INSTALLATION

as shown in Figure 17. Pointing the vent down 

protects it from freezing rain or sleet.
Install sediment trap in supply line as shown 

in Figure 16. Place sediment trap where it is 

within reach for cleaning. Place sediment trap 

where trapped matter is not likely to freeze. 

A sediment trap traps moisture and contami-

nants. This keeps them from going into heater 

controls. If sediment trap is not installed or is 

installed wrong, heater may not run properly.

Figure 16 - Gas Connection

* Purchase the optional CSA design-certified equipment 

shutoff valve from your dealer.

Apply pipe joint sealant lightly to male threads. 

This will prevent excess sealant from going 

into pipe. Excess sealant in pipe could result 

in clogged heater valves.
The installer must supply an external regula-

tor. The external regulator will reduce incom-

ing gas pressure. You must reduce incoming 

gas pressure to between 11" and 14" of water. 

If you do not reduce incoming gas pressure, 

heater regulator damage could occur. Install 

external regulator with the vent pointing down 

Figure 17 - External Regulator 

with Vent Pointing Down

External 

Regulator with 

Vent Pointing 

Down

Propane/LP 

Supply Tank

Equipment 

Shutoff Valve

Ground 

Joint Union

3/8" NPT 

Pipe Nipple

Tee Joint

Reducer 

Bushing to 

1/8" NPT

1/8" NPT 

Plug Tap

Test Gauge 

Connection*

Sediment 

Trap

Tee Joint

Pipe Nipple

Gap

3" Minimum

Natural Gas

From Gas Meter

 

(5" W.C.** to 9.5" W.C. 

Pressure)

Propane/LP 

From External 

Regulator (11" 

W.C.** to 14" W.C. 

Pressure)

CHECKING GAS CONNECTIONS

1.  Disconnect heater with its appliance main 

gas valve (control valve) and equipment 

shutoff valve from gas supply piping sys-

tem. Pressures in excess of 1/2 PSIG will 

damage heater regulator.

2.  Cap off open end of gas pipe where equip-

ment shutoff valve was connected.

3.  Pressurize supply piping system by either 

using compressed air or opening gas sup-

ply valve.

 WARNING: Test all gas piping 

and connections for leaks after 

installing or servicing. Correct 

all leaks at once.

 WARNING: Never use an open 

flame to check for a leak. Apply a 

mixture of liquid soap and water 

to all joints. If bubbles form, there 

is a leak. Correct all leaks at once.

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

4.  Check  all  joints  of  gas  supply  piping 

system. Apply mixture of liquid soap and 

water to gas joints. If bubbles form, there 

may be a leak.

5.  Correct all leaks at once.
6.  Reconnect heater and equipment shutoff 

valve to gas supply. Check reconnected 

fittings for leaks.

Summary of Contents for BWH30NLTE-2

Page 1: ...ot touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supp...

Page 2: ...s manual WARNING Improper installation adjustment al teration service or maintenance can cause injury or property damage Refer to this manual for correct in stallation and operational procedures For a...

Page 3: ...er serviced Some people are more af fected by carbon monoxide than others These include pregnant women people with heart or lung disease or anemia those under the influ ence of alcohol and those at hi...

Page 4: ...off If heated the vapors from these prod ucts may create a white powder residue within burner box or on adjacent walls or furniture 8 Do not use heater if any part has been under water Immediately ca...

Page 5: ...n either Propane LP or Natural gas The heater is shipped from the factory ready for connect ing to Propane LP The heater can easily be changed to Natural gas by having your quali fied installer follow...

Page 6: ...UCT OF UNVENTED ROOM HEATERS Water vapor is a by product of gas combus tion An unvented room heater produces ap proximately one 1 ounce 30 mL of water for every 1 000 BTUs 0 3 KWs of gas input per hou...

Page 7: ...eathe Fresh air must enter your home All fuel burning ap pliances need fresh air for proper combustion and ventilation Exhaust fans fireplaces clothes dryers and fuel burning appliances draw air from...

Page 8: ...to adjoining room see option 3 Figure 2 Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Air for Combustion and Ventilation for required size of ventilation grills or ducts Ventilation Air From O...

Page 9: ...kerosene lamps etc in the air exist maycausewallstodiscolor Figure 4 Mounting Clearances as Viewed From Front of Heater IMPORTANT Vent free heaters add moisture to the air Although this is beneficial...

Page 10: ...ounting bracket is located on back panel of heater It has been taped there for shipping Remove mounting bracket from back panel Methods For Attaching Mounting Bracket To Wall Use only the last hole on...

Page 11: ...ne up last hole on each end of bracket with wall anchors 6 Insert mounting screws through bracket and into wall anchors 7 Tighten screws until mounting bracket is firmly fastened to wall Marking Screw...

Page 12: ...s firmly secured to wall Do not over tighten Note Do not replace front panel at this time Replace front panel after making gas connec tions and checking for leaks Figure 10 Mounting Heater Onto Mounti...

Page 13: ...void gas leak age for the gas not being used at the inlet of regulator a qualified installer or service technician must use supplied cap You will notice a color coded plungerontheinsideoftheregu lator...

Page 14: ...ile pushing in rotate the fitting clockwise until the threads engage the regulator After the fitting has been hand tightened into the regulator use a wrench to complete tightening of the fitting Insta...

Page 15: ...the heater and gassupply Gassupplierprovides externalregulatorfornaturalgas Theinstallerprovidestheexternal regulator for propane LP gas CAUTION Avoid damage to regulator Hold gas regulator with wren...

Page 16: ...lator with Vent Pointing Down Propane LP Supply Tank Equipment Shutoff Valve Ground Joint Union 3 8 NPT Pipe Nipple Tee Joint Reducer Bushing to 1 8 NPT 1 8 NPT Plug Tap Test Gauge Connection Sediment...

Page 17: ...l leaks at once 6 Light heater see Lighting Instructions on page 18 Check all other internal joints for leaks 7 Turn off heater see To Turn Off Gas Ap pliance page 19 8 Replace front panel 1 Open equi...

Page 18: ...n above 2 Make sure equipment shutoff valve is fully open 3 Turn control knob clockwise to the OFF position 4 Wait five 5 minutes to clear out any air Then smell for gas including near the floor If yo...

Page 19: ...ousing construction TO TURN OFF GAS TO APPLIANCE Shutting Off Heater Turn control knob clockwise to the OFF position Shutting Off Burner Only pilot stays lit Turn control knob clockwise to the PILOT p...

Page 20: ...Code and for US instal lations the National Electrical Code ANSI NFPA NO 70 WARNING If repairing or replacing any electrical compo nent or wiring the original wire routing colorcodingandsecur ing loca...

Page 21: ...to cool which shuts the heater off If pilot flame pattern is incorrect as shown in Figure 25 turn heater off see To Turn Off Gas to Ap pliance page 19 see Troubleshooting pages 23 through 26 WARNING I...

Page 22: ...es 2 Remove four screws securing front panel 3 Pull front panel forward 4 Inspect burner and pilot for dust and dirt 5 Blow air through the ports slots and holes in the burner 6 Replace front panel us...

Page 23: ...life and require no further lubrication However periodic cleaning vacuuming of the appliance around the air intake and exhaust as well as the fan heater is recommended For heavy or continuous use per...

Page 24: ...valve 2 Fully press in control knob while pressing ignitor button 3 Continue holding down con trol knob Repeat igniting op eration until air is removed 4 Clean ODS pilot see Care and Maintenance page...

Page 25: ...t 1 Burner orifice is clogged 2 Inlet gas pressure is too low 1 Clean burner orifice see Care and Maintenance page 22 2 Contact local gas supplier Delayed ignition of burner s 1 Manifold pressure is t...

Page 26: ...products Heater produces un wanted odors 1 Heater is burning vapors from paint hair spray glues etc See IMPORTANTstatement page23 2 Gas leak See Warning State ment at the top of page 23 3 Low fuel sup...

Page 27: ...ontact your local gas supplier REPLACEMENT PARTS Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty PARTS UNDER WARRANTY Call Customer...

Page 28: ...www sureheat com 200305 01C 28 PARTS MODEL BWH30NLTE 2 2 11 3 9 8 7 1 12 10 5 6 14 13 15 12 16 4 17...

Page 29: ...161133 01 Piezo Ignitor 1 4 161130 01 Thermostat Valve Assy 1 5 Burner Assembly 1 6 161139 01 ODS Pilot 1 7 Dual Fuel Regulator 1 8 161200 01 Inlet Cover Plug 1 9 160960 01 Cap with Seal 1 10 Bezel T...

Page 30: ...____________________ ________________________________________________________________ ________________________________________________________________ _________________________________________________...

Page 31: ...____________________ ________________________________________________________________ ________________________________________________________________ _________________________________________________...

Page 32: ...ge resulting from any of the following Negligent use or misuse of the product including exposing the product to chemicals or cleaning products not approved by SHM International Corp Corrosion rust or...