background image

2

Drawing No. LP1140  

Effective 08 2021

GENERAL METER SPECIFICATIONS

Note:

 The

 

PM-50 4.3 inch host accepts a maximum of 5 

modules while the 3.5 inch host accepts a maximum of 3. 

Only one module from each function type (i.e. communication, 

relay, analog output) can be installed.

1. 

POWER

: The meter is intended to be powered by NEC/CEC 

class 2, IEC/EN/UL 60950-1 LPS or UL/CSA 601010-1 

Limited Energy power source.

MODEL

4.3-INCH

3.5-INCH

Input Voltage (Volts)

10-30 VDC

10-30 VDC

Max Power PM-50 only

4.6 W

4.6 W

Max Power PM-50, with modules

12 W

12 W

Host Isolation: 500 Vrms for 1 min. to all inputs and outputs.

2. 

DISPLAY

:

 

4.3" or 3.5" Color TFT display with resistive analog 

touch screen

SIZE

4.3-INCH

3.5-INCH

TYPE

TFT

TFT

COLORS

262,144

262,144

 PIXELS

480 X 272

320 X 240

 BRIGHTNESS

420 cd/m

2

540 cd/m

2

 LED BACKLIGHT LIFE

*

30,000 HR TYP.

30,000 HR TYP.

* Lifetime at room temperature (25°C)

3. 

SENSOR POWER

:

+24 VDC, ±5% @ 50 mA max.

4. 

COUNTER DISPLAYS

: 9 digits available

Display Range: -99,999,999 to 999,999,999

Over Range Display: Overrange

Under Range Display: Underrange

Display Designators: Cnt-A, Cnt-B, Cnt-C

Maximum Count Rates: 50% duty cycle

If Setpoints Disabled: 35 KHz for all modes except Quadrature 

x4 (32 KHz)

If Setpoint(S) Enabled: 20 KHz for any mode except 

Quadrature x1 (19 KHz), Quadrature x2 (17 KHz) and 

Quadrature x4 (10 KHz)

5. 

RATE DISPLAYS

: 6-digit

Maximum Frequency: 50 KHz

Minimum Frequency: 0.001 Hz

Display Update Time: 0.1 to 999.9 seconds

Accuracy: ±0.01%

6. 

SIGNAL INPUTS (INPUT A and INPUT B)

:

Software configurable input types including switch contacts, 

TTL outputs, magnetic pickups and all standard RLC 

sensors. Inputs are configurable for current sinking or 

current sourcing outputs with input filtering for low 

frequency signals or switch contact debounce. Not isolated 

from the sensor input common.

Logic: Input trigger levels V

IL

 = 1.2 V max.; V

IH

 = 3.75 V min.

Sink: Adds internal 7.8 KΩ pull-up resistor to +5 VDC, 0.7 

mA max

Source: Adds internal 3.9 KΩ pull-down resistor, 7.3 mA 

max. at 28 VDC, V

MAX

 = 30 VDC

Magnetic Pickup:

V

IN_PK

 = 200 mV; V

IN_HSYS

 = 100 mV; Must also have SRC 

selection turned on through software

V

MAX

 = ± 40 V

PEAK

 or 28 Vrms

Dual Count Modes:

When any dual count mode is used, then User Inputs 1 and/

or 2 will accept the second signal of each signal pair. The user 

inputs do not have the Logic/Mag, HI/LO Freq, and Sink/

Source software selections. The user inputs are inherently a 

logic input with no low frequency filtering implemented in 

software. The user input may only be selected for sink/

source by the User Input Active parameter. 

7. 

USER INPUTS

: Two programmable user inputs

Max. Continuous Input: 30 VDC

Isolation to Sensor Input Common: Not isolated.

Logic State: User programmable for sink/source (Lo/Hi)

INPUT STATE

LO/SINK

HI/SOURCE

20 KΩ pull-up to +3.3 V

20 KΩ pull-down

Active

V

IN

 < 0.9 VDC

V

IN

 > 2.4 VDC

Inactive

V

IN

 > 2.4 VDC

V

IN

 < 0.9 VDC

8. 

MEMORY

: Nonvolatile memory retains all programmable 

parameters and display values.

Memory Card: microSD slot accepts up to 32 GB capacity 

cards in FAT16/FAT32 format.

9. 

RS485 SERIAL PORT: 

Uses Modbus protocol

Baud Rate: Up to 115,200

Data Format: 7/8 bit; odd, even, or no parity; 1 or 2 stop bits

Isolation: 500 Vrms to sensor, user power and digital inputs. 

Not isolated to solid state outputs

10. 

Wi-Fi CAPABILITIES:

Wi-Fi: Power output up to 20.5 dBm

Frequency:

TECHNOLOGY

CHANNELS

FREQUENCIES

Wi-Fi

1-13

2412-2484 MHz

Note: Channel/frequency limitation is enforced based on 

configured country/region code.

Wi-Fi Compliance: TCP/IP; 802.11 b/g/n

11. 

ON-BOARD DUAL SSR OUTPUTS: 

Both outputs must be 

used either in SINKING or in SOURCING mode together.

Sinking Mode:

Type: Switched DC, N-channel open drain MOSFET

Max Sink Current: 100 mA

V

DS

 ON: 0.3 V @ 100 mA

V

DS

 MAX: 30 VDC

Offstate Leakage Current: 0.5 mA max

Sourcing Mode:

Type: Switched DC, P-channel open source MOSFET

Max Source Current: 100 mA

V

DS

 ON: 0.3 V @ 100 mA

V

DS

 MAX: 30 VDC

Offstate Leakage Current: 0.5 mA max

12. 

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range: -10 to 55 °C

Storage Temperature Range: -20 to 60 °C

Operating and Storage Humidity: 0 to 85% max. RH non-

condensing

Vibration to IEC 68-2-6: Operational 5-500 Hz, 2 g

Shock to IEC 68-2-27: Operational 20 g (10 g relay)

Altitude: Up to 2000 meters

Installation Category II, Pollution Degree 2 as defined in IEC/

EN 60664-1.

13. 

CERTIFICATIONS AND COMPLIANCES

:

CE Approved

EN 61326-1 Immunity to Industrial Locations

Emission CISPR 11 Class A

IEC/EN 61010-1

RoHS Compliant

FCC ID#: 2AC7Z-ESP32WROOM32U

UL Hazardous: File # E317425

Type 4X Indoor/IP65 Enclosure rating (Face only) for all models

IP20 Enclosure rating (Rear of unit)

14. 

CONNECTIONS

: High compression spring-clamp terminal 

block

Summary of Contents for PM-50

Page 1: ...uirements for AC power and they can be accommodated with our AC to DC Power Module PACKAGE CHECKLIST This product package should contain the items listed below If any items are missing or damaged contact Red Lion immediately PM 50 Digital Input Panel Meter Accessory Pack Installation Guide SAFETY SUMMARY All safety related regulations local codes and instructions that appear in this document or on...

Page 2: ...accept the second signal of each signal pair The user inputs do not have the Logic Mag HI LO Freq and Sink Source software selections The user inputs are inherently a logic input with no low frequency filtering implemented in software The user input may only be selected for sink source by the User Input Active parameter 7 USER INPUTS Two programmable user inputs Max Continuous Input 30 VDC Isolati...

Page 3: ...near devices that generate excessive heat should be avoided The PM 50 4 3 and 3 5 inch models meet NEMA 4X IP65 requirements when properly installed This unit is designed for through panel mounting The mounting surface should have a minimum thickness of 0 04 1 02 mm and maximum thickness of 0 25 6 35 mm Cut the mounting hole per the dimensions shown in the diagram Care should be taken to remove an...

Page 4: ... properly grounded This is especially useful in applications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radio transmitter Also Signal or Control cables within an enclosure should be routed as far away as possible from contactors control relays transformers and other noisy components 4 Long cable runs are more suscep...

Page 5: ...and User Input Common terminals Appropriate considerations must then be given to the potential of the user input common with respect to earth common and the common of the isolated plug in modules with respect to input common 14 15 MAGNETIC PICKUP INP COM INP A 14 15 to 2 5 mA MAX Resistor to limit current AC INP COM INP A 14 10 15 2 2KΩ INP COM 24V EXC INP A NPN O C 10 14 15 24V EXC INP COM INP A ...

Page 6: ...130K B A COM 130K RX TX 8 7 9 RS485 2 WIRE CONNECTIONS See appropriate document for instructions on module installation and wiring support CONFIGURING A PM 50 Various options are available to configure your PM 50 so you can choose the one that fits your requirement Programming Wizard On initial power up a Programming Wizard will offer assistance Proceeding with the Wizard will help with the basic ...

Page 7: ...d Orientation 3 5 Inch Meter ORDERING INFORMATION DESCRIPTION PART NUMBER Graphical Panel Meter 4 3 Display Digital Input PM500D0400800F00 Graphical Panel Meter 3 5 Display Digital Input PM500D0301600F00 Accessories TYPE DESCRIPTION PART NUMBER Modules RS232 Serial Communications Module PMM000CM23200000 Ethernet Communications Module PMM000CMENT00000 Analog Output Module PMM000I0AN000000 Dual Setp...

Page 8: ...ANTABILITY B WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE OR C WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY RIGHTS OF A THIRD PARTY WHETHER EXPRESS OR IMPLIED BY LAW COURSE OF DEALING COURSE OF PERFORMANCE USAGE OFTRADE OR OTHERWISE Customer shall be responsible for determining that a Product is suitable for Customer s use and that such use complies with any applicable local state or fed...

Reviews: