Installation
Variomat 1 — 06.07.2016 – Rev. B
English — 27
6.4
Switching and make-up variants
6.4.1
Function
The current filling level is recorded in the primary tank by the "LIS" level sensor and evaluated in the controller. The value for the
minimum filling level is specified in the controller's Customer menu. If the level drops below the defined minimum, the "WV" make-up
valve opens and fills the primary tank.
Note!
To complete the make-up function from the drinking water system, Reflex offers the Fillset with integrated system
separator and Fillsoft softening equipment,see chapter 4.6 "Optional equipment and accessories" on page 13 .
6.4.1.1
Using a single-tank system
1
Heat generator
WC Make-up line
2
"MAG" pressure expansion tank
PIS
Pressure transducer
3
Primary tank
WV Make-up solenoid valve
4
Control unit
EC
Degassing line
•
For gas-rich water from the system.
•
For degassed water into the system.
5
Reflex Fillset, see chapter 4.6 "Optional equipment and
accessories" on page 13 .
LIS
Level sensor
ST
Dirt trap
Single-
tank system ≤
350 kW, water temperature < 100 °C.
•
Use the Reflex Fillset with integrated system separator when using drinking water for make-up.
–
If you don't use a Reflex Fillset, you must use an "ST" dirt trap with a mesh size ≥
0.25 mm for the make-up.
Notice!
The quality of the make-up water must comply with the applicable standards such as VDI 2035.
– If you cannot meet this quality, use the Reflex Fillsoft to soften the make-up water from the potable water network,
see chapter 4.6 "Optional equipment and accessories" on page 13 .