Controller
46 — English
Fillcontrol Auto Make-up and degassing — 06.07.2016 - Rev. B
ER Code
Alarm
Floating
contact
Cause
Remedy
Alarm reset
07
Makeup cycles
-
Set value exceeded
•
Check set value in the
Customer or Service
menu
•
Seal the leak in the
system
Quit
08
Pressure
measurement
-
Controller receives incorrect
signal
•
Connect the plug
•
Check the cable for
damage
•
Check the pressure
transducer
Quit
10
Maximum pressure
-
Set value exceeded
•
Check set value in the
Customer or Service
menu
•
Set the tripping
pressure of the safety
valve
-
11
Back-up volume
-
"With water meter" must be
activated in the Customer menu
•
Set value exceeded
•
Severe water loss in the
system
•
Check set value in the
Customer or Service
menu
•
Check the water loss in
the plant system
Quit
15
Makeup valve
-
Contact water meter measures
without makeup request
Check the motor ball valve
for leaks
Quit
16
Power failure
-
No power
Connect to power
-
19
Stop
˃
4 hours
-
Device is in Stop mode for more
than 4 hours
Set the controller to
Automatic mode
-
20
Maximum makeup
quantity
-
Set value exceeded
Reset the "Makeup quantity"
meter in the Customer menu
Quit
21
Maintenance
recommendation
-
Set value exceeded
Carry out maintenance
Quit
30
I/O module fault
-
•
I/O module defective
•
Connection between option
card and controller faulty
•
Option card defective
•
Replace the I/O module
•
Check the connection
between option card
and controller
•
Replace the option card
-