40
|
City Series ACC40E
installation
Vent Guard - if required*
(Part #946-506/P)
102mm
Horizontal Terminations
Flex Flue 102mm x 175mm
These venting systems, in combination with the ACC40LE/ACC40RE Direct Flue Gas Fireplace, have been tested and listed as a direct flue heater system
by Warnock Hersey/ Intertek. The location of the termination cap must conform to the requirements in the Flue Terminal Locations diagram in "Exterior Flue
Termination Locations" section.
Regency
®
Direct Flue (Flex) System Termination Kits includes all the parts needed to install the ACC40LE/ACC40RE using a flexible flue.
FPI Kit #
Length
Contains:
#946-515
1.2m
1.
175mm flexible outer liner (Kit length)
2.
102mm flexible inner liner (Kit length)
3.
spring spacers
4.
thimble
5.
AstroCap
termination cap
6.
screws
7.
tube of Mill Pac
8.
plated screws
9.
S.S. screws #8 x 38mm drill point
#946-516
3m
Notes:
1. Liner sections should be continuous without any joints
or seams.
2. Only Flex pipe purchased from Regency
®
may be used
for Flex installations
3. Horizontal vent must be supported every 0.9m.
4. Regency
®
Direct Vent System (Flex) is only approved for
horizontal terminations.
5. Flex system can only be used up to a maximum continu-
ous vent length of up to 3m. If longer runs are required,
rigid pipe must be used.