Drawing No. LP1140  

Effective 08 2021

USER INPUT WIRING

User Input terminal does not need to be wired in order to remain in the inactive state.

   

Sinking Logic

When the parameter is 

programmed to Low, check 

with device GUI option. The 

user inputs of the controller 

are internally pulled up to 

+3.3 V with 20 KΩ 

resistance. The input is 

active when it is pulled low 

(<0.9 V).

Sourcing Logic

When the parameter is 

programmed to High, check 

with device GUI option. The 

user inputs of the controller 

are internally pulled down to 

0 V with 20 KΩ resistance. 

The input is active when a 

voltage greater than 2.4 VDC 

is applied.

USER/EX

CO

M

USER 

1

USER 

2

12 13

11

OR

12

11

13

+

-

(30V max.)

SUPPLY

V

USER 

1

USER 

2

OR

USER/EX

CO

M

ON-BOARD DUAL SSR WIRING   

Sinking Mode

Sourcing Mode

100 mA PER OUTPUT

SSR OUTPUTS SINKING MODE

LO

AD

4

OP1

OP2

LO

AD

OP 

COM

5

6

30V

+ -

3

OP 

EXT 

POWER

100 mA PER OUTPUT

SSR OUTPUTS SOURCING MODE

+ -

OP 

EXT 

POWER 3

LO

AD

4

OP1

5

OP2

LO

AD

30V

6

OP 

COM

The SSR outputs require meter configuration to address their functionality. 

The drawings below illustrate the wiring for each option.

RS485/MODBUS   

Transmit

Enable

+5V

130K

B (-)

A (+)

COM

130K

RX

TX

8

7

9

RS485 2-WIRE CONNECTIONS

See appropriate document for instructions on module installation and wiring support.

CONFIGURING A PM-50

Various options are available to configure your PM-50 so you 

can choose the one that fits your requirement.

Programming Wizard

On initial power up a Programming Wizard will offer assistance. 

Proceeding with the Wizard will help with the basic configuration 

including screen set-up, selecting the input and programming the 

output. After completion your device will display the items you 

selected. Additional capabilities can be accessed via the Programming 

App, Web Server, or manually entering the programming.

Web Interface

To configure the device for web access, login as Admin and 

follow the below steps to setup Wi-Fi:

1. 

Go to System → Network Configuration → Wi-Fi Configuration

2. Enable Wi-Fi as “ON” and select the right arrow

3. From here, make your Wi-Fi configuration selections based on 

your connection setup.

App Connectivity

Programming and monitoring of the device can be done via an 

App. Go to the App Store and search for PM50 by Red Lion.  

Install the app on your smart device. With Wi-Fi enabled, 

monitoring and controlling of the device can be done through the 

app. Now programming the device is as easy as making some 

selections and downloading to the device.

Summary of Contents for PM-50

Page 1: ...uirements for AC power and they can be accommodated with our AC to DC Power Module PACKAGE CHECKLIST This product package should contain the items listed below If any items are missing or damaged contact Red Lion immediately PM 50 Digital Input Panel Meter Accessory Pack Installation Guide SAFETY SUMMARY All safety related regulations local codes and instructions that appear in this document or on...

Page 2: ...accept the second signal of each signal pair The user inputs do not have the Logic Mag HI LO Freq and Sink Source software selections The user inputs are inherently a logic input with no low frequency filtering implemented in software The user input may only be selected for sink source by the User Input Active parameter 7 USER INPUTS Two programmable user inputs Max Continuous Input 30 VDC Isolati...

Page 3: ...near devices that generate excessive heat should be avoided The PM 50 4 3 and 3 5 inch models meet NEMA 4X IP65 requirements when properly installed This unit is designed for through panel mounting The mounting surface should have a minimum thickness of 0 04 1 02 mm and maximum thickness of 0 25 6 35 mm Cut the mounting hole per the dimensions shown in the diagram Care should be taken to remove an...

Page 4: ... properly grounded This is especially useful in applications where cable runs are long and portable two way radios are used in close proximity or if the installation is near a commercial radio transmitter Also Signal or Control cables within an enclosure should be routed as far away as possible from contactors control relays transformers and other noisy components 4 Long cable runs are more suscep...

Page 5: ...and User Input Common terminals Appropriate considerations must then be given to the potential of the user input common with respect to earth common and the common of the isolated plug in modules with respect to input common 14 15 MAGNETIC PICKUP INP COM INP A 14 15 to 2 5 mA MAX Resistor to limit current AC INP COM INP A 14 10 15 2 2KΩ INP COM 24V EXC INP A NPN O C 10 14 15 24V EXC INP COM INP A ...

Page 6: ...130K B A COM 130K RX TX 8 7 9 RS485 2 WIRE CONNECTIONS See appropriate document for instructions on module installation and wiring support CONFIGURING A PM 50 Various options are available to configure your PM 50 so you can choose the one that fits your requirement Programming Wizard On initial power up a Programming Wizard will offer assistance Proceeding with the Wizard will help with the basic ...

Page 7: ...d Orientation 3 5 Inch Meter ORDERING INFORMATION DESCRIPTION PART NUMBER Graphical Panel Meter 4 3 Display Digital Input PM500D0400800F00 Graphical Panel Meter 3 5 Display Digital Input PM500D0301600F00 Accessories TYPE DESCRIPTION PART NUMBER Modules RS232 Serial Communications Module PMM000CM23200000 Ethernet Communications Module PMM000CMENT00000 Analog Output Module PMM000I0AN000000 Dual Setp...

Page 8: ...ANTABILITY B WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE OR C WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY RIGHTS OF A THIRD PARTY WHETHER EXPRESS OR IMPLIED BY LAW COURSE OF DEALING COURSE OF PERFORMANCE USAGE OFTRADE OR OTHERWISE Customer shall be responsible for determining that a Product is suitable for Customer s use and that such use complies with any applicable local state or fed...

Reviews: