Active messages are displayed in the message line of the display. In addition to this the error LED lights up (red). The dry
operation protection is signalled directly by a separate LED (→ p. 4). If several messages are active simultaneously, these
can be directly displayed with .
Most of the messages automatically acknowledge themselves once the cause has been remedied. Errors such as „make-up
time 06“ or „make-up cycle 07“ must be acknowledged manually.
An error and parameter memory is available for subsequent analysis (→ p. 16). For remote transmission it is possible to use
the floating changer for the aggregate message, the floating contact for the dry operation protection and the RS-485 inter-
face (→ p. 17). In the customer menu (→ p. 16) it is possible to select whether only the messages characterised as alarms
or all messages will pass through the floating output.
Messages
ER
Code
Type of error
Cause of errors
Troubleshooting remedy
01
Pressure below
– Water loss in the system
– Correct leak
minimum pressure p
0
– Pressure maintenance incorrectly set
– Acknowledge error („quit“ button)
(alarm)
or defective
02.1
Dry operation protection
– Water deficiency switch (16) not wired up
– Wire up water deficiency switch
Time exceeded
– No water enters the vacuum spray-tube
(alarm)
- Ball valve on inlet side closed
– Open ball valve
- Dirt trap of the pressure reducing valves
– Clean dirt trap
(5,8) dirty
02.2
Dry operation protection
– Not enough water flows into the vacuum
Number exceeded
spray-tube
(alarm)
- Dirt trap of the pressure reducing
– Clean dirt trap
valves (5,8) dirty
- Pressure reducing valves (5,8) or
– Correct pressure setting on the pres-
overflow valve (3) incorrectly set
sure reducing valves, perform hydraulic
balancing
– Dipstick tube-deaeration unit (18) defective – Replace dipstick tube-deaeration unit
04.1
Pump
– Pump fuse defective
– Check fuse, replace if required
fault
– Pump blocked
– Free pump
(alarm)
– Short circuit
– Establish cause and rectify
06
Make-up time
– Major leaks in the system
– Correct leaks, acknowledge error
exceeded (standard 20 min)
– Make-up time inadequate for
– Reduce make-up hysteresis
downstream pressure maintenance
of the pressure maintenance
07
Make-up cycles
– Minor leaks in the system
– Correct leaks, acknowledge error
exceeded (standard 3 in 2 h)
message
08
Pressure measurement
– Pressure measuring transducer not
– Check wiring, replace if required
fault (alarm)
connected or defective
10
Max. pressure
– Pressure losses between ’servitec’
– Incorporate pressure measuring trans-
exceeded
and system excessive
ducer in the system or use greater no-
minal widths for the piping to the system
– Expansion vessel in the system with
– Check expansion vessel pre-pressure
incorrect pre-pressure
– Solenoid valve (4) fails to close
– Inspect solenoid valve for dirt,
clean or replace if required
– PS in customer menu set too low
– Co-ordinate PS setting with safety valve
activation pressure of the system
11
Make-up quantity
– Major leaks in the system
– Correct leaks, acknowledge error
within a make-up cycle
– Make-up quantity inadequate for
– Reduce make-up hysteresis of
exceeded
downstream pressure maintenance
the pressure maintenance or increase
maximum make-up quantity
12
Filling time
– Max. filling time exceeded
– Check filling status of the system,
exceeded (standard 10 h)
acknowledge error and refill if required
13
Filling quantity
– Max. filling quantity exceeded
– Check the filling status of the system,
exceeded
acknowledge error and refill if required
15
Make-up solenoid valve
– Make-up solenoid valve (4) leaking
– Inspect solenoid valve for dirt,
(control)
(contact water meter is counting without
clean or change if required
make-up request)
16
Power failure
–
– Check power supply
19
Stop > 4 h
– ’servitec’ has been in stop mode for
– Activate auto mode as applicable
more than 4 h
20
Max. make-up quantity
– The maximum make-up quantity set in
– Acknowledge message
exceeded (added)
the customer menu has been exceeded
(→ p. 16)
Mainten.
Maintenance interval
– Reminder of the minimum annual
– Perform maintenance
rec.
expired
maintenance
– Acknowledge message
30
EEPROM defective
– EEPROM has internal
– Change CPU board
(alarm)
calculation errors
*
*
*
*
* Only if contact water meter is connected and activated in the control (→ p. 10 and 15)