Use
A9MA03EN 02/2012
33
Remote Indication
States of the indication outputs on the Reflex iC60 integrated control circuit breaker with and without Ti24
interface:
Circuit breaker output states
Circuit breaker status
Circuit
breaker
With or without Ti24
interface
With Ti24 interface
Terminal
block
C
D
E
Output
O/C
auto/OFF
O/C
auto/OFF
0
1
The integrated control circuit breaker is ready.
It is possible to control the closing of the contactor
by means of Y1, Y2, Y3 and the pushbutton on the
front of the Reflex iC60 circuit breaker.
1
1
The integrated control circuit breaker is closed.
It is possible to control the opening of the contactor
by means of Y1, Y2, Y3 and the pushbutton on the
front of the Reflex iC60 circuit breaker.
0
0
The circuit breaker is open following tripping
caused by a fault in the power circuit downstream
of the Reflex iC60 circuit breaker.
1
0
The poles are welded. This is shown by the
absence of the green line which indicates the
position of the poles locally on the front of the
Reflex iC60 circuit breaker.
The green line ensures the physical opening of the
contacts and enables work to be carried out on the
downstream circuit in complete safety.
0
1
Overheat protection of the remote control is active.
No control is possible at present.
The circuit breaker is open
1
1
Remote control overheat protection tripped
No control is possible at present.
The circuit breaker is closed
NOTE:
(Filtering) The O/C and auto/OFF contacts may change state for less than 10 ms. These brief changes of state
(bounce) must not be taken into account and must be filtered by a device external to the Reflex iC60 circuit breaker.
14
12
11
24
22
21
14
12
11
24
22
21
14
12
11
21 22 24
14
12
11
21 22 24
14
12
11
24
22
21
14
12
11
24
22
21