABLE ALARM PRESSURE SWITCH REF NFPA 72 OUT IN WATER SUPPLY PRESSURE GAUGE WATER SUPPLY CONTROL VALVE FROM SUPPLY MODEL A 2 PRESSURE MAINTENANCE...

Page 24: ...DOUBLE INTERLOCK PREACTION SYSTEM AS THESE ARE NOT COMPATIBLE WITH THE MODEL A 2 PRESSURE MAINTENANCE DEVICE MODEL DDX DELUGE VALVE SOLENOID VALVE MODEL B HYDRAULIC EMERGENCY STATION TROUBLE ALARM ANU...

Page 25: ...03060049 6 168 mm Flg Flg ASME Class 150 Black 6103060046 ASME Class 150 Red 6103060047 ISO PN16 Red 6103060050 165 mm Grv Grv N A Red 6103060028 165 mm Flg Grv ASME Class 150 Red 6103060051 ISO PN16...

Page 26: ...Class 150 Red 6505A66226 N A ISO PN16 Red 6505A69226 8 200 mm Grv Grv N A Black 6505080226 6505080225 Red 6505A80226 6505A80225 8 200 mm Flg Flg ASME Class 150 Black 6505083226 N A ASME Class 150 Red...

Page 27: ...onal Accessories CA2Z Class A Wiring Module for Initiating Circuits CAM Class A Wiring Module for Indicating Circuits ARM 1 ARM 2 Auxiliary Relay Module RA 4410 RC Remote Annunciator 7 Alarm Annunciat...

Page 28: ...432 6 150 mm 165 mm 8 1 2 215 9 229 11 1 2 292 16 406 26 3 4 679 19 483 19 483 22 559 37 1 2 952 8 203 7 178 5 1 2 140 8 1 4 210 13 3 4 349 4 3 4 121 6 1 2 165 8 3 4 222 12 305 17 432 8 200 mm 8 1 2 2...

Page 29: ...RE TO CLOSE THE SYSTEM CONTROL VALVE TO AVOID UNINTENTIONAL OPERATION OF THE DELUGE VALVE 1 Inspections It is imperative that the system be inspected and tested in accordance with NFPA 25 on a regular...

Page 30: ...ing are some of the many precision made Reliable products that guard life and property from fire around the clock Reliable For Complete Protection Automatic sprinklers Flush automatic sprinklers Reces...

Reviews: