Troubleshooting
60
Error List
REFUsol 100K
982059/02
2020-11
A017F
HW VPos activation
The hardware protection has detected an im
-
permissible overvoltage in the positive DC link
during the activation phase.
▸
Check DC voltage for permissible range.
A0180
HW VNeg activation
The hardware protection has detected an im
-
permissible overvoltage in the negative DC
link during the activation phase.
A0181
HW PowNok activation
The hardware protection has detected a prob
-
lem with the circuit-breakers during the acti
-
vation phase.
▸
If error occurs more than once, contact
REFU Service.
A0182
HW DcUnsy activation
The hardware protection has detected an im
-
permissible asymmetry in the DC link during
the activation phase.
▸
Open and close the DC switch.
▸
If this error occurs more than once, contact
REFU Service.
A0183
HW driver activation
The hardware protection has detected a prob
-
lem in the circuit breaker driver during the ac
-
tivation phase.
A0184
HW I L1 activation
The hardware protection has detected an im
-
permissible overcurrent in L1 during the acti
-
vation phase.
A0185
HW I L2 activation
The hardware protection has detected an im
-
permissible overcurrent in L2 during the acti
-
vation phase.
A0186
HW I L3 activation
The hardware protection has detected an im
-
permissible overcurrent in L3 during the acti
-
vation phase.
Error Code Message
Description
Instructions