Controller
Fillcontrol Auto Make-up and degassing — 06.07.2016 - Rev. B
English — 43
9.2.1
Customer menu
Use the Customer menu to correct or determine system-specific values. In the course of commissioning, the factory settings must be
adjusted for the system-specific conditions.
A three-digit PM code is assigned to the setting options
PM code Parameter
Setting
Remarks
Language
EN
Display language
Time
hh:mm:ss
Time
Date
dd:MM:yy
Date
005
Minimum working pressure P
0
1.8 bar
see chapter 7.2 "Determining the P
pressure for the controller" on page 29
006
Safety valve, pressure
3.0 bar
Tripping pressure for the safety valve at the heat
generator in the system
Degassing, active only in Fillcontrol Auto 2PS
011
Degassing programme
Continuous degassing
Continuous degassing time
24 h
Makeup
020
Maximum makeup time
20 minutes
021
Maximum makeup cycles
3 cycles within 2 hours
3x makeup within 2 hours for maximum 20 minutes each
022
Water meter
NO
Optional contact water meter
023
Makeup quantity
0 Litres
Only if controller with "With water meter YES"
024
Maximum makeup quantity
Next maintenance
18 months
Time left to the next due maintenance
Floating alarm contact
NO
Only the messages marked in the "Messages" list
Horn
NO
Acoustic signal is output with the fault contact
Fault memory
History of all messages
Parameter memory
History of parameter input
Software version
V0.60