Installation
32 — English
Variomat 1 — 06.07.2016 – Rev. B
Terminal
number
Signal
Function
Wiring
1
PE
230 V power supply via mains cable and plug.
Pre-wired
2
N
3
L
4
PE
Pump for maintaining the pressure.
Pre-wired
5N
N
6 M1
M 1
7
Y2
Overflow solenoid valve
•
Not used in a standard device.
---
8
N
9
PE
10
Y 1
Valve to control the water make-up.
Pre-wired
11
N
12
PE
13
COM
Group message (floating).
User, optional
14
NC
15
N.O.
16
Not assigned
External make-up request.
•
To be used only upon consultation with the Reflex Customer
Service.
---
17
Make-up (230 V)
18
Make-up (230 V)
19
PE shield
Level analogue input.
•
Display at the controller.
•
Activation of the make-up.
•
Dry-running protection of the pump.
Factory prepared,
sensor plug must be
inserted on site
20
- Level (signal)
21
+ Level (+ 18 V)
22
PE (shield)
Pressure analogue input.
•
Display at the controller.
•
Control of pressure maintenance.
Pre-wired
23
- Pressure (signal)
24
+ Pressure (+ 18 V)
25
0 – 10 V (correcting
variable)
Motor ball valve in the overflow line to control the pressure
maintenance.
Pre-wired
26
0 – 10 V (feedback)
27
GND
28
+ 24 V (supply)
29
A
RS-485 interface.
User, optional
30
B
31
GND
32
+ 24 V (supply) E1
Supply for E1 and E2.
Pre-wired
33
E1
Contact water meter (in Fillset, for example), see chapter 4.6
"Optional equipment and accessories" on page 13 .
•
Evaluation of the make-up.
– If contact 32/33 is closed = meter pulse.
User, optional
34
E2
Insufficient water switch.
•
Not used in this device.
– If contact 32/34 is closed = OK.
---