EN
INSTRUCTION
DTTH(C)
IN20046 REV. B, 2021-06-08
C
Caauuttiioonn!! Read and understand the instruction before using the product.
C
Caauuttiioonn!! Ensure that the installation complies with local safety
regulations.
C
Caauuttiioonn!! Before installation or maintenance, the power supply should first
be disconnected. Installation or maintenance of this unit should only be
carried out by qualified personnel. The manufacturer is not responsible
for any eventual damage or injury caused by inadequate skills during instal-
lation, or through removal of or deactivation of any security devices.
Function
The measurements received from DTTH(C) can be used to control
ventilation with high precision and improve the air quality in for
example residential and office areas. By increasing the air exchange only
when it is necessary, it is possible to minimise energy costs.
Technical Data
Supply voltage
24 V ~ (20…28 V ~ 50…60 Hz, 2 VA) / 15…35
V DC
Power consumption
< 1.5 W
Load impedance, 0...10 V
Min. 10 kΩ
Protection class
IP65 (housing)
Ambient humidity
0…90 % RH, non-condensing
Ambient temperature
-40…+60 °C (DTTH) / 0…+50 °C (DTTHC)
Storage temperature
-40…+80 °C
Max overvoltage
+10 V (referenced to GND)
Mounting
Duct
Insertion length
37…195 mm
Media
Air, non-combustible and non-aggressive gases
Measuring range,
temperature
-40…+60 °C
Output signal,
temperature
0…10 V (0 V = -40 °C, 10 V = 60 °C)
Accuracy, temperature
±0.2 K at 0…60 °C
Measuring range,
humidity
0…100 % RH
Output signal, humidity
0…10 V (0 V = 0 % RH, 10 V = 100 % RH)
Accuracy, humidity
±2 % RH at 25 °C, 10...90 % RH
Measuring range, CO
2
0…2000 ppm
Output signal, CO
2
0…10 V (0 V = 0 ppm, 10 V = 2000 ppm)
Accuracy, CO
2
±(50 ppm + 3 % of the measured value) at 25 °C
Temperature depend-
ency, CO
2
2.5 ppm/K at 0…50 °C
Cable gland
2 x M16
Cable connection
Screw terminals max. 1.5 mm
2
(AWG 16)
Warmup time
4 min
Diameter, probe
12 mm
Dimensions, external
(WxHxD)
104 x 211/212.5 x 79 mm
Table 1 Response times
Article
Response time,
temp
Response time,
humidity
Response time,
CO
2
DTTH
<50 s
1
<50 s
1
-
DTTHC
<50 s
1
<50 s
1
<100 s
1
1. At 3 m/s air speed
Installation
– Find a location in the duct where the transmitter can be expected to
give a representative reading. It should be placed at least 4 duct
diameters from a bend or other obstacle, e.g. a damper, for minimal
turbulence.
– Use a 13 mm drill bit to make a hole in duct
– Twist the cover to access the terminals
– Place the DTTHC transmitter in the duct with the cable glands
perpendicular to the air flow direction, see
– Connect the wires to the terminals according to the wiring diagram
in
– After applying power to the transmitter, the time it takes to show
correct values is specified under
Warmup time
in the technical data
table. A green LED, located under the cover, indicates when the
transmitter is ready to use (see
).
– Screw the cover back on and ensure that it is properly fastened and
that the cable gland makes a tight seal around the cable.
N
No
ottee!! If there is a risk for condensation in the probe, mount the transmit-
ter upright.
Figure 1 Installation direction in duct (A = air flow direction)
LED indications
A LED light under the lid indicates the status of the transmitter as
shown in
Table 2 LED status indications
LED indications
Description
Green, solid
Power is on. All is OK.
Red, solid
Sensor problem.
Wiring
The terminals are accessed by twisting the cover. Connect the cables
according to the wiring diagram below.
Figure 2 Wiring diagram
A
Ɵ Ɵ Ɵ Ɵ Ɵ Ɵ Ɵ
□ □ □ □ □ □ □
G
G0
AO1
AO2
AO3
AGND
AO4
DTTH(C)
1