Introduction

10

A9MA03EN 02/2012

Overview

Introduction

The Reflex iC60 integrated control circuit breaker combines the function for remote control of an 
installation and the protection functions of a circuit breaker in a single unit. Reflex iC60 integrated control 
circuit breakers are available with 2, 3 and 4 poles.

All Reflex iC60 products have two 230 V AC local controls:

z

Input Y1: latched order local control or on edges (depending on operating mode)

z

Input Y2: local one-shot closing and opening control

The Reflex iC60 product version with Ti24 enables the Reflex iC60 circuit breaker to interface directly with 
a PLC, in order to:

z

Execute remote control (input Y3, low level 24 V DC)

z

Indicate the position (open/closed) of the circuit breaker’s poles (O/C contacts) or tripping of the circuit 
breaker (auto/OFF contacts)

The iMDU auxiliary is used to control the Reflex iC60 circuit breaker at 24/48 V AC/DC.

Catalog numbers of Reflex iC60 circuit breakers

There are 2 families of integrated control circuit breakers (Reflex iC60N and Reflex iC60H) which are 
characterized by their breaking capacity.

The composition rule for A9C••••• catalog numbers is as follows:

Example: Catalog number A9C62316 corresponds to a type N, curve C, 3P, 16 A Reflex iC60 integrated 
control circuit breaker with Ti24 interface.

Catalog numbers of Reflex iC60N integrated control circuit breakers with Ti24 interface: 

Catalog numbers of Reflex iC60N integrated control circuit breakers without Ti24 interface: 

Family

Reflex iC60N

Reflex iC60H

Operating voltage Ue

220 to 240 V

380 to 415 V

220 to 240 V

380 to 415 V

Ultimate breaking capacity Icu

20 kA

10 kA

30 kA

15 kA

Service breaking capacity Ics

z

63 A rating: 50% Icu

z

Other ratings: 75% Icu

All ratings: 50% Icu

Field

A9

C

• = 5 / 6

• = 1 / 2 / 3 / 4

• = 2 / 3 / 4

•• = A

Meaning

Acti 9 range

Control

5 = without Ti24 
interface
6 = with Ti24 interface

1 = type N, curve B
2 = type N, curve C
3 = type N, curve D
4 = type H, curve B

2 = 2 poles
3 = 3 poles
4 = 4 poles

•• = 
10 A/16 A/25 A/
40 A/63 A

Reflex 
iC60N

Number of poles

2 P

3 P

4 P

Tripping curves

Rating

B

C

D

B

C

D

B

C

D

10 A

A9C61210

A9C62210

A9C63210

A9C61310

A9C62310

A9C63310

A9C61410

A9C62410

A9C63410

16 A

A9C61216

A9C62216

A9C63216

A9C61316

A9C62316

A9C63316

A9C61416

A9C62416

A9C63416

25 A

A9C61225

A9C62225

A9C63225

A9C61325

A9C62325

A9C63325

A9C61425

A9C62425

A9C63425

40 A

A9C61240

A9C62240

-

A9C61340

A9C62340

-

A9C61440

A9C62440

-

63 A

A9C61263

A9C62263

-

A9C61363

A9C62363

-

A9C61463

A9C62463

-

Reflex 
iC60N

Number of poles

2 P

3 P

4 P

Tripping curves

Rating

B

C

D

B

C

D

B

C

D

10 A

-

A9C52210

-

-

A9C52310

-

-

A9C52410

-

16 A

-

A9C52216

-

-

A9C52316

-

-

A9C52416

-

25 A

-

A9C52225

-

-

A9C52325

-

-

A9C52425

-

40 A

-

A9C52240

-

-

A9C52340

-

-

A9C52440

-

63 A

-

A9C52263

-

-

A9C52263

-

-

A9C52263

-

Summary of Contents for iC60H

Page 1: ...A9MA03EN 01 www schneider electric com Reflex iC60 Integrated Control Circuit Breaker A9MA03EN 02 2012 Reflex iC60 Integrated Control Circuit Breaker iC60 Circuit Breakers Reference Manual 02 2012...

Page 2: ...y suggestions for improvements or amendments or have found errors in this publication please notify us No part of this document may be reproduced in any form or by any means electronic or mechanical i...

Page 3: ...14 Connection 16 Chapter 3 Use 21 Operating Modes 22 Selection of the Operating Mode 28 Automatic Overheat Protection for the Reflex iC60 Integrated Control Circuit Breaker 31 Operation 32 Chapter 4 A...

Page 4: ...4 A9MA03EN 02 2012...

Page 5: ...ards or to call attention to information that clarifies or simplifies a procedure PLEASE NOTE Electrical equipment should be installed operated serviced and maintained only by qualified personnel No r...

Page 6: ...6 A9MA03EN 02 2012...

Page 7: ...d protection of installations via either electrical control or PLC control Related Documents You can download these technical publications and other technical information from our website at www schne...

Page 8: ...8 A9MA03EN 02 2012...

Page 9: ...N 02 2012 9 1 Reflex iC60 Integrated Control Circuit Breaker Introduction A9MA03EN 02 2012 Introduction What s in this Chapter This chapter contains the following topics Topic Page Overview 10 Descrip...

Page 10: ...flex iC60 integrated control circuit breaker with Ti24 interface Catalog numbers of Reflex iC60N integrated control circuit breakers with Ti24 interface Catalog numbers of Reflex iC60N integrated cont...

Page 11: ...P Tripping curves Rating B C D B C D B C D 10 A A9C64210 A9C65210 A9C66210 A9C64310 A9C65310 A9C66310 A9C64410 A9C65410 A9C66410 16 A A9C64216 A9C65216 A9C66216 A9C64316 A9C65316 A9C66316 A9C64416 A9...

Page 12: ...h Ti24 interface A 230 V AC power supply terminal block B Y1 Y2 control input terminal block C Terminal block for the circuit breaker pole position open closed indication contact D Terminal block for...

Page 13: ...N 02 2012 13 2 Reflex iC60 Integrated Control Circuit Breaker Installation A9MA03EN 02 2012 Installation What s in this Chapter This chapter contains the following topics Topic Page Assembly 14 Connec...

Page 14: ...circuit breaker using a screwdriver 4 Assemble the Vigi iC60 auxiliary with the Reflex iC60 circuit breaker 5 Place the assembly on the DIN rail and push in the 5 locking clips 6 Push the padlocking...

Page 15: ...Vigi iC60 auxiliary with the Reflex iC60 circuit breaker 5 Place the assembly on the DIN rail and push in the 3 locking clips 6 Push the padlocking device back in auto OFF Reflex iC60N 1 Ready Mode1 2...

Page 16: ...assume that all circuits are live until they have been de energized tested and labeled Pay particular attention to the design of the power supply circuit Take account of all power supply sources incl...

Page 17: ...contact F Local control auto OFF Reflex iC60N A B D C F Ready Mode1 2 3 I ON O OFF Overheat 12 11 14 21 22 24 O C auto OFF Y1 Y2 N P Terminal Function N Neutral P Phase Terminal Function Y1 Mode 1 loc...

Page 18: ...g edge Mode 3 centralized closing control on rising edge and opening control on falling edge 24 V 24 V DC power supply Terminals Function 0 5 25 A Power 32 63 A Power Item Terminal block Tightening to...

Page 19: ...rcuit breaker with Ti24 interface used in mode 1 2 or 3 The following diagram illustrates connection of a Reflex iC60 integrated control circuit breaker with Ti24 interface used in mode 3 N P P N Y1 Y...

Page 20: ...iC60 integrated control circuit breaker via a 24 48 V AC DC output The following diagram illustrates connection of the control inputs on a Reflex iC60 integrated control circuit breaker using iMDU aux...

Page 21: ...eaker Use A9MA03EN 02 2012 Use What s in this Chapter This chapter contains the following topics Topic Page Operating Modes 22 Selection of the Operating Mode 28 Automatic Overheat Protection for the...

Page 22: ...24 A9C6 with Ti24 1 Local closing control on rising edge and opening control on falling edge Y1 Local one shot closing and opening control Y2 Centralized closing control on rising edge and opening con...

Page 23: ...ircuit breaker switches to closed position z When input Y1 changes to 0 the Reflex iC60 circuit breaker switches to Ready position contacts open z A pulse on input Y2 makes the Reflex iC60 circuit bre...

Page 24: ...gram shows mode 2 operation of versions with Ti24 interface Operation is as follows z A rising edge on input Y1 makes the Reflex iC60 circuit breaker switch to Ready position contacts open z The state...

Page 25: ...are ineffective z On input Y3 in this case controls on input Y2 are ineffective Mode 3 is used for centralized opening closing of the circuit breaker and local override z local control selector Y1 0...

Page 26: ...0 the Reflex iC60 circuit breaker switches to Ready position contacts open Connection diagram 2 The following connection diagram enables the Reflex iC60 circuit breaker to optionally use depending on...

Page 27: ...ational When input Y3 Ti24 changes to 1 the Reflex iC60 circuit breaker switches to closed position When input Y3 Ti24 changes to 0 the Reflex iC60 circuit breaker switches to Ready position contacts...

Page 28: ...LED indicates the operating mode z Mode 1 the LED flashes once green z Mode 2 the LED flashes twice green z Mode 3 the LED flashes three times green NOTE Selection of the operating mode is described...

Page 29: ...t auto OFF 5 6 Mode 1 Mode 2 Mode 3 Ti24 auto OFF auto OFF 3 4 YES NO Mode OK auto OFF Mode 3 x 1 x 1 x 1 2 1 4 1 u 3 s 4 2 Ti24 Reflex iC60N Ready Mode1 2 3 I ON O OFF Overheat Reflex iC60N Ready Mod...

Page 30: ...with Ti24 interface 4 Press the pushbutton several times in succession to select the required operating mode Each press switches the circuit breaker from one mode to the next 5 Once the operating mode...

Page 31: ...60 integrated control circuit breaker is likely to switch to automatic overheat protection for a period of 5 to 25 seconds Activation of Overheat Protection During normal operation of the Reflex iC60...

Page 32: ...breaker is open or tripped No control locally by means of the pushbutton or Y1 Y2 Y3 is possible The following actions are necessary in order to control the circuit breaker z If the circuit breaker i...

Page 33: ...tripping caused by a fault in the power circuit downstream of the Reflex iC60 circuit breaker 1 0 The poles are welded This is shown by the absence of the green line which indicates the position of t...

Page 34: ...ep Action 1 Pull out the padlocking device from the Reflex iC60 integrated control circuit breaker 2 Attach the padlock diameter 3 to 6 mm to the padlocking device 3 On 3P 4P circuit breaker models at...

Page 35: ...grated Control Circuit Breaker Application examples A9MA03EN 02 2012 Application examples What s in this Chapter This chapter contains the following topics Topic Page Outdoor parking lot lighting 36 O...

Page 36: ...A multifunction time switch combined with a light sensitive switch sends opening or closing commands to each circuit breaker via input Y1 according to the time slots corresponding to the periods when...

Page 37: ...e circuit breaker is open and the controls on input Y2 are inhibited When input Y1 is at low state the circuit breaker is controlled by input Y2 z Pushbuttons are used to control the office lighting l...

Page 38: ...are controlled by Reflex iC60 circuit breakers connected to a PLC via the Ti24 interface and set to mode 3 In this mode input Y1 is used to choose between local mode Y1 0 and centralized mode Y1 1 In...

Page 39: ...N P N P 24 V c 0 V Ti24 Y1 Y2 1 Manual Auto 2 4 Supervisory control system N P 24 V 0 V Outputs Inputs 24 V Y3 0 V O C Q3 Reflex iC60 Mode 3 Floor 1 lighting Floor 2 lighting 24 V c 0 V ISSW1 1 ISSW2...

Page 40: ...Application examples 40 A9MA03EN 02 2012...

Page 41: ...4 11 class III Immunity to power supply frequency variation IEC 61 000 4 28 and IACS E10 Harmonic resistance IEC 61 000 4 13 class 2 Immunity to electrostatic discharge air 8 kV IEC 61 000 4 2 contact...

Page 42: ...y Minimum duration of control pulse for input Y2 200 ms Maximum response time of input Y2 250 ms Inrush currents for 230 V AC 50 Hz control 2P 4 2 A peak 3P 8 2 A peak 4P 16 2 A peak Consumption 1 W I...

Page 43: ......

Page 44: ...e from time to time please ask for confirmation of the information given in this publication A9MA03EN 01 A9MA03EN 01 Schneider Electric Industries SAS 35 rue Joseph Monier CS30323 F 92506 Rueil Malmai...

Reviews: