Preliminary Checkout and Power-Up (continued)
2.
Check the Unit fuse (F1) to insure that it is properly installed (see Figure 4 on page 17).
3.
Check to make sure that all internal connections are secure.
4.
Apply power to purge unit and measure voltages at TB1 -1 & TB1-6 and TB1-3 & TB1-6
(see figures 8 and 8A on pages 51 and 52).
5.
The voltage between TB1-1 & TB1-6 should be 103 to 127 VAC, and between TB1 -3 &
TB1-6 should be 0 volts with chiller "OFF" and 103 to 127 VAC when chiller is ”ON”.
6.
Check purge control panel LCD display, the display should be displaying:
System Ready
Select Mode:
Alternating with:
System Ready
00:00 AM
(current clock time)
NOTE:
Upon initial power-up the purge display may read
BATTERY FAULT PRESS RESET
KEY
. Simply press the RESET keypad switch to reset the purge unit and begin the
QUICK START program.
(See “QUICK START” starting on page 24.)
7.
Preliminary Checkout is complete.