Installation
A9MA03EN 02/2012
17
The following diagram shows the 5 connection blocks of a Reflex iC60 integrated control circuit breaker
without Ti24 interface.
A
230 V AC power supply terminal block
B
Y1/Y2 control input terminal block
C
Terminal block for the circuit breaker pole position (open/closed) indication contact
D
Terminal block for the circuit breaker trip indication contact
F
Isolated terminals
Description of the Terminals
A
230 V AC power supply terminal block
B
Y1/Y2 control input terminal block
C
Terminal block for the circuit breaker pole position (open/closed) O/C indication contact
D
Terminal block for the circuit breaker trip auto/OFF indication contact
F
Local control
auto
OFF
Reflex iC60N
A
B
D
C
F
Ready-Mode1.2.3
I. ON
O. OFF
Overheat
12
11
14
21
22
24
O/C
auto/
OFF
Y1
Y2
N
P
Terminal
Function
N
Neutral
P
Phase
Terminal
Function
Y1
Mode 1: local closing control on rising edge and opening control on falling edge
Mode 2: local opening control on rising edge, latched at high state (state = 1) to inhibit Y2
Mode 3: centralized control enabled (Y1 = 1) or centralized control inhibited (Y1 = 0)
Y2
Mode 1: local one-shot closing and opening control
Mode 2: local one-shot closing and opening control
Mode 3: local one-shot closing and opening control
Terminals
Contact
Function
11–12
NC (normally closed)
Circuit breaker state: closed
11–14
NO (normally open)
Circuit breaker state: open
Terminals
Contact
Function
21–22
NC (normally closed)
Circuit breaker state: closed
21–24
NO (normally open)
Circuit breaker state: open following tripping