6.0 Cleaning:
Cleaning of the urinal is an important part of the regular maintenance. This should not just only involve the ceramic
part of the urinal. Cleaning the trap and pipe connection at regular intervals is equally important.
Water can react with urine and form struvite. Struvite is a hard crystalline deposit that will form on the ceramic and
inside the trap and pipe connection. Over time Struvite can build up creating a blockage. Struvite deposits have to
be frequently removed with a suitable acidic type toilet cleaner at regular intervals.
Cleaning agents are more effective if they soak for a certain time (refer to the cleaning agent instructions). To assist
with the soaking period, the controller is equipped with a cleaning cycle that suspends
fl
ushing for 30 minutes.
How to activate cleaning cycle in Program 1 (Normal Mode):
1)
Hold the blade of a screwdriver with your bare hands (no gloves can be worn) into the water below the grate for 10
seconds. Whilst still holding the rod in the water pour some of the cleaning agent into the water of the urinal.
2)
Now remove the rod from the water. This will trigger two short
fl
ushes which will carry the cleaning agent to the back of
the trap and pipe connection. Now the
fl
ushing is suspended for 30 minutes.
3)
Add more of the cleaning agent to the water of the urinal. After 30 minutes a
fl
ush will automatically trigger and the urinal
is ready for use.
How to clean in Program 2 (ECO Mode):
In Program 2 which
fl
ushes after every third user or approximately 15 minutes after use whichever is
fi
rst, cleaning may be
done within 15 minutes in 2 ways.
A)
The cleaner can visually check if the urinal has been flushed.
If it has been flushed proceed as follows.
1)
In a bucket mix the cleaning agent with some water (follow cleaning agent instructions) and pour into the urinal.
This will carry the cleaning agent into the back of the trap and pipe connection.
2)
No longer disturb the urinal in any way for the next 15 minutes until it automatically
fl
ushes.
B)
If it hasn’t been flushed proceed as follows
.
1)
Hold the blade of a screwdriver into the water for 2 seconds and remove.
Wait for 10 seconds to see if the urinal flushes. If not repeat the same procedure until it flushes.
2)
In a bucket mix the cleaning agent with some water (follow cleaning agent instructions) and pour into the urinal.
This will carry the cleaning agent into the back of the trap and pipe connection.
3)
No longer disturb the urinal in any way for the next 15 minutes until it automatically
fl
ushes.
7.0
Overflow Protection:
To avoid overflow in the case of a pipe blockage the urine sensing device will cease to activate further flushing once the urinal
bowl has filled.
page 8 of 16