ACTIVE SENSOR-FLUSH URINAL

Plumbers, please ensure a copy of the installation 
instructions is left with the end user for future reference

HIDEAWAY

ACTIVE SENSOR-FLUSH URINAL

Dynamic w ater 

Pressure 

LED 

Flashes

Approximate flush 

volume 

475 kPa 

1x

800 ml

425 kPa 

2x

800 ml

375 kPa 

3x

800 ml

325 kPa 

4x

800 ml

275 kPa 

5x

800 ml

LED FLASH RESPONSE 

FIRST TIME POWER ON

MEANING

1)

Initial 

2 short 

ashes followed by a sequence of double

ashes in 3 second intervals. After about 25 seconds of

the double flashing sequence 

the flashing will change

into a rapid on and off sequence and then stop.  This

signals that the self-check cycle has ended.

Self-check has detected a fault with the sensor.  Please switch off the 

power.  Un-plug and re-plug every cable connection.  Check that no cable 

has been damaged during construction.  Re-connect the power and check 

if the LED response is as above in A.

If the fault is still indicated contact Service

ph. 07- 3875 2465

Do not proceed with sealing the urinal with sealant to the wall.

2)

After a pause of 20 seconds 4 short flushes will be

triggered.

LED FLASH RESPONSE 

FIRST TIME POWER ON

MEANING

1)

Initial

2 short 

ashes followed by a sequence of quick triple

flashes in 2 second intervals.  After about 25 seconds of

the triple flashing sequence 

the flashing will change to a

rapid on and off sequence and then stop.  This signals that

the self-check cycle has ended.

Self-check has detected a fault with the solenoid.  Please switch off the 

power.

1) Unplug the solenoid valve connection.

2) Check that the pins in the male plug are not bent apart and line up

with the holes in the female plug.  If required use your fingers to

squeeze the plug and pins together.

3) Check plug alignment and re-connect.  Re-connect the power and

check if the LED response is as above in A.

If a fault is still indicated contact Service

ph. 07-3875 2465.

Do not proceed with sealing the urinal with sealant to the wall.

2)

No flushes will be triggered.

3. If no faults have been detected the urinal can now be sealed to the wall with anti-fungal flexible sealant.

4. Flush Time: To achieve the required flush volume, measure the dynamic water pressure that is available at the

installation site.  Compare your measurement with table values in Fig.10 and select the required 

ush time

setting with ‘Button1' on the controlle

r. The 

ush time of a new controller is supplied with the setting adjusted to

375 kPa. To change 

ush times follow the instructions below.

How to change the flush time 

A)

Press Button 1 once (for 1 to 3 seconds) and the LED will indicate current controller setting by 

ashing 1x or 2x

up to 5x - at which setting the controller currently is.

Note: 

The LED will continue 

ashing in a steady repeating rhythm to indicate that the controller is still in editing mode 

and settings can be changed. Do not be distracted by this 

ashing. 

B)

Press ‘Button 1' again and the fl

ush time will advance to the next 

ush time setting. The LED will now respond by

ashing 1x or 2x up to 5x to indicate the new selected setting.

C)

Once the desired setting is achieved wait for approximately 20 seconds for the controller to automatically exit the

edit mode.

As con

rmation that the controller is now ready for use 2 

ushes will be automatically triggered.

B

C

Factory 

setting

Button 1

page 6 of 16

Summary of Contents for HIDEAWAY

Page 1: ...ions or queries during installation please contact Tech Support for phone assistance free call 07 3875 2465 We are happy to assist you Dear Customer This is the warranty by Reece Pty Ltd relating to t...

Page 2: ...d valve is fitted with 200mm cable and 2 pin connector Fig 1 Cables are supplied as follows Sensor extension cable 2500mm long with female male 4 pin connectors 1800mm power cable wired with single ma...

Page 3: ...mum size not supplied free of kinks for sensor extension cable Fig 4 7 Fit single 240 volt 10 amp GPO for transformer power supply unit adjacent to proposed location of controller 3 0 Control Unit Con...

Page 4: ...V flush with finished wall Fig 7 5 Fit kee seal to waste trap and lubricate before gently pushing into 50mm PVC DWV pipe so trap finishes flush with face of wall Fix waste trap to wall with single scr...

Page 5: ...r C Do not press buttons on the controller yet LED FLASH RESPONSE FIRST TIME POWER ON MEANING 1 Initial 2 short ashes followed by steady flashes at 1 second intervals After about 25 seconds of steady...

Page 6: ...ns in the male plug are not bent apart and line up with the holes in the female plug If required use your fingers to squeeze the plug and pins together 3 Check plug alignment and re connect Re connect...

Page 7: ...Schools This program will ush the urinal only after every 3 rd user or 15 minutes after use whichever comes rst It also triggers a janitor s ush after 48 hours of non use Button 2 To change the progr...

Page 8: ...onnection Now the ushing is suspended for 30 minutes 3 Add more of the cleaning agent to the water of the urinal After 30 minutes a ush will automatically trigger and the urinal is ready for use How t...

Page 9: ...instructions is left with the end user for future reference HIDEAWAY ACTIVE SENSOR FLUSH URINAL 8 0 Installation Types Use the following figures to provide installation guidance Fig 11 In ceiling ins...

Page 10: ...NSOR FLUSH URINAL Plumbers please ensure a copy of the installation instructions is left with the end user for future reference HIDEAWAY ACTIVE SENSOR FLUSH URINAL 8 0 Installation Types Continued Fig...

Page 11: ...HIDEAWAY ACTIVE SENSOR FLUSH URINAL HIDEAWAY ACTIVE SENSOR FLUSH URINAL 8 0 Installation Types Continued Fig 13 page 11 of 16...

Page 12: ...ically switch to Saver Mode 1 flush every minute when 4 users visit the urinal in less than 1 minute intervals no matter how many times used 1 minute of non use will reset the control unit back to Nor...

Page 13: ...sioning Look for 2 confirmation flushes to confirm urinal is functioning normally Problem fixed If problem cannot be resolved call 07 3875 2465 for assistance 5 seconds pause Pause then Temperature Se...

Page 14: ...ge is blocked Dynamic pressure has changed Un screw the solenoid cartridge and rinse out dirt out of the strainer see Section 1 Maintenance of the Solenoid Cartridge Check dynamic pressure and reset f...

Page 15: ...enoid cartridge lubricate the two O Rings with a suitable tap O Ring lubricant Hydroseal tap lubricant or equivalent Note Do not over tighten The max torque is 1Nm hand tight 13 0 Spare parts 9503303...

Page 16: ...RINAL INLET OUTLET SEAL 200 034 9503309 HIDEAWAY URINAL SOLENOID CARTRIDGE 200 036 9503310 HIDEAWAY URINAL SOLENOID BODY 200 037 9503311 HIDEAWAY URINAL AIR BREAK 200 038 9503312 HIDEAWAY URINAL FLUSH...