32
|
City Series CV72E
installation
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may
NOT
be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
if these clearances (air space) to combustible materials are not
adhered to. It is of greatest importance that this fireplace and vent
system be installed only in accordance with these instructions.
Clearances
The clearances listed below are minimum distances unless otherwise stated:
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this
fireplace and vent system be installed only in accordance with these instructions.
Clearance: single sided
Dimension
Measured From:
A: Mantel Height (min.)
**
Top of Fireplace Opening
B1:From Floor
min. 0"
Bottom of Fireplace Opening
B2: Opening Height
15-1/16" (383mm)
Bottom/Top of Fireplace Opening
C: Sidewall (on one side)
8" (203mm)
Side of Fireplace Opening
D: Mantel Depth (max.)
**
E: Alcove Width
88" (2135mm)
Sidewall to Sidewall (Minimum)
F: Alcove Depth
36" (914mm)
Front to Unit (Maximum)
G: Ceiling
(in front of fireplace)
61-3/4" (1568mm)
Top of Fireplace Opening
H: Convection Air Outlet*
*288 square inches
J: Convection Air Outlet Opening Offset
*0-2" (0-51mm)
Max. offset from top of chase
enclosure
K: Chase Enclosure (Min.)
87" (2210mm)
From base of unit/floor
L: Clearance to Sprinkler Head (Min.)
36" (914mm)
Perpendicular from chase grill
Hearth
0"
No hearth required
*ALso see previous page for alternate ventilation opening locations.
** See mantel clearances chart in this manual.
Flue Clearances to Combustibles
Horizontal - Top
3"
Horizontal - Side
2"
Horizontal - Bottom
2"
Vertical
2"
Passing through wall/
floor/ceiling - when
firestop is used.
1-1/2"
Note: This appliance uses 5" x 8" venting.
Alcove
E
F
D
A
C
B
1
G
B
2
J
H
K
The
HeatWave
Duct Kit has differ-
ent clearance and framing require-
ments, check the
HeatWave
manual
for details.
*
A minimum of 288 square
inches of open area, not
lower than 0-2" from top of
enclosure, required for all
installations
Side view
L
Chase grill
Sprinkler