32
“
AUTO
” Keypad Switch
To enter the "Auto" mode press the "Auto" Switch. The display will read “On Auto” mode
indicating the purge is operating in the "Auto" mode. The purge will remain in the “Auto" mode
until another keypad switch is pressed, such as STOP, or SET CLOCK or when a different
mode is selected. Display changes to:
ON Auto
Hh: Mm left 00:15
(Example)
Off Auto
Hh: Mm left 02:35
(Example)
Off Auto
Chiller is off
Indicates the purge is active and
the amount of time (hours and
minutes) remaining in the “ON”
period (see page 29 for further
information).
Indicates the amount of time
(hours and minutes) remaining
in the “OFF” period (see page
29 for further information).
Indicates all purging activity has
ceased while the chiller is off
(see page 29 for further
information).
NOTE:
While in the “Auto” mode the display may alternate between one or more displays.
The display will usually be self explanatory.
“
ADAPTIVE
” Keypad Switch
(for additional information see “Operating Modes” page 29)
To enable the "Adaptive" mode press the "Adaptive" Switch. The display will read “On
Adaptive” indicating the purge is operating in the "Adaptive" mode. The purge will remain in
the Adaptive" mode until another keypad switch is pressed, such as STOP, or SET CLOCK or
when a different mode is selected. Display changes to:
ON Adaptive
Hh: Mm left 00:15
(Example)
Off Adaptive
Hh: Mm left 02:35
(Example)
Adapt, 3hr test
Hh: Mm left 02:43
(Example)
Indicates the purge is active and
the amount of time (hours and
minutes) remaining in the “ON”
period (see page 29 for further
information).
Indicates the amount of time
(hours and minutes) remaining
in the “OFF” period (see page
29 for further information).
Indicates the purge is running in
the three (3) hour test after a
chiller shut down to determine if
there are any residual non-
condensables remaining in the
chiller (see page 42 pumpout
during first 3 hours after last
chiller shutdown for further
information).
NOTE:
While in the “Adaptive” mode the display may alternate between one or more displays.
The display will usually be self explanatory.
Summary of Contents for Redi-Purge PRG-113-C3
Page 2: ...2 Revised Technically as of October 11 2013 1994 REDI CONTROLS INC GREENWOOD INDIANA...
Page 4: ...4...
Page 67: ...67...