ER Code
Alarm
Floating
contact
Cause
Remedy
Alarm reset
31
EEPROM defective
Yes
•
EEPROM defective
•
Internal calculation error
Contact the Reflex Customer
Service
Quit
32
Undervoltage
Yes
Supply voltage not achieved
Check power supply
-
33
Adjustment
parameter faulty
-
EPROM parameter memory
defective
Contact the Reflex Customer
Service
Quit
34
Main board
communication
faulty
-
•
Connecting cable defective
•
Main circuit board defective
Contact the Reflex Customer
Service
Quit
35
Digital input voltage
faulty
-
Short-circuit of input voltage
Check the wiring at the
digital inputs (water meter,
for example)
-
36
Analogue input
voltage faulty
-
Short-circuit of input voltage
Check the wiring at the
analogue inputs
(pressure/level)
-
37
No input voltage for
the 3-ways motor
ball valve
-
Short-circuit of input voltage
Check the wiring of the
motor ball valve
-