10
|
Regency Horizon HZ30E-10 Gas Fireplace
|
10
installation
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may
NOT be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fireplace and vent
system be installed only in accordance with these instructions.
CLEARANCES
The clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fireplace and vent system be installed only in accordance with these instructions.
F
E
D
A
Installed Close
to Floor
G
Clearance:
Dimension
Measured From:
A: Sidewall (on one side)
8" (203mm)
Side of Fireplace Opening
B: Ceiling
(room and/or alcove)
39" (991mm)
Top of Fireplace Opening
C: Mantel Height (min.)
13-1/4" (330mm)
Top of Fireplace Opening
D: Mantel Depth (max.)
12" (305mm)
21-1/4" Above Fireplace
Opening
E: Alcove Width
60" (1524mm)
Sidewall to Sidewall (Minimum)
F: Alcove Depth
36" (914mm)
Front to Back Wall (Maximum)
G: From Floor
21" (533mm)
Top of Fireplace Opening
Note:
0"
No hearth required
B
A
Flue Clearances to Combustibles
Horizontal - Top
3"
Horiztonal - Side
2"
Horiztonal - Bottom
2"
Vertical
2"
Passing through wall/
floor/ceiling - when
firestop is used.
1-1/2"
Alcove
Unit
E
F