City Series CV72E
|
55
installation
7. Ensure that the pipe clearances to combustible
materials are maintained (Diagram 55). Install
the termination cap.
Note: If installing termination on a vinyl
siding covered wall, a vinyl siding
standoff or furring strips must be
used to ensure that the termination
is not recessed into the siding.
The four wood screws provided should be
replaced with appropriate fasteners for stucco,
brick, concrete, or other types of sidings.
8. Before connecting the horizontal run of vent pipe
to the vent termination, slide the Wall Thimble
over the vent pipe. The wall thimble is required
for all horizontal terminations.
9. Slide the appliance and vent assembly towards
the wall carefully inserting the vent pipe into the
vent cap assembly. It is important that the vent
pipe extends into the vent cap sufficient distance
so as to result in a minimum pipe overlap of
1-1/4 inches (32mm). Secure the connection
between the vent pipe and the vent cap.
10. Install wall thimble in the center of the framed
hole and attach with wood screws.
Install the vent system according to the manufacturer's
instructions included with the components.
1. Set the unit in its desired location. Check to
determine if wall studs or roof rafters are in the
way when the venting system is attached. If this
is the case, you may want to adjust the location
of the unit. Rough in the gas preferably on the
right side of the unit and the electrical (junction
block is on the left side) on the left.
2. Direct Vent pipe and fittings are designed with
special twist-lock connections to connect the
venting system to the appliance flue outlet. A
twist-lock appliance adaptor is required.
3. In conjunction with the Approved Vent system,
install the adaptor after the unit is set in its de-
sired location. Slip the adapter over the existing
inner and outer flue collar. Fasten to the outer
collar only with the 3 supplied screws (drilling
pilot holes will make this easier).
4. Level the fireplace and fasten it to the framing
using nails or screws through the top and side
nailing strips.
Horizontal runs of vent must be supported every
3 feet (0.9meter). Wall straps are available for
this purpose.
6. Mark the wall for a square hole.-see chart to left
for size. The center of the square hole should
line up with the center-line of the horizontal pipe.
Cut and frame the square hole in the exterior
wall where the vent will be terminated. See
diagram 54 for center line requirements.
If the wall being penetrated is constructed of
non-combustible material, i.e. masonry block
or concrete, an 8" (203mm) diameter hole is
acceptable.
Notes:
a)
The horizontal run of vent must be level, or
have a 1/4 inch rise for every 1 foot of run
towards the termination. Never allow the
vent to run downward. This could cause
high temperatures and may present the
possibility of a fire.
b)
The location of the horizontal vent
termination on an exterior wall must meet all
local and national building codes, and must
not be blocked or obstructed. See "Exterior
Vent Termination Locations" section for
more details.
5. Assemble the desired combination of pipe and
elbows to the appliance adaptor and twist-lock
for a solid connection.
Note: For best results and optimum
performance with each approved
venting system, it is highly
recommended to apply “Mill-Pac”
sealant (supplied) to every inner
pipe connection. Failure to do so
may result in drafting or performance
issues not covered under warranty.
55-1/4
”(1403 mm)
center
of hole
Horizontal Top*
3" (76mm)*
Horizontal Side
2 " (51mm)
Horizontal Bottom
2" (51mm)
Vertical Vent
2" (51mm)
Minimum Vent Clearances to
Combustibles
Horizontal Termination - 5" x 8"
Venting (Rigid Vent Systems)
Below are the recommended framing dimensions
(inside measurements) for the 5" x 8" rigid vent
terminations - for use with a firestop or wall thimble.
Diagram 1
Diagram 2
Diagram 3
* Clearances noted below must be maintained;
except when passing through a wall, ceiling or at
the termination where the use of a firestop or wall
thimble reduces clearance to 1-1/2" (38mm).
c) Snorkel Terminations:
For installations requiring a vertical rise on the
exterior of the building, 14-inch and 36-inch
tall Snorkel Terminations are available, as well
as the standard Riser Vent. Follow the same
installation procedures as used for standard
Horizontal Termination. NEVER install the
snorkel upside down
.
Below Grade Snorkel Installation
If the snorkel termination must be installed below
grade, i.e. basement application, proper drainage
must be provided to prevent water from entering
the snorkel termination. See diagram 56. Do not
attempt to enclose the snorkel within the wall or
any other type of enclosure.
Window
Well
Adequate
Drainage
Gravel
Snorkel
(305 mm)
Min. 12”
Min. 12"*
(305mm)
Snorkel
Diagram 5
*As specified in CGA B149 Installation Code. Local
codes or regulations may require different clearances.