Elektrisk anslutning/Electrical connection

Reflex påfyllningsstation kan nu kopplas in till strömförsörjningen. Endast ett 230 V uttag behövs för
anslutning. Alla elektriska anslutningar samt inkoppling av larmfunktion får endast utföras av behörig
elektriker som följer bestämmelserna enligt (EVU) och VDE.

Kopplings schemat här nedanför måste följas noggrant.

Stäng av strömmen innan arbetet med de elektriska komponenterna inleds.

reflex ’fillcontrol’  is ready to be plugged (power supply and plug for jack bush). Only a 230 V safety socket is 
required on-site. The electric wiring and, if required, the connection of a dry collective alert contact has to be 
carried out by a qualified electrician acc. to the local (EVU) and VDE regulations.

The terminal connection diagram (see below) has to be strctly observed. 

De-energize the system before commencing work on electrical components. 

Relä

Relay

Strömbrytare 

Jack bush 
(plug, power supply)

Kopplings schema/

Terminal connection diagram

Givare

Transducer

 

Tryckgivare - -pols anslutning (PH)

 

• Strömförsörjd tryckgivare
• Jord tryckgivare
• Signal tryckgivare 
  (från höger till vänster)

Pressure sensor  
 

         - three-pole PH Connector 

• Supply pressure sensor
• Ground pressure sensor
• Signal pressure sensor 
  (from left to right)

Motor, Micro strömställare, Batteri  
                       - 6 pols anslutning (PH)

 

• +Pol Batteri
• Jordat Batteri
• Jordad Motor 
• Strömförsörjnings motor 
• Micro strömställare 
• Micro strömställare 
  (från höger till vänster)

Motor, micro switch, battery 
                        - six-pole PH connector

 

• +pol battery
• Ground battery
• Ground motor 
• Supply motor 
• Micro switch 
• Micro switch 
  (from left to right)

Potentialfri larmutgång
      -3-pols teminal
• Strömväxlare
   växlar 1+2, växlar vid funktionsfel 2+3)
• Router 
• Växling till omvänd funktion        
   mellan 1+2

 

   (Från  toppen till botten)

Floating collective alert
Three-pole terminal
• Switching bridge (during regular operation 
   bridge between 1+2, in case of malfunction 
   between 2+3)
• Root
• Change-over to reverse the function of 
   switches 1+2 
   (from top to bottom)

S

GB

S

GB

S

GB

S

GB

reflex ’påfyllningsstation’ 

Installation/Installation

Summary of Contents for fillcontrol

Page 1: ...reflex fillcontrol reflex p fyllningsstation Water make up device Installation Drift och sk tselanvisningar Installation operation and maintenance instructions Stand Status 04 06...

Page 2: ...lectrical connection 7 Terminal connection diagram 7 Initial start up Prerequisites for initial start up 8 Steps of initial start up 8 System dependent setting 8 9 Pressure reducer setting 9 10 Parame...

Page 3: ...us Access menus Quit error messages Upp ner val knappar Up Down operation selection buttons 1 Avst ngning Shut off 2 Tryck givare Pressure sensor 3 Kontroll panel Control Control panel 4 Motor kulvent...

Page 4: ...cal data are provided on the type plate or the markings on the valve Make sure to fully comply with the service parameters of tempera ture and pressure protection do not remain under these values and...

Page 5: ...off system separator type BA acc to DIN EN 1717 tundish dirt trap mano meter connections motor operated ball valve control unit pressure sensor manometer and pressure reducer acc to DIN EN 1567 Adjus...

Page 6: ...the connecting pipe of the reflex fillcontrol make sure that stagnation is excluded The down stream pipe has to be passed in a way length nominal width that the the loss of pressure in this pipe is 0...

Page 7: ...power supply Kopplings schema Terminal connection diagram Givare Transducer Tryckgivare 3 pols anslutning PH Str mf rs rjd tryckgivare Jord tryckgivare Signal tryckgivare fr nh gertillv nster Pressure...

Page 8: ...ometern har blivit installerad p reduceringsventilen fabriks monterad fr n approx 06 06 Installation reflex fillcontrol is completed The connection on the water side of the system and to the refill wa...

Page 9: ...e knappen igen i 4 sekunder s kommer lysdiod I Tryck blinka var 0 5 sekund Det inst llda trycket visas nu i displayen f r att st lla in r tt v rde p0 s f r man justera det genom att trycka p ner eller...

Page 10: ...fyllningstiden verstiger tv timmar tror systemet att det finns ett l ckage och ett felmeddelande kommer fram i displayen S 12 Under systemets fyllningstid skall trycket kvarst S 8 Drift vervakningen...

Page 11: ...low the setting value if the second value is exeeded reflex fillcontrol is turned off p 8 During the LED Auto is green and at the same time the LED IV is red The operation time and the number of cycle...

Page 12: ...ppen i 3 sek E3 Auto blinkar r tt Osannolikt tryck signal och eller motorn terg r inte till noll l ge och eller internt systemfel ROM och eller internt systemfel EE Flera Olika Informera Reflex servic...

Page 13: ...nande vatten Kolla s att O ringen och t tningarna r intakta reng r eller byt ut om det r n dv ndigt Underh ll reduceringsventil Reduceringsventilen m ste testas med j mna mellanrum minst en g ng per r...

Page 14: ...rating conditions but after one year at the latest The connections available for ball valves allow a functionality test of the device to be carried out with an adequate pressure gauge Dirt trap Isolat...

Page 15: ...r Inspection report no ECL SAF TR 05 071 V01 00 Pr finstitut Labor Inspection body inspection institiute Herberg Service Plus GmbH N rnberg EMV Richtlinie EMV directive EN 55014 1 und 55014 2 Category...

Page 16: ...ical modifications Reflex Winkelmann GmbH Co KG Gersteinstrasse 19 59227 Ahlen Germany Telefon 49 23 82 70 69 0 Telefax 49 23 82 70 69 588 www reflex de Somatherm AB Bang rdsgatan 1 Box 900 671 29 ARV...

Reviews: