43
NOTE:
In the ADAPTIVE or AUTO mode the number of ON/OFF cycles per day are based
upon historical data from a 30 day average (sliding window) of purge operation.
Log 10 -
Number of Adaptive only run cycles
“Chiller OFF”
(
maximum 8 cycles per day)
Indicates the number of current minimum “ON” purging cycles the purge will run per day (while
the chiller is off) in the “ADAPTIVE” mode only.
NOTE:
In the ADAPTIVE mode the number of ON/OFF cycles per day are based upon
historical data from a 30 day average (sliding window) of purge operation.
Log 11 - Interval log (
in days, hours and minutes
)
Allows the purge operator a method of tracking p urge operation during certain operator
determined service intervals (see interval log at the end of the explanation of LOGs keypad
switch on page 39 for more information).
“SENSORS” Display
Displays:
Superheat
°
F
(purge unit compressor suction temperature)
Evaporator
°
F
(purge tank Evaporating temperature)
and...
Liq. Level High
or
Low
(purge tank liquid level status)
(Superheat) Refrigeration Compressor Suction Temperature
Indicates suction line temperature in degrees ºF.
(Evaporator) Purge Tank Evaporating Temperature.
Indicates purge tank inlet evaporating temperature in degrees ºF.
(Liquid Level Status) Drain Status
Indicates status of liquid refrigerant level in the purge tank.
(see “Drain Back Equalization Cycle” on page 44 for more information on purge tank liquid
drain activity)