Horizontal Terminations - Inline Power Vent
4" x 6-5/8" Flex Vent
These venting systems, in combination with the CB40EPV Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Intertek.
The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent Termination Locations" section.
Regency
®
Direct Vent (Flex) System Termination Kits include all the parts needed to install the CB40EPV using a flexible vent.
920-210c
10.04.21
5
CV72EPV/CB72EPVCB40EPV/CC40EPV/CV40EPV/CB60EPV/CV60EPV
Inline Power Vent Vertical or Hortizontal Installation Instructions
Vent Reducer
(Part #946-758)
Vent Guard - if required
(Part #946-506/P)
(TM)
AstroCap
Termination Cap
(Part #946-523/P)
Wall Thimble
Adaptor Pipe
(Part # 946-219/P)
Maximum 2 - 20'
(6.10 m)
long liners
6-5/8" (152 mm)
Dia. Flue Pipe
4" (102 mm)
Dia. Flue Pipe
Power Vent Terminal
(Part # 666-945)
Notes:
1. Only Flex pipe purchased from Regency
®
may be
used for Flex installations
2. Horizontal vent must be supported every 3 feet (0.91
m).
3. Regency
®
Direct Vent System (Flex) is only approved
for horizontal terminations.
4. Flex system can only be used up to a maximum vent
length of up to 40 feet (12.19 m) using up to 2 x 20
ft (6.10 m) flex kits (part # 946-756). If longer runs
are required, rigid pipe must be used.
5. Must use adaptor pipe (946-219/P) to connect inner
flex pipe as shown.
Horizontal Terminations-Inline Power Vent
4" x 6
-5/8" Flex Vent
These venting systems, in combination with this model Direct Vent Gas Fireplace, have been tested and listed as a direct vent heater system by Intertek. The
location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent Termination Locations" section.
Regency
®
Direct Vent (Flex) System Termination Kits include all the parts needed to install this model using a flexible vent.
Maximum total vent length = 72' (21.95 m) maximum
of six-90
0
elbows permitted.
One 90
0
elbow = two 45
0
elbows
Maximum total negative vent length = 7' (2.13 m)
Note: Maximum length of 72' (21.95 m) is based
on overall length of combined chimney
components.
Do not run positive venting after a negative run.
Inline power vent location restrictions:
Minimum 4 ft (1.22 m) from the unit
Minimum 1 ft (0.3 m) prior to an elbow.
Minimum 1 ft (0.3 m) following an elbow.
Minimum 1 ft (0.3 m) prior to a termination cap.
Minimum 6 ft (1.82 m) rise from top of unit if there
is a negative run.
Power Vent Kit (Part 666-945)
2 Max.
946-756
20' Flex Kit
Sold separately
1
Power Vent Fan
Included w/Power Vent kit
1
911-250/P
45' (13.72 m)-5 Wire BX Cable
or
Sold separately
1
911-251/P
90' (27.43 m) 5-Wire BX Cable Sold separately
1
666-945
Power Vent Kit
Sold separately
1
946-219/P
Adaptor Pipe
Included w/power vent kit
1
946-206
Vinyl Siding Standoff
Sold separately
1
946-523/P
Astro Cap Termination
Sold separately
1
946-763
Wall Thimble
Sold separately
1
946-506/P
Vent Guard
Sold separately
CV72EPV shown
Summary of Contents for CB40EPV-LP
Page 120: ...120 City Series CB40EPV ...
Page 121: ...City Series CB40EPV 121 notes ...
Page 122: ...122 City Series CB40EPV notes ...
Page 123: ...City Series CB40EPV 123 warranty ...