P33CE-10 Direct Vent Gas Fireplace
|
11
|
11
installation
coMBustiBle Mantels
Because of the extreme heat this fireplace emits, the mantel clearances are critical.
Combustible mantel clearances from top of unit are shown in the
diagram below.
Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible board.
This drawing is to scale at 1:6 (one inch = 6 inches). Mantel can be installed anywhere in shaded area or higher using the above scale.
Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint may discolour.
Combustible mantel leg clearances as per diagrams below:
Drywall
Mantel Clearances
2
0
12
6
4
8
10
2
0
12
6
4
8
10
Top opening
of Unit
12" (305mm)
0” - 3-1/2" (89mm)
7-1/2"(191mm)
15-3/4" (400mm)
11-3/4"(298mm)
13-3/4"(349mm)
24-1/4"(616mm)
to floor
3"(76mm)
Standoff
Side View
16
14
Non-combustible material