City Series CB40EPV
|
35
installation
Framing Dimensions CB40EPV
NOTE:
Framing may be constructed of combustible material (ie. 2x4) and does not require steel studs. Two (2) optional steel stud kits may also be purchased.
These kits may be used in place of the conventional wood framing as shown below. It comes as a compact kit (flush to the appliance on all sides)or
an extended kit. The extended kit protrudes beyond each side of the appliance as shown on the front cover of this manual. There is also an optional
hearth kit which may be purchased as shown on the front cover of this manual. These kits are highly recommended as it was designed specifically for
the product to facilitate ease of installation. See instructions in this manual for details.
Framing Dimensions
Description
CB40EPV
A
Framing Height
37-3/8” (949 mm)
B
Framing Width
48-1/2" (1232 mm)
C**
Framing Depth
19" (483 mm)
D
Minimum Height to Combustibles
63"(1600 mm)
G*
Vent Centerline Height
45-1/2" (1156 mm)
*
Important:
Minimum overall vent run must be 4 feet (1.21 m). Even though centerline is 45 1/2" (1156 mm), if appliance is framed at minimum
depth, the 4 feet (1.21 m) of vent run could not be obtained. Center line will need to be increased in height in order to achieve a minimum vent
run of 4 feet.
Note:
A combined minimum of 120 square inches of open area is required for the convection air outlet to cool the enclosure. Ensure clearances for Convection
Air Outlets are met. See clearances CB40EPV (3 sided) in this manual as there are different methods as to how this can be achieved.
Note:
Only basic framing dimensions are shown. The framing may also extend beyond the appliance on either side and also extend out front if a hearth is
desired. See clearance/finishing requirements for details.
Note:
Unit is not load bearing. All finished materials must be supported by framing.
Note
: This appliance must be in-
stalled on a solid surface such as
a plywood floor which must be the
full width and depth of the appliance.
*
*The framing depth does not take into account drywall/wood or
similar materials against the back wall. The framing depth will
need to change based on the thickness of the material (example:
19'' framing depth + 1/2'' drywall = 19-1/2'')
Note: Wood
header on edge
may be 2'' x 4'' or
2'' x 6''.
Maximum material dimen-
sions 2" x 4" for wood
studs in front and both
sides. Studs behind can
be either 2'' x 4'' or 2'' x 6''.