Disposal
50
Periodicity of Maintenance
REFUsol 100K
982059/02
2020-11
* Shorter maintenance intervals may be required
(depending on location and ambient conditions)
10 Disposal
Dispose of the packaging and replaced parts
according to the rules applicable in the country where
the product is installed. Do not dispose of the
REFUsol
100K
with normal domestic waste. The
REFUsol 100K
conforms to RoHS.
▷
REFU Elektronik GmbH takes the
REFUsol 100K
back
completely. Please contact the REFU Service team!
Checking the PowerUnit fans for function and
operating noise.
12 months
Checking the ConnectionBox fans for function
and operating noise.
12 months
Visual inspection of the ConnectionBox fuses
(Decentral ConnectionBox).
12 months*
Checking the surge protection device (AC and
DC side) and the external fuses for damage.
12 months
Checking the strength of the clamping connec
-
tions of the power cables and re-tighten if nec
-
essary. Pay attention to discoloration/changes
on the insulation and terminals. Replace dam
-
aged or corroded cable connections or contact
elements.
12 months
Function test of the insulation monitoring.
12 months
Checking AC and DC voltages.
12 months
Checking starting behavior.
12 months
Checking the display field or LEDs for function. 12 months
Checking warning notices (stickers) and if nec
-
essary replace the stickers
12 months
Documenting the operating environment and
the device with a camera.
12 months
Activities to be performed
Interval
Visual inspection of the operating conditions.
Check minimum distance (2 m) to surrounding
shrubs, hedges etc.
12 months*
Replacing the device fans, if fans are indicated
as defect.
8 years*
Replacement DC fuses
(Decentral ConnectionBox).
10 years*
Activities to be performed
Interval