Troubleshooting
61
Error List
REFUsol 100K
982059/02
2020-11
En
gl
is
h
D
eu
ts
ch
A0187
HW error PreActiv
The hardware protection has detected a gen
-
eral error before the activation phase.
▸
If error occurs more than once, contact
REFU Service.
A0188
HW VPos PreActiv
The hardware protection has detected an im
-
permissible overvoltage in the positive DC link
before the activation phase.
▸
Check DC voltage for permissible range.
A0189
HW VNeg PreActiv
The hardware protection has detected an im
-
permissible overvoltage in the negative DC
link before the activation phase.
A018A
HW PowNok PreActiv
The hardware protection has detected a prob
-
lem with the circuit-breakers before the acti
-
vation phase.
▸
If error occurs more than once, contact
REFU Service.
A018B
HW DcUnsy PreActiv
The hardware protection has detected an im
-
permissible asymmetry in the DC link before
the activation phase.
▸
Open and close the DC switch.
▸
If this error occurs more than once, contact
REFU Service.
A018C
HW driver PreActiv
The hardware protection has detected a prob
-
lem in the circuit breaker driver before the ac
-
tivation phase.
Error Code Message
Description
Instructions