![Reflex Reflexomat RS 150/1 Operating Manual Download Page 52](http://html1.mh-extra.com/html/reflex/reflexomat-rs-150-1/reflexomat-rs-150-1_operating-manual_1432679052.webp)
Controller
52 — English
Reflexomat with Touch controller — 06.07.2016 - Rev. B
ER Code
Alarm
Floating
contact
Causes
Remedy
Alarm reset
07
Make-up cycles
–
•
Set value exceeded.
•
Leakage in the
system.
•
Check set value in the Customer
or Service menu.
•
Seal any leak in the system.
"OK"
08
Pressure
measurement
–
Controller receives
incorrect signal.
•
Connect the plug.
•
Check functioning of the
pressure sensor.
•
Check the cable for damage.
"OK"
09
Level sensor
–
Controller receives
incorrect signal.
•
Check functioning of the load
cell.
•
Check the cable for damage.
•
Connect the plug.
"OK"
10
Maximum pressure
–
•
Set value exceeded.
•
Overflow line
disabled.
•
Dirt trap clogged.
•
Check set value in the Customer
or Service menu.
•
Check functioning of the
overflow line.
•
Clean the dirt trap.
"OK"
11
Make-up quantity
–
Only if "With water meter"
is activated in the
Customer menu.
•
Set value exceeded.
•
Severe water loss in
the system.
•
Check set value in the Customer
or Service menu.
•
Check water loss in the system
and repair, if necessary.
•
Water quantity per contact
incorrectly set in the Service
menu.
"OK"
15
Make-up valve
–
Contact water meter
measures without make-
up request.
•
Check the "WV" make-up valve
for leaks.
"OK"
16
Power failure
–
No power.
Connect to power supply.
–
19
Stop > 4 h
–
Device is in Stop mode for
more than 4 hours.
Set the controller to Automatic
mode.
–
20
Max. Make-up
volume
–
Set value exceeded.
Reset the "Make-up quantity" meter
in the Customer menu.
"OK"
21
Maintenance
recommended
–
Set value exceeded.
Carry out maintenance.
"OK"
24
Softening
–
•
Set value for soft
water capacity
exceeded.
•
Time interval for
replacement of the
softening cartridge
exceeded.
Replace the softening cartridges.
"OK"
30
I/O module fault
–
•
I/O module defective.
•
Connection between
option card and
controller faulty.
•
Option card defective.
Inform Reflex Customer Service.
–