57
Checking for Calibration
Temperature Sensors TS1, TS2 and optional TS3 can be checked for proper calibration by
measuring sensor resistance (see Table below).
Table 2. -
Sensor Temperature
-vs- Resistance
Temperature
Resistance
(° F)
(° C)
(Ohms)
10
-12.2
14.07K
20
-6.6
10.41K
30
-1.1
7.782K
40
4.4
5.874K
50
10
4.482K
60
15.5
3.458K
70
21.1
2.678K
80
26.6
2.011K
90
32.2
1.653K
100
37.7
1.317K
110
43.3
1.051K
120
48.8
849.3