X-IP-SERIES USER MANUAL
7
PIN NO.
PCB IDENT
WIRE COLOUR
1
TxP
White / Orange
2
TxN
Orange
3
RxP
White / Green
4
-
Blue
5
-
White / Blue
6
RxN
Green
7
-
White / Brown
8
-
Brown
Terminal No.
P19
P18
P17
P16
1
Alarm 1 Signal
Alarm 5 Signal
Alarm 9 Signal
Alarm 13 Signal
2
Alarm 1 Ground
Alarm 5 Ground
Alarm 9 Ground
Alarm 13 Ground
3
Alarm 2 Signal
Alarm 6 Signal
Alarm 10 Signal
Alarm 14 Signal
4
Alarm 2 Ground
Alarm 6 Ground
Alarm 10 Ground
Alarm 14 Ground
5
Alarm 3 Signal
Alarm 7 Signal
Alarm 11 Signal
Alarm 15 Signal
6
Alarm 3 Ground
Alarm 7 Ground
Alarm 11 Ground
Alarm 15 Ground
7
Alarm 4 Signal
Alarm 8 Signal
Alarm 12 Signal
Alarm 16 Signal
8
Alarm 4 Ground
Alarm 8 Ground
Alarm 12 Ground
Alarm 16 Ground
3.2.2.4
ALARM INPUTS
Four 8 Way screw terminal block connectors.
All alarm inputs are 'volt free' and
MUST NOT
be connected to any powered contacts. Permanent damage may result from
failure to correctly connect the alarm inputs.
NOTE: The 'Alarm xx Ground' connections are all common on the PCB and connected to the PSU ground.
3.2.2.5 AUXILIARY
OUTPUTS
Three sets of NO/NCAuxiliary Output contacts are provided (ALARM / AUX / WASH). Each set of contacts are isolated, and
useable for any circuit within the following limitations:-
Rated load
:
0.5A @ 125 Vac / 1.0A @ 24Vdc Resistive
Max. carrying current
:
2A
Max. switching Current :
1A
Max. switching Power
:
62.5VA, 30W
Contact Resistance
:
100mOhm max.
ALARM contacts are operated whenever any alarm signal is active.
WASH contacts are operated under operator control for camera lens washing.
AUX contacts are configurable in the camera setup to operate under various scenarios.
3.2.2.3 NETWORK
CONNECTION
RJ45 SOCKET
This socket is a typical Ethernet 100BASE-T type, for connection of a 'Cat 5' cable, wired to the T568A or T568B scheme.
The typical wire colours noted below are of the T568B scheme.
The camera supports automatic polarity and automatic crossover (Auto MDI/MDIX) to simplify installation cabling.
The Alarm PSU includes an active Ethernet repeater, consequently the maximum specified cable run from the PSU to
network hub or switch is 100m.
The use of high quality Cat5e cable to connect to the network is highly recommended for reliable operation.