Commissioning
46 — English
Variomat 1 — 06.07.2016 – Rev. B
Switch to the "Parameter memory" sub-menu.
•
Press "OK" to open the menu.
•
Use the "
▼▲
" buttons to open the sub-menu.
Parameter memory
˃
The last 10 entries of the minimum working pressure are stored with date and time.
P0 = xx.x bar
Date | Time
The system displays the values for the volume and the diameter of the "VG" primary tank.
•
If you identify differences to the information provided on the primary tank's
nameplate, please contact the Reflex Customer Service.
Tank info
00800 l
This value displays in percent the opening angle of the motor ball valve of the overflow
line.
Pos. motor ball valve
000 %
Information about the software version
Variomat
mkh
V1.00
7.7
Starting Automatic mode
The Automatic mode can be started as soon as the system is filled with water and the gases contained have been vented.
•
At the controller, press "Auto" for automatic operation.
– During commissioning, continuous degassing is automatically activated to remove any residual free or dissolved gases from
the system. This time can be set in the Customer menu as required by the system conditions. The default setting is 12 hours.
Subsequent to the continuous degassing, the device automatically switches to interval degassing.
Note!
The commissioning process is now concluded.
Notice!
The "ST" dirt trap in the "DC" degassing line must be cleaned after the expiry of the continuous degassing time at the
latest, see chapter 10.2 "Cleaning the dirt trap" on page 57 .