INSTRUCTION

DTTH(C)

IN20046 REV. B, 2021-06-08

C

Caauuttiioonn!! Read and understand the instruction before using the product.

C

Caauuttiioonn!! Ensure that the installation complies with local safety

regulations.

C

Caauuttiioonn!! Before installation or maintenance, the power supply should first

be disconnected. Installation or maintenance of this unit should only be
carried out by qualified personnel. The manufacturer is not responsible
for any eventual damage or injury caused by inadequate skills during instal-
lation, or through removal of or deactivation of any security devices.

Function

The measurements received from DTTH(C) can be used to control
ventilation with high precision and improve the air quality in for
example residential and office areas. By increasing the air exchange only
when it is necessary, it is possible to minimise energy costs.

Technical Data

Supply voltage

24 V ~ (20…28 V ~ 50…60 Hz, 2 VA) / 15…35
V DC

Power consumption

< 1.5 W

Load impedance, 0...10 V

Min. 10 kΩ

Protection class

IP65 (housing)

Ambient humidity

0…90 % RH, non-condensing

Ambient temperature

-40…+60 °C (DTTH) / 0…+50 °C (DTTHC)

Storage temperature

-40…+80 °C

Max overvoltage

+10 V (referenced to GND)

Mounting

Duct

Insertion length

37…195 mm

Media

Air, non-combustible and non-aggressive gases

Measuring range,
temperature

-40…+60 °C

Output signal,
temperature

0…10 V (0 V = -40 °C, 10 V = 60 °C)

Accuracy, temperature

±0.2 K at 0…60 °C

Measuring range,
humidity

0…100 % RH

Output signal, humidity

0…10 V (0 V = 0 % RH, 10 V = 100 % RH)

Accuracy, humidity

±2 % RH at 25 °C, 10...90 % RH

Measuring range, CO

2

0…2000 ppm

Output signal, CO

2

0…10 V (0 V = 0 ppm, 10 V = 2000 ppm)

Accuracy, CO

2

±(50 ppm + 3 % of the measured value) at 25 °C

Temperature depend-
ency, CO

2

2.5 ppm/K at 0…50 °C

Cable gland

2 x M16

Cable connection

Screw terminals max. 1.5 mm

2

(AWG 16)

Warmup time

4 min

Diameter, probe

12 mm

Dimensions, external
(WxHxD)

104 x 211/212.5 x 79 mm

Table 1 Response times

Article

Response time,
temp

Response time,
humidity

Response time,
CO

2

DTTH

<50 s

1

<50 s

1

-

DTTHC

<50 s

1

<50 s

1

<100 s

1

1. At 3 m/s air speed

Installation

– Find a location in the duct where the transmitter can be expected to

give a representative reading. It should be placed at least 4 duct
diameters from a bend or other obstacle, e.g. a damper, for minimal
turbulence.

– Use a 13 mm drill bit to make a hole in duct

– Twist the cover to access the terminals

– Place the DTTHC transmitter in the duct with the cable glands

perpendicular to the air flow direction, see

Figure 1

.

– Connect the wires to the terminals according to the wiring diagram

in

Figure 2

– After applying power to the transmitter, the time it takes to show

correct values is specified under

Warmup time

in the technical data

table. A green LED, located under the cover, indicates when the
transmitter is ready to use (see

Table 2

).

– Screw the cover back on and ensure that it is properly fastened and

that the cable gland makes a tight seal around the cable.

N

No

ottee!! If there is a risk for condensation in the probe, mount the transmit-

ter upright.

Figure 1 Installation direction in duct (A = air flow direction)

LED indications

A LED light under the lid indicates the status of the transmitter as
shown in

Table 2

.

Table 2 LED status indications

LED indications

Description

Green, solid

Power is on. All is OK.

Red, solid

Sensor problem.

Wiring

The terminals are accessed by twisting the cover. Connect the cables
according to the wiring diagram below.

Figure 2 Wiring diagram

A

Ɵ Ɵ Ɵ Ɵ Ɵ Ɵ Ɵ

□ □ □ □ □ □ □

G

G0

AO1

AO2

AO3

AGND

AO4

DTTH(C)

1