Controller
46 — English
Reflexomat with Touch controller — 06.07.2016 - Rev. B
9.3
Configuring settings in the controller
You can configure the controller settings regardless of the currently selected and active operating mode.
9.3.1.1
Customer menu – overview
Use the Customer menu to correct or determine system-specific values. In the course of commissioning, the factory settings must be
adjusted for the system-specific conditions.
Note!
For a description of the operation, see chapter 9.1 "Operator panel" on page 44 .
A three-digit PM code is assigned to the setting options.
PM code
Description
001
Select the language
002
Set the time
003
Set the date
Execute null balancing
– The primary tank must be empty!
– The system checks whether the signal from the level sensor matches the selected primary tank.
005
Set the P
0
minimum operating pressure, see chapter 7.2 "Determining the P
minimum operating pressure for the
controller" on page 35 .
Make-up >
021
•
Make-up ON at … %
022
•
Make-up OFF at … %
023
•
Maximum make-up time …min
024
•
Maximum make-up cycles … /2 h
027
•
With contact water meter "Yes/'No"
– If "Yes", continue with 028
028
•
Reset make-up quantity "Yes/No"
029
•
Maximum make-up quantity ... l
030
•
With softening "Yes/'No"
– If "Yes", continue with 031
031
•
Block make-up "Yes/No" (if water capacity is exhausted)
033
•
Hardness reduction … °dH = GHactual – GHtarget
032
•
Soft water capacity
•
Fillsoft I: Soft water capacity = 6000 l / hardness reduction
•
Fillsoft II: Soft water capacity = 12000 l / hardness reduction
034
•
replacement interval… months (for softening cartridges according to manufacturer).
007
Maintenance interval… months
008
Floating contact
•
Message selection >
•
Message selection: only messages marked with "√“ are output.
•
All messages: All messages are output.
Fault memory > History of all messages
Parameter memory > History of parameter input
Display settings > Brightness, screen saver
009
•
Brightness … %
010
•
Screen saver brightness … %
011
•
Screen saver delay …min
Information >
•
Tank: Tank information
•
Software version