Controller
Reflexomat with Touch controller — 06.07.2016 - Rev. B
English — 49
Service menu
Parameter
Setting
Remarks
Pressurisation
Compressor "ON"
P
0
+ 0.3 bar
Differential pressured added to the "P
0
" minimum
operating pressure.
Compressor "OFF"
P
0
+ 0.4 bar
Differential pressured added to the "P
0
" minimum
operating pressure.
"Compressor run time exceeded" message
240 minutes
The message is displayed after the compressor runs for
240 minutes.
Overflow line "CLOSED"
P
0
+ 0.4 bar
Differential pressured added to the "P
0
" minimum
operating pressure.
Overflow line "OPEN"
P
0
+ 0.5 bar
Differential pressured added to the "P
0
" minimum
operating pressure.
Maximum pressure
P
0
+ 3 bar
Differential pressured added to the "P
0
" minimum
operating pressure.
Filling levels
Insufficient water "ON"
5 %
Insufficient water "OFF"
12 %
Solenoid valve in overflow line "CLOSED"
90 %
Water quantity for each contact
10 litres / contact
Optional, if a contact water meter is installed (such as
Fillset Impulse).