Effective 08 2021

Drawing No. LP1140

WIRING

All power, input and output (I/O) wiring must be in accordance 

with Class I, Division 2 wiring methods and in accordance with 

the authority having jurisdiction. Electrical connections are made 

via pluggable spring-clamp terminal blocks. It is recommended 

that the power supplied to the meter be protected by a fuse or 

circuit breaker.

When wiring the meter, refer to the label on the unit for pin-out 

numbering against those shown in the wiring drawings for proper 

wire position. Strip and connect the wire according to the 

terminal block specifications on Page 3. Use a small screwdriver 

to press down on tab next to the terminal position to open the 

spring clamp. Insert the wire into the terminal position and then 

remove the screwdriver to engage the spring-clamp.

 

POWER WIRING   

Must use a Class 2 circuit according to 

National Electrical Code (NEC), NFPA-70 or 

Canadian Electrical Code (CEC), Part I, C22.1 or 

a Limited Power Supply (LPS) according to IEC/

EN 60950-1 or Limited-energy circuit according 

to IEC/EN 61010-1.   

+

-

1

2

VDC 

 +

VDC 

 -

10 to 30 VDC

DC Power

INPUT SIGNAL WIRING   

    

CAUTION:

 Sensor input common is NOT isolated from user input common. In order to preserve the safety of the controller 

application, the sensor input common must be suitably isolated from hazardous live earth referenced voltages; or input common must 

be at protective earth ground potential. If not, hazardous live voltage may be present at the User Inputs and User Input Common 

terminals. Appropriate considerations must then be given to the potential of the user input common with respect 

to earth common, and the common of the isolated plug-in modules with respect to input common.

14

15

MAGNETIC PICKUP

INP 

CO

M

INP 

A

14

15

to 2.5 mA MAX.

Resistor to limit current

AC

INP 

CO

M

INP 

A

14

10

15

2.2K

INP 

CO

M

+24V 

EX

C

INP 

A

NPN O.C.

10

14

15

+24V 

EX

C

INP 

CO

M

INP 

A

PNP O.C.

10

14

15

+24V 

EX

C

INP 

CO

M

INP 

A

14

15

+5V

COMM

DIODE

INP 

CO

M

INP 

A

14

15

INP 

CO

M

INP 

A

10

15

+24V 

EX

C

INP 

A

10

14

15

+24V 

EX

C

INP 

CO

M

INP 

A

AC Inputs From Tach Generators, Etc.

Input A

Two Wire Proximity, Current Source

Input A

Magnetic Pickup

Input A

Current Sourcing Output

Input A

Interfacing With TTL

Input A

Current Sinking Output

Input A

Switch or Isolated Transistor; Current Sink

Input A

16

10

14

15

NPN O.C.

+24V 

EX

C

INP 

B

INP 

CO

M

INP 

A

Current Sink Output; Quad/Direction

Single Counter A

Switch or Isolated Transistor; Current Source

Input A

Emitter Follower; Current Source

Input A

16

10

14

15

NPN O.C.

NPN O.C.

13

Rate

Count

USER 

1

+24V 

EX

C

INP 

B

INP 

CO

M

INP 

A

10

12

13

14

NPN O.C.

Count A

15

16

NPN O.C.

Count B

USER 

2

USER 

1

+24V 

EX

C

INP 

B

INP 

CO

M

INP 

A

Current Sink Output; Quad/Direction

Counter A 

& Rate B

Counter A & 

Counter B

Current Sink Output; Quad/Direction

Ensure software configuration is set to correspond with your required application wiring.

User Input Configured in Sink Position in Software

User Input Configured in Sink Position in Software

Shaded areas not recommended for counting applications.

Software Configuration - Select Mag Mode

If using Single Counter B, then wire signal to 16 and Quad/Direction to 12. 

Settings configured in Software.

Summary of Contents for PM-50

Page 1: ...uirements for AC power and they can be accommodated with our AC to DC Power Module PACKAGE CHECKLIST This product package should contain the items listed below If any items are missing or damaged contact Red Lion immediately PM 50 Digital Input Panel Meter Accessory Pack Installation Guide SAFETY SUMMARY All safety related regulations local codes and instructions that appear in this document or on...

Page 2: ...accept the second signal of each signal pair The user inputs do not have the Logic Mag HI LO Freq and Sink Source software selections The user inputs are inherently a logic input with no low frequency filtering implemented in software The user input may only be selected for sink source by the User Input Active parameter 7 USER INPUTS Two programmable user inputs Max Continuous Input 30 VDC Isolati...

Page 3: ...near devices that generate excessive heat should be avoided The PM 50 4 3 and 3 5 inch models meet NEMA 4X IP65 requirements when properly installed This unit is designed for through panel mounting The mounting surface should have a minimum thickness of 0 04 1 02 mm and maximum thickness of 0 25 6 35 mm Cut the mounting hole per the dimensions shown in the diagram Care should be taken to remove an...

Page 4: ... properly grounded This is especially useful in applications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radio transmitter Also Signal or Control cables within an enclosure should be routed as far away as possible from contactors control relays transformers and other noisy components 4 Long cable runs are more suscep...

Page 5: ...and User Input Common terminals Appropriate considerations must then be given to the potential of the user input common with respect to earth common and the common of the isolated plug in modules with respect to input common 14 15 MAGNETIC PICKUP INP COM INP A 14 15 to 2 5 mA MAX Resistor to limit current AC INP COM INP A 14 10 15 2 2KΩ INP COM 24V EXC INP A NPN O C 10 14 15 24V EXC INP COM INP A ...

Page 6: ...130K B A COM 130K RX TX 8 7 9 RS485 2 WIRE CONNECTIONS See appropriate document for instructions on module installation and wiring support CONFIGURING A PM 50 Various options are available to configure your PM 50 so you can choose the one that fits your requirement Programming Wizard On initial power up a Programming Wizard will offer assistance Proceeding with the Wizard will help with the basic ...

Page 7: ...d Orientation 3 5 Inch Meter ORDERING INFORMATION DESCRIPTION PART NUMBER Graphical Panel Meter 4 3 Display Digital Input PM500D0400800F00 Graphical Panel Meter 3 5 Display Digital Input PM500D0301600F00 Accessories TYPE DESCRIPTION PART NUMBER Modules RS232 Serial Communications Module PMM000CM23200000 Ethernet Communications Module PMM000CMENT00000 Analog Output Module PMM000I0AN000000 Dual Setp...

Page 8: ...ANTABILITY B WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE OR C WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY RIGHTS OF A THIRD PARTY WHETHER EXPRESS OR IMPLIED BY LAW COURSE OF DEALING COURSE OF PERFORMANCE USAGE OFTRADE OR OTHERWISE Customer shall be responsible for determining that a Product is suitable for Customer s use and that such use complies with any applicable local state or fed...

Reviews: