30
|
Regency Horizon® HZ40E-11 Gas Fireplace
installation
Vent Guard - if required*
(Part #946-506/P)
175mm
Notes:
1. Liner sections should be continuous without any
joints or seams.
2. Only Flex pipe purchased from Regency
®
may be
used for Flex installations
3. Horizontal vent must be supported every 3 feet.
4. Regency
®
Direct Vent System (Flex) is only approved
for horizontal terminations.
5. Flex system can only be used up to a maximum
continuous vent length of up to 10 feet. If longer
runs are required, rigid pipe must be used.
Horizontal Terminations
Flex Vent 4" x 6-7/8"
These venting systems, in combination with the HZ40E Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by Warnock
Hersey/ Intertek. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent Termination
Locations" section.
Regency
®
Direct Vent (Flex) System Termination Kits includes all the parts needed to install the HZ40E using a flexible vent.
FPI Kit #
Length
Contains:
#946-513
2 Feet
1.
6-7/8” flexible outer liner (Kit length)
2.
4” flexible inner liner (Kit length)
3.
spring spacers
4.
thimble
5.
AstroCap
termination cap
6.
screws
7.
tube of Mill Pac
8.
plated screws
9.
S.S. screws #8 x 1-1/2” drill point
#946-515
4 Feet
#946-516
10 Feet