10
|
F5200 Regency Freestanding Woodstove
|
10
installation
*8
*8
8
8
*
*
*
*
FLOOR PROTECTION
(EMBER PROTECTION ONLY
REQUIRED)
A combustible floor must be protected by non-combustible
material (like tile, concrete board, or certified to UL-1618 or
as defined by local codes) extending beneath the heater and
a minimum of 8" (203mm) from each side and minimum 16"
(406mm) (USA) from the front face of the stove and minimum
8" (203mm) (or the rear clearance to combustibles whichever
is smaller) from the rear of the stove.
When installed with horizontal venting, non-combustible floor
protection must beneath the flue pipe and extend 2" (51mm)
beyond each side.
Minimum Overall Width (X) of Floor
Protector
for all installations:
Stove
F5200
36" (914 mm)
NOTE: In Canada, floor protection must extend 18" (450mm) to the front
and 8" (203mm) to each side (measured from fuel door opening)
and back of the stove.
Minimum Overall Depth (Y) of Floor Protector
Unit
Residential
Close Clearance
Mobile Home
Close Clearance
Alcove
F5200
Y
Z
Y
Z
Y
Z
USA
51-1/8"
(1299mm)
8"
(203mm)
51-1/8"
(1299mm)
8"
(203mm)
51-1/8"
(1299mm)
8"
(203mm)
Canada
53-1/8"
(1349mm)
8"
(203mm)
53-1/8"
(1349mm)
8"
(203mm)
53-1/8"
(1349mm)
8"
(203mm)
The rear clearance to combustibles is less than 6" (for corner installations the rear corners may
be angled to take advantage of the closer clearances.
Minimum Overall Depth (Y) of Floor Protector - Corner Hearth
Hearth Depth
F5200
L
M
N
O
Canada
36"
(914mm)
69-1/2"
(1765mm)
57-5/8"
(1464mm)
32-3/16"
(818mm)
USA
36"
(914mm)
67-1/2"
(1714mm)
56-1/4"
(1429mm)
30-3/4"
(781mm)
Reference only when hearth pad is installed to rear wall at minimum pipe clearances.
Residential Close Clearance (To be installed with required pipe components)
*Measurement is taken from fuel door opening
NOTE:
USA clearances shown above.