F5200 Regency Freestanding Woodstove

 | 

4

safety decal

This is a copy of the label that accompanies each 
Regency  Freestanding  Woodstove  (F5200). 
We have printed a copy of the contents here 
for your review.

NOTE:

  Regency  units  are  constantly  being 

improved.  Check  the  label  on  the  unit  and  if 
there is a difference, the label on the unit is the 
correct one.

Part #:      920-101

Size:       11- 9/16" H x 5-3/4" W (File at 100%)

Color:     Everything printed black on grey except what is indicated is printed red on grey.

Material: 2 ml silver matt polyester (DPM SMS)

April 26/19: Created draft.

April 30/19: Updated Logo

May 09/19:  Updated measurements

May 13/19:  Added report #

June 13/19: Added (R2015)

HOT WHILE IN OPERATION DO NOT TOUCH.  KEEP CHILDREN,

CLOTHING AND FURNITURE AWAY. CONTACT MAY CAUSE

SKIN BURNS. READ NAMEPLATE AND INSTRUCTIONS.

ATTENTION

CHAUD EN COURS DE FONCTIONNEMENT.

NE PAS TOUCHER. ÉLOIGNER LES ENFANTS, LES VÊTEMENTS ET LES 

MEUBLES DE L'APPAREIL. LE CONTACT AVEC L'APPAREIL PEUT OCCA-

SIONNER DES BRÛLURES. LIRE CETTE ÉTIQUETTE ET LES CONSIGNES.

DO NOT REMOVE THIS LABEL

525

 JAN

 

  FEB

 

 MAR

 

 APR

 

 M

AY

 

 JUN

 

 JUL

 

 AUG 

 

 SEPT

 

 OCT

 

 NOV

 

 DEC

CAUTION

DA

TE OF MANUF

ACTURE

920-101

LISTED ROOM HEATER, SOLID FUEL TYPE,  ALSO 

FOR USE IN MOBILE HOME INSTALLATION 

MODEL:  REGENCY  FREESTANDING STOVE -  F5200

TESTED TO:  UL-1482 -2011 (R2015) / ULC-S627-00   

THE SPACE BENEATH THE HEATER MUST NOT BE OBSTRUCTED. OPERATE ONLY WITH FIREBRICKS IN PLACE.
FOR USE WITH SOLID WOOD FUEL ONLY.  USE OF OTHER FUELS MAY DAMAGE HEATER AND CREATE A HAZARDOUS CONDITION.  DO NOT OBSTRUCT COMBUSTION AIR 
OPENINGS.  OPERATE ONLY WITH FIREBRICKS IN PLACE.  RISK OF SMOKE AND FLAME SPILLAGE, OPERATE ONLY WITH DOORS FULLY CLOSED. DO NOT USE GRATE 
OR ELEVATE FIRE.  BUILD WOOD FIRE DIRECTLY ON HEARTH.  DO NOT OVERFIRE - IF HEATER OR CHIMNEY CONNECTOR GLOWS YOU ARE OVERFIRING.  INSPECT AND 
CLEAN CHIMNEY AND CONNECTOR FREQUENTLY.  UNDER CERTAIN CONDITIONS OF USE CREOSOTE BUILDUP MAY OCCUR RAPIDLY.  KEEP FURNISHINGS AND OTHER 
COMBUSTIBLE MATERIAL AWAY FROM HEATER.  REPLACE GLASS ONLY WITH NEOCERAM GLASS. COMBUSTIBLE FLOOR MUST BE PROTECTED BY NON-COMBUSTIBLE 
MATERIAL EXTENDING BENEATH THE HEATER AND TO THE FRONT AND SIDES AS INDICATED OR TO THE NEAREST PERMITTED COMBUSTIBLE MATERIAL.
OPTIONAL COMPONENTS: FAN (846-515), ELECTRICAL RATING: VOLTS 115, 60 HZ, 2 AMPS., AIRMATE, OUTSIDE AIR KIT, ASH DRAWER, COMBUSTOR PART #051-530
THIS WOOD HEATER CONTAIN A CATALYTIC COMBUSTOR WHICH REQUIRES PERIODIC INSPECTION AND REPLACEMENT FOR PROPER OPERATION. IT IS AGAINST THE 
LAW TO OPERATE THIS WOOD HEATER IN A MANNER INCONSISTENT WITH OPERATING INSTRUCTIONS IN INSTRUCTION MANUAL, OR IF THE CATALYTIC ELEMENT IS 
DEACTIVATED OR REMOVED.
DANGER: RISK OF ELECTRIC SHOCK. DISCONNECT POWER BEFORE SERVICING UNIT. DO NOT ROUTE POWER CORD UNDER OR IN FRONT OF APPLIANCE.
CAUTION: MOVING PARTS MAY CAUSE INJURY. DO NOT OPERATE UNIT WITH FAN HOSING REMOVED.
CAUTION: HOT PARTS. DO NOT OPERATE UNIT WITH DOOR OR GLASS REMOVED.
COMPONENTS REQUIRED FOR MOBILE HOME INSTALLATION: OUTSIDE AIR KIT AND ONE OF THE FOLLOWING DOUBLE WALL CONNECTOR 
IN CANADA: LISTED SECURITY MODEL DP, OR OLIVER MACLEOD PRO-VENT PV DOUBLE WALLED CONNECTOR WITH LISTED CHIMNEY SYSTEM: LISTED SECURITY MODEL 
SECURITY S2100+, ICC EXCEL 2100, SIMPSON DURA-PLUS HTC, SELKIRK SENTINAL CF.
IN USA:   LISTED DOUBLE WALL CONNECTORS SECURITY MODEL DP, SELKIRK MODEL DS, OLIVER MACLEOD PRO VENT PV, SIMPSON DURA VENT MODEL DVL, METAL-
FAB DOUBLE WALL.  CONNECTED TO ONE OF THE FOLLOWING COMPATIBLE CHIMNEY SYSTEMS SELKIRK SURE-TEMP, PROJET Nova Temp, SECURITY SECURE TEMP 
ASH+, SECURITY SECURE TEMP S-2100+, METAL-FAB TEMP/GUARD 2100, AMERI-TEC HS, ICC EXCEL 2100 .  USE CHIMNEY COMPONENTS AS SPECIFIED IN INSTALLATION 
INSTRUCTIONS.

HAUTEUR MINIMALE DU PLAFOND DE L’ALCÔVE : 2,1M / 83PO. PROFONDEUR MAXIMALE DE L’ALCÔVE : 1219 MM / 48 PO.

   

L'ESPACE SOUS LE CHAUFFAGE NE DOIT PAS ÊTRE OBSTRUÉ. UTILISEZ SEULEMENT AVES DES BIQUES EN PLACE.

POUR UTILISATION AVEC BOIS SOLIDE SEULEMENT. L’UTILISATION D’AUTRES COMBUSTIBLES PEUT ENDOMMAGER LE POÊLE ET CRÉER UNE CONDITION DAN-

GEREUSE.

 

L’ESPACE AU-DESSOUS DU POÊLE NE DOIT PAS ÊTRE OBSTRUÉ. UTILISER SEULEMENT AVEC LES BRIQUES RÉFRACTAIRES EN PLACE. 

NE PAS SURCHAUFFER – SI LE POÊLE OU LE CONNECTEUR DE CHEMINÉE SE MET À ROUGIR, VOUS SURCHAUFFEZ. INSPECTEZ ET NETTOYEZ FRÉQUEMMENT LA 

CHEMINÉE ET LE CONNECTEUR. EN CERTAINES CONDITIONS D’UTILISATION, UN DÉPÔT DE CRÉOSOTE PEUT SE FORMER RAPIDEMENT. GARDEZ LES MEUBLES ET 

AUTRES MATÉRIAUX COMBUSTIBLES ÉLOIGNÉS DU POÊLE

REMPLACEZ LA VITRE SEULEMENT PAR DU VERRE EN NEOCERAM 

.

LE PLANCHER COMBUSTIBLE DOIT ÊTRE PROTÉGÉ PAR DES MATÉRIAUX NON COMBUSTIBLES DÉPASSANT DU DESSOUS, DU DEVANT ET DES CÔTÉS DU POÊLE, TEL 

QU’INDIQUÉ, OU JUSQU’AU MATÉRIAU COMBUSTIBLE LE PLUS PRÈS PERMIS.

COMPONENTS OPTIONNELS: VENTILLATEUR (846-515), ÉVALUATION ÉLECTRIQUES: VOLTS 115, 60 HZ, 2 AMPS., AIRMATE, OUTSIDE AIR KIT, CENDRIER, COMBUSTER 
PART  NO. 051-53CETTE APPAREILLE A BOIS CONTIENT UNE CHAMBRE DE COMBUSTION CATALYTIQUE, QUI A BESOIN D`INSPECTION ET DE REMPLACEMENT PÉRIODI-
QUEMENT POUR LE FONCTIONNEMENT APPROPRIE. CONSULTER LE MANUEL D'INSTALLATION PUR DE PLUS AMPLES INFORMATION. II EST CONTRE LA LOI D'AC-
TIONNEUR CETTE APPAREILLE A BOIS EN QUELQUE SORTE CON TRADICTOIRE AVE LES CONSIGNES D'UTILISATION DU MANUEL, OU SI L'ÉLÉMENT CATALYTIQUE EST 

ENLÈVE OU DÉSACTIVÉ.
ATTENTION: RISQUE DU CHOC ÉLECTRIQUE. AVANT DE L'ENTRETIEN, DÉBRANCHER L'APPAREIL. NE PLACEZ PAS LE CORDON D'ALIMENTATION EN FACE OU EN DES-
SOUS DE L'APPAREIL. 
REMARQUE:  D'ÉPLACER LES PIÈCES PEUVENT CAUSER LES BLESSEURS.  L'APPAREIL NE DEVRAIT JAMAIS ÊTRE UTILISÉ LORSQUE FAN HOSING IS REMOVED
REMARQUE: TEMPÉRATURES ÉLEVÉES.  NE JAMAIS FAIRE FONCTIONNER L’APPAREIL SI LA PORTE VITRÉE N'EST PAS BIEN EN PLACE.
COMPOSANTS EXIGÉS POUR INSTALLATION DANS UNE MAISON MOBILE : KIT DE PRISE D’AIR EXTÉRIEUR ET L’UN DES CONNECTEURS DE CHEMINÉE À DOUBLE PAROI 
SUIVANTS :
AU CANADA: CONNECTEURS DE CHEMINÉE HOMOLOGUÉS À DOUBLE PAROI : LISTED SECURITY MODEL DP, OR OLIVER MACLEOD PRO-VENT PV DOUBLE WALLED 
CONNECTOR WITH LISTED CHIMNEY SYSTEM: LISTED SECURITY MODEL SECURITY S2100+, ICC EXCEL 2100, SIMPSON DURA-PLUS HTC, SELKIRK SENTINAL CF.
AUX ÉTATS-UNIS : CONNECTEURS DE CHEMINÉE HOMOLOGUÉS À DOUBLE PAROI: SECURITY MODEL DP, SELKIRK MODEL DS, OLIVER MACLEOD PRO VENT PV, SIMP-
SON DURA VENT MODEL DVL, METAL-FAB DOUBLE WALL.  CONNECTÉ À L’UN DES SYSTÈMES DE CHEMINÉE COMPATIBLES SUIVANTS:SELKIRK SURE-TEMP, PROJET 
Nova Temp, SECURITY SECURE TEMP ASH+, SECURITY SECURE TEMP S-2100+, METAL-FAB TEMP/GUARD 2100, AMERI-TEC HS, ICC EXCEL 2100 .  
UTILISER LES COMPOSANTS DE CHEMINÉE SPÉCIFIÉS DANS LES INSTRUCTIONS D’INSTALLATION.

FLOOR 

PROTECTION*

INSTALL AND USE ONLY IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION AND OPERATING INSTRUCTIONS.  CONTACT LOCAL BUILDING 
OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION IN YOUR AREA.  USE 8"(203 MM) DIAMETER MINIMUM 24 MSG BLACK OR 
26 MSG BLUED STEEL CONNECTOR WITH LISTED UL103 HT FACTORY-BUILT CHIMNEY SUITABLE FOR USE WITH SOLID FUELS OR MASONRY CHIMNEY. 
DOUBLE WALL CONNECTOR ONLY. 
SEE LOCAL BUILDING CODE AND MANUFACTURER'S INSTRUCTIONS FOR PRECAUTIONS REQUIRED FOR PASSING A CHIMNEY THROUGH A COMBUSTIBLE 
WALL OR CEILING.  DO NOT PASS CHIMNEY CONNECTOR THROUGH COMBUSTIBLE WALL OR CEILING.  DO NOT CONNECT THIS UNIT TO A CHIMNEY 
FLUE SERVING ANOTHER APPLIANCE.
CAUTION:

 BURNING OF MATERIAL OTHER THAN THE SPECIFIED FUELS MAY MAKE THE CATALYST IN THE COMBUSTOR INACTIVE. THE COMBUSTOR 

IS FRAGILE, HANDLE CAREFULLY.
THE PERFORMANCE OF THE CATALYTIC DEVICE OR ITS' DURABILITY HAS NOT BEEN EVALUATED AS PART OF THE CERTIFICATION.

INSTALLER ET UTILISER SEULEMENT SELON LES INSTRUCTIONS D’INSTALLATION ET D’UTILISATION DU FABRICANT.

CONTACTER LES RESPONSABLES DU BÂTIMENT OU DU SERVICE-INCENDIE DE VOTRE RÉGION POUR CONNAÎTRE LES RESTRICTIONS ET EXI-

GENCES D’INSPECTION DANS VOTRE RÉGION. UTILISER UN CONNECTEUR D’UN DIAMÈTRE MINIMAL DE 203 MM (8PO) 24 MSG EN ACIER NOIR OU 

26 MSG EN ACIER BRONZÉ AVEC CHEMINÉE PRÉFABRIQUÉE HOMOLOGUÉE 

CONÇUE POUR UTILISATION AVEC COMBUSTIBLES SOLIDES OU UNE CHEMINÉE DE MAÇONNERIE.

VOIR LE CODE DU BÂTIMENT LOCAL ET LES INSTRUCTIONS DU FABRICANT CONCERNANT LES PRÉCAUTIONS  EXIGÉES POUR INSTALLER UNE 

CHEMINÉE TRAVERSANT UN MUR OU PLAFOND EN MATÉRIAUX COMBUSTIBLES. NE FAITES PAS TRAVERSER LE CONNECTEUR DE CHEMINÉE 

DANS UN MUR OU PLAFOND EN MATÉRIAUX COMBUSTIBLES. NE RACCORDEZ PAS CE POÊLE À BOIS À UN CONDUIT DE CHEMINÉE DESSERVANT 

UN AUTRE APPAREIL.

CERTIFICATION DU MAISON MOBILE,  APPAREIL DE CHAUFFAGE AMBIANT HOMOLOGUÉ À COMBUSTIBLE SOLIDE, CONVENANT AUSSI POUR 

INSTALLATION DANS UNE MAISON MOBILE. 

In USA:

V    203 mm / 8"

W   406 mm / 16" 

X  914 mm  /  36"

Y  1299 mm  /  51-1/8" 

Z  203 mm  /  8"

In Canada:

V    203 mm / 8"

W   450 mm / 18" 

X  914 mm  /  36"

Y  1349 mm  /  53-1/8" 

Z  203 mm  /  8"

2022

2021

2024

2025

2023

525

A

E

D

B

G

A

E

D

B

F

C

C

H

B

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS

INSTALLATION USING 8" LISTED DOUBLE WALL 

CONNECTOR ONLY: RESIDENTIAL, ALCOVE, MOBILE 

HOME

To Top of stove: 
A)  279mm / 11"

To Flue Centre Line:
E)  435mm / 17-1/8"

To Rear Shield:
B)  254mm / 10"

To Flue Centre Line:
 F)  572mm / 22-1/2"

To Corner of Stove:
C)  203mm / 8"

Alcove width:
G)  1600mm / 63"

To Flue Centre Line:
D)  648mm / 25-1/2"

To Top of Flue: 
H)  152mm / 6"

Y

X

Z

W

V

OMNI-Test Laboratories, Inc.

Report # 0219WS016S

MANUFACTURED BY: 

REGENCY FIREPLACE PRODUCTS

6988 VENTURE ST.

DELTA, BC  V4G 1H4

MADE IN CANADA

MINIMUM PARALLEL / ALCOVE CEILING HEIGHT: 2.1 M / 83"         MAXIMUM ALCOVE DEPTH 1219 MM / 48 IN. 

HAUTEUR MINIMALE DU PLAFOND DE L’ALCÔVE : 2,1 M / 83PO.  PROFONDEUR MAXIMALE DE L’ALCÔVE : 1219MM / 48 PO.

      

U.S. ENVIRONMENTAL PROTECTION AGENCY CERTIFIED TO COMPLY WITH 2020 PARTICULATE EMISSION STANDARDS USING CORD WOOD.”  TESTED TO 
ASTM E3053.  MODEL REGENCY F5200M – 0.9G /HR. THIS WOOD HEATER NEEDS PERIODIC INSPECTION AND REPAIR FOR PROPER OPERATION. CONSULT 
THE OWNER'S MANUAL FOR FURTHER INFORMATION. IT IS AGAINST FEDERAL REGULATIONS TO OPERATE THIS WOOD HEATER IN A MANNER INCONSIS-
TENT WITH THE OPERATING INSTRUCTIONS IN THE OWNER'S MANUAL.
CERTIFIÉ CONFORME AUX NORMES 2020 DU U.S. ENVIRONMENTAL PROTECTION AGENCY EN MATIÈRE D'ÉMISSION DE PARTICULES DE BOIS AVEC DU 
BOIS DE CORDE''. APPROUVÉ ASTM E3053. MODÈLE REGENCY F5200M – 0,9 G /H. CET APPAREIL DE CHAUFFAGE AU BOIS DOIT ÊTRE INSPECTÉ PÉRI-
ODIQUEMENT ET RÉPARÉ POUR FONCTIONNER CORRECTEMENT. CONSULTER LE MANUEL D’INSTALLATION POUR PLUS D’INFORMATION. LA RÉGLEMEN-
TATION FÉDÉRALE INTERDIT DE FAIRE FONCTIONNER UN TEL APPAREIL SI LES CONSIGNES D'UTILISATION CONTENUES DANS LE PRÉSENT MANUEL NE 
SONT PAS RESPECTÉES.

SAFETY LABEL FOR F5200

Summary of Contents for Pro Series

Page 1: ...omplete the details on the back cover and leave this manual with the homeowner Homeowner Please keep these instructions for future reference Owners Installation Manual Tested by www regency fire com F5200 Video French Manual https bit ly 3qAsPmW Manuel en Français https bit ly 3qAsPmW Pro Series Freestanding Woodstove 0219WS016S ...

Page 2: ...is manual or if the catalytic element is deactivated or removed This wood heater contains a catalytic combustor which needs periodic inspection and replacement for proper operation It is against the law to operate this wood heater in a manner inconsistent with operating instructions in this manual or if the catalytic element is deacti vated or removed CAUTION BURN UNTREATED WOOD ONLY OTHER MATERIA...

Page 3: ...oke Deflector Installation Replacement 19 Brick Installation 20 Fan Installation 21 Operating Instructions Seasoned Wood 22 Operating Instructions 23 Draft Control 23 First Fire 23 Fan Operation 24 Ash Disposal 24 Safety Guidelines and Warnings 24 Troubleshooting Guide 25 Maintenance Maintenance 26 Thermometer 26 Creosote 26 Door Catch Adjustment 26 Door Gasket 26 Glass Maintenance 26 Wood Storage...

Page 4: ... LES CONSIGNES D UTILISATION DU MANUEL OU SI L ÉLÉMENT CATALYTIQUE EST ENLÈVE OU DÉSACTIVÉ ATTENTION RISQUE DU CHOC ÉLECTRIQUE AVANT DE L ENTRETIEN DÉBRANCHER L APPAREIL NE PLACEZ PAS LE CORDON D ALIMENTATION EN FACE OU EN DES SOUS DE L APPAREIL REMARQUE D ÉPLACER LES PIÈCES PEUVENT CAUSER LES BLESSEURS L APPAREIL NE DEVRAIT JAMAIS ÊTRE UTILISÉ LORSQUE FAN HOSING IS REMOVED REMARQUE TEMPÉRATURES É...

Page 5: ...16 39 3 4 3 7 1 8 28 1 16 31 3 16 792mm 735mm 181mm 76mm 930mm 962mm 986mm 1010mm 737mm 27 15 8 689mm ALL PICTURES DIAGRAMS SHOWN THROUGHOUT THIS MANUAL ARE FOR ILLUSTRATION PURPOSES ONLY ACTUAL PRODUCT MAY VARY DUE TO PRODUCT ENHANCEMENTS Shown with optional fan 8 203mm diameter flue collar ...

Page 6: ...6 F5200 Regency Freestanding Woodstove 6 dimensions WOOD STOVE OUTSIDE AIR DIMENSIONS With pedestal from base of unit to centerline 5 1 2 138mm Rear ...

Page 7: ...d to the floor by using the bolt down holes inside the pedestal the same ones used in Mobile Home installations 11 For residential installations 8 double wall chimney only the chimney connector must be at least 24 gauge steel Do not use galvanized pipe For Mobile Home installation refer to the Mobile Home installation instructions within this manual 12 DO NOT CONNECT THIS UNIT TO A CHIM NEY SERVIN...

Page 8: ...the rear heat shield See Diagrams 2 3 Rear Heat Deflector Assembly for F5200 The rear heat deflector is supplied with the stove and must be installed unless the optional airmate has been selected It stops the heat radiated from the flue collar from overheating the rear wall The rear heat deflector is installed on top of the rear heat shield as shown in Diagram 4 Side Shield Adjustment The left and...

Page 9: ...tor A B C D E F 11 279mm 10 254mm 8 203mm 25 1 2 648mm 17 1 8 435mm 22 1 2 572mm Mobile Home Close Clearance To be installed with required pipe components Listed Double Wall Pipe When the stove is installed as a close clearance residential unit a listed double wall connector is required from the stove collar to the ceiling level Refer to Mobile Home Installation in this manual F5200 withAirmateor ...

Page 10: ...18 450mm to the front and 8 203mm to each side measured from fuel door opening and back of the stove Minimum Overall Depth Y of Floor Protector Unit Residential Close Clearance Mobile Home Close Clearance Alcove F5200 Y Z Y Z Y Z USA 51 1 8 1299mm 8 203mm 51 1 8 1299mm 8 203mm 51 1 8 1299mm 8 203mm Canada 53 1 8 1349mm 8 203mm 53 1 8 1349mm 8 203mm 53 1 8 1349mm 8 203mm The rear clearance to combu...

Page 11: ...s through and T section package firestops where needed insulation shield roof flashing chimney cap etc Maintain proper clearance to the structure as recommended by the manufacturer The chimney must be the required height above the roof or other obstructions for safety and proper draft operation Minimum vertical of 36 before any offset Horizontal Maximum of 36 with 1 4 rise per foot NOTE Recommend ...

Page 12: ...mper may have to be removed to allow installation Minimum vertical of 36 before any offset Horizontal Maximum of 36 with 1 4 rise per foot NOTE Recommend using 2 45º instead of 90º to improve draft and performance NOTE Approved with listed double wall pipe only Do not use single wall pipe Max 36 Horizontal Min 36 Vertical Rise 6 152mm 10 254mm NOTE Must be 8 203mm in diameter This chimney cannot b...

Page 13: ...combustibles Masonry chimney Chimney Flue Minimum chimney clearance to brick and combustibles 2 in 50 8mm Minimum clearance 12 in 304 8mm of brick Chimney connector Fire clay liner Starting with a minimum 24 gage 024 61 mm 8 203 2 mm metal chimney connector and a minimum 24 gage ventilated wall thimble which has two air channels of 1 25 4 mm each construct a wall pass through There shall be a mini...

Page 14: ...ut and frame the roof hole It is recommended that no ceiling support member be cut for chimney and support box installation If it is necessary to cut them the members must be made structurally sound 2 Install radiant shield and support from above 3 Stack the insulated pipe onto your finish sup port to a minimum height of 3 feet above the roof penetration or 2 feet above any point within 10 feet me...

Page 15: ...Addition at sea level 9 ft Recommended Flue Height Elevation Example a Example b 0 18 21 1000 18 72 21 84 2000 19 44 22 68 5000 21 60 25 20 8000 23 76 27 72 MINIMUM RECOMMENDED FLUE HEIGHTS IN FEET Measured from the top of the unit ELEVATION FT ABOVE SEA LEVEL NUMBER OF ELBOWS For listed double wall pipe 0 2 x 15o 2 x 30o 2 x 45o 0 1000 12 0 13 0 15 0 16 0 1000 2000 12 5 13 5 15 5 16 5 2000 3000 1...

Page 16: ...ositioned aguardormethodofenclosing the chimney shall be fitted at the point of exit for a height up to 7ft 2130mm 6 The chimney shall be attached directly to the room heater and shall extend at least 3 ft 914mm above the part of the roof through whichitpasses Thetopofthechimneyshould project at least 2ft 610mm above the high est elevation of any part of the Mobile Home within 10 ft 3048mm of the ...

Page 17: ...e Air Through Pedestal Rear Remove the blanking plate from the rear of the pedestal and bend the two tabs out 90 degrees Pipe fresh air into the pedestal area by using a minimum 4 metallic duct pipe with a mesh grill at the outside termination Fasten the pipe to the cover plate using the tabs and 2 screws Damper Installation NOTE The damper cannot be installed if attaching outside air to the botto...

Page 18: ...useunlabelled parts or substitute parts made for another chimney system Installasperchimneymanufacturer sinstal lation instructions LISTED COMPONENTS FOR MOBILE HOME INSTALLATION TheRegencyF5200Freestandingpedestalunits are approved for installation in a Mobile Home if one of the following pipe systems is used NOTE Requireddoublewallchimneyconnector mustbeingoodconditionandkeptclean U S Installati...

Page 19: ...flector loosen off both 7 16 bolts and slide deflector up ward and out Install new deflector and hand tighten 7 16 hex head bolts Ensure positive location of the deflector prior to hand tightening WARNING Operation of the unit without proper installation of smoke deflector will void warranty 3 Ensure deflector is seated so bolts are situated at the top of the opening before tightening Hand tighten...

Page 20: ... a grate 1 Remove box of firebricks from inside unit 2 Remove Lyotherm sheet from mailer tube and install on base of firebox as shown below NOTE The AD brick covers the Ash Dump hole that is used when the Ash Drawer Kit is installed Lytherm Sheet Final Install 3 Order of firebrick install a Rear Firebrick b Firebox floor install brick over Lytherm Sheet c Right and left side Firebricks Fire bricks...

Page 21: ... off continuously the thermo switch sensor is not making contact with the stove body Remove the fan bend the bracket closer to the stove and re install the fan MANUAL To manually operate the fan system push the bottom switch to MAN and the top switch to either HIGH or LOW This will bypass the sensing device and allow full control of the fan Switching from AUTO to MAN or HIGH to LOW may be done any...

Page 22: ...sides Softer woods like pine spruce and poplar aspen that is cut split and stacked properly in the early spring maybe be ready for burning in the fall Extremely hard woods like oak and maple and large pieces of firewood may take a minimum of a full year to dry enough Drying may also take longer in damp climates There are a few ways to tell if wood is dry enough to burn efficiently Use as many indi...

Page 23: ...tal has been warmed Left Open Right Closed Back Closed Front Open Primary Air Damper Catalyst Bypass Control DRAFT CONTROL Both the primary and air wash drafts are controlled by the control slide located on the front left side of the unit when facing the unit To increase your draft slide to the left to open and to decrease slide to the right to close The F5200 unit has a secondary draft system tha...

Page 24: ...revent smoke spillage as this may set off a false alarm 5 Donotoverfireheater Ifthechimneyconnector flue baffle or the stove top begin to glow you are over firing Stop adding fuel and close the draft control Over firing can cause extensive damage to your stove including warping and premature steel corrosion Over firing will void your warranty 6 Do not permit creosote or soot build up in the chimne...

Page 25: ...iameter wood with the combustor in the operating position without light off ever occurring Burn dried seasoned wood Make sure combustor has light off before closing the bypass damper It may be possible to burn off the soot or creosote accumulation by putting the combustor in a partially open and partially closed position after a hot fire has been started Masking Soot Combustor has not maintained a...

Page 26: ...wice a year during the first year of use and at least once a year thereafter or when a significant layer of creosote has accumulated 3 mm 1 8 or more it should be removed to reduce the risk of a chimney fire DOOR CATCH ADJUSTMENT The door Catch may require adjustment as the door gasket compresses after a few fires The door latch compression may require adjustment to renew seal Removal of the space...

Page 27: ...gth of your heating season and how often you use your stove Proper maintenance will increase the combustor s effectiveness and pre vent many problems Inspect your combustor before each heating season and during the season if your stove s performance seems to change This catalytic heater is equipped with a temperature probe to monitor cata lyst operation Properly functioning combustors typically ma...

Page 28: ...R First clean the combustor area and the area around the by pass use a vacuum cleaner Lift the new combustor into position with the stainless flanges on each end facing forward The combustor should slide easily into position you may need to pinch down the top center with your finger to start gently push as far to the back of the stove as possible Replace the flame shield in the orientation shown b...

Page 29: ...embly to reveal gasket 3 Loosen the 3 rear nuts then remove 3 front nuts Support the Bypass Door from the front back and slide forward to remove Bypass Door Assembly Note if any of the bolts become damaged the bolt bracket assemblies may be replaced see next page Important Bypass door is very heavy 18 lbs use caution when servicing 6 Reverse steps to reinstall ensure the pass rod is seated with th...

Page 30: ... channel on right F5200 Airtube Replacement BYPASS DOOR BOLT BRACKET ASSEMBLY REPLACEMENT If any of the bolts used to secure the bypass door become damaged the bypass door bolt bracket assembly can be replaced 1 Allow the stove to burn out and cool down until cool to touch 2 Remove bypass door before attempting to remove bolt bracket assembly see detailed instructions on previous page 3 Open stove...

Page 31: ...e baffle into the stove in the orientation shown below SIDE BAFFLE INSTALLATION REMOVAL 3 Manoeuvre the side baffle underneath the upper corner filler then let the baffle rest on the side of the combustor housing 4 Repeat process on other side Corner filler Side Baffle Orientation Side Baffle Installed This edge to outside of firebox ...

Page 32: ...ney cleaning recommended DOOR CATCH ADJUSTMENT The door catch may require adjustment as the door gasket compresses after a few fires The door catch compression may require adjustment to renew seal Removal of the spacer washer shown in the Diagram below will allow the catch to be moved closer to the door frame causing a tighter seal Remove and replace the nuts washer and spacer as shown Spacer wash...

Page 33: ...ly not shown 063 954 Airtube 1 x 23 long Part Description 11 051 067 Thermometer 051 221 Cast Bypass Door 936 074 Gasket Bypass Door per foot 12 051 003 Stainless Steel Smoke Deflector 13 051 509 Door Hinge Assembly 14 106 561 Door Catch assembly 15 156 241 Removable Cast Handle 051 006 L R stainless steel firebox filler 051 085 Gasket Bypass Frame 051 510 Bypass Frame 3 bolt assembly ea 19 948 22...

Page 34: ...00 Regency Freestanding Woodstove 34 parts list F5200 STOVE BRICK LAYOUT Fire bricks Size 1 4 1 2 x 9 2 2 x 9 3 3 1 2 x 4 1 2 4 1 3 4 x 4 1 2 5 2 x 7 5 4 2 2 3 1 1 1 1 1 1 AD Brick 051 960 Brick Set Complete ...

Page 35: ...155 HINGE PIN 5 940 384 P GLASS CERAMIC 6 936 243 TAPE 7 8 WINDOW ADHESIVE Part Description 7 051 058 GASKET BRACKET TOP BOTTOM 8 051 056 GLASS GASKET FRAME 9 936 077 5 8 MEDIUM DENSITY 936 077 10 904 809 SCREW 1 4 20 x 3 8 TUSS HD PHIL ZINC PD ea 11 904 146 SCREW 10 x 1 2 SELFTAP PAN HD PHILIPS ea 12 904 513 HEX BOLT 1 4 20 x 3 4 LG ea 051 057 SIDE GASKET BRACKET ea 846 551 DOOR GLASS GASKET REPA...

Page 36: ...Crazing 1 Catalyst Combustor 10 Years Prorated Venting Chimney 1 Screens 1 See specific warranty details in regards to the catalyst combustor in unit manual Conditions Warranty protects against defect in manufacture or FPI factory assembled components only unless herein specified otherwise Any part s found to be defective during the warranty period as outlined above will be repaired or replaced at...

Page 37: ... incorrect chimney components including but not limited to cap size or type operator error abuse misuse use of improper fuels such as unseasoned cordwood mill ends construction lumber or debris off cuts treated or painted lumber metal or foil plastics garbage solvents cardboard coal or coal products oil based products waxed cartons compressed pre manufactured logs kiln dried wood lack of regular m...

Page 38: ...mages so the above limitations or exclusions may not apply to you Customers located outside the U S should consult their local provincial or national legal codes for additional terms which may be applicable to this warranty How to Obtain Warranty Service Customers should contact the authorized selling dealer to obtain all warranty and service In the event the authorized selling dealer is unable to...

Page 39: ...in order for us to serve you better Warranty Registration Form or Register online immediately at the above Web Site Warranty Details Serial Number required Purchase Date required mm dd yyyy Product Details Product Model required Dealer Details Dealer Name required Dealer Address Dealer Phone Installer Date Installed mm dd yyyy Your Contact Details required Name Address Phone Email For purchases ma...

Page 40: ......

Page 41: ...thin the ten 10 year period 4 Second replacement at 50 off retail within the original ten 10 years 5 Subsequent replacements or if ten 10 year coverage has expired at full retail price 6 The catalytic combustor must not have been mechanically abused nor must the wrong fuels have been used in the appliance 7 All claims must be accompanied by clear photos of the catalytic combustor showing all damag...

Page 42: ...42 F5200 Regency Freestanding Woodstove 42 warranty ...

Page 43: ......

Page 44: ...r Name Address _______________________________________________ ___________________________________________________________________ Installer ____________________________________________________________ Phone ____________________________________________________________ Date Installed _______________________________________________________ Serial _____________________________________________________...