Installation
Variomat 1 — 06.07.2016 – Rev. B
English — 21
•
Align the primary tank.
– The distance of the primary tank to the control unit
must match the length of the connection set.
•
Connect the connection set (2) and (3) with the screw
fittings and gaskets to the connections at the lower tank
flange of the primary tank.
– Ensure that you connect the connection set for the
overflow collector to the connection (2) below the
label (1).
– Interchanging the connections may cause the
pump to run dry.
– For tanks up to 740 mm Ø:
•
Connect the connection set (2) and (3) to the
two free 1-inch barrel nipples at the tank
flange.
•
Connect the connection set (4) of the secondary
tank to the T-joint at the outlet of the tank
flange.
– For tanks from 1000 mm Ø:
•
Connect the connection set (2) to the 1-inch
barrel nipple of the tank flange.
•
Connect the connection sets (3) and (4) to the
T-joint at the 1-inch barrel nipple of the tank
flange.
1 Adhesive label
3 "Pump" connection set
2 "Overflow collector" connection
set
4 Secondary tank
connection set
Note!
If necessary, install the supplied connection set (4) at the optional secondary tank. Connect the connection set (4) with a
user-supplied flexible pipeline to the primary tank.