8.
SERIAL COMMUNICATIONS (Optional):
(Cont’d)
Serial Hardware Specifications
-
SO - Output Transistor Rating: V
max
= 30 VDC, V
SAT
= 1 V
max
at 20 mA.
(Can address 16 units in a loop)
SI - Input Diode Rating: VF = 1.25 V
TYP
; 1.5 V
max
Note: The compliance voltage rating of the source must be greater than the
sum of the voltage drops around the loop.
9
.
OUTPUT(S):
Solid-State
- Current sinking NPN open collector transistor(s). I
SNK
= 100 mA
maximum. V
OH
= 30 VDC maximum
(Internal Zener diode protection)
. V
OL
=
1 VDC max. @ 100 mA.
Relay(s) -
Mounted on a field replaceable P.C. board. Form C contacts rated at
5 amps @ 120/240 VAC or 28 VDC
(resistive load)
, 1/8 H.P. @ 120 VAC
(inductive load)
. The operate time is 5 msec. nominal and the release time is 3
msec. nominal.
Relay Life Expectancy -
100,000 cycles at Max. Rating.
(As load level
decreases, life expectancy increases.)
Programmable Timed Outputs -
The timed outputs can be set from 0.01 to
599.99 seconds, +/-
(0.01% + 10 msec)
.
10.
CERTIFICATIONS AND COMPLIANCES:
SAFETY
IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment
for measurement, control, and laboratory use, Part 1.
IP65 Enclosure rating (Face only), IEC 529
Type 4 Enclosure rating (Face only), UL50
ELECTROMAGNETIC COMPATIBILITY:
Immunity to EN 50082-2
Electrostatic discharge
EN 61000-4-2 Level 2; 4 Kv contact
1
Level 3; 8 Kv air
Electromagnetic RF fields
EN 61000-4-3 Level 3; 10 V/m
80 MHz - 1 GHz
Fast transients (burst)
EN 61000-4-4 Level 4; 2 Kv I/O
Level 3; 2 Kv power
2
RF conducted interference
EN 61000-4-6 Level 3; 10 V/rms
150 KHz - 80 MHz
Power frequency magnetic fields EN 61000-4-8 Level 4; 30 A/m
Emissions to EN 50081-2
RF interference
EN 55011
Enclosure class A
Power mains class A
Notes:
1. Metal bezel of unit connected with ground from rear bezel screw to metal
mounting panel.
2. When the unit is DC powered, a power line filter (RLC# LFIL0000 or
equivalent) was installed, so as not to impair the function of the unit.
Refer to the EMC Compliance Installation section of the manual for
additional information.
11.
ENVIRONMENTAL CONDITIONS:
Operating Temperature
: 0 to 50°C
Storage Temperature
: -40 to 80°C
Operating and Storage Humidity
: 85% max. relative humidity
(non-condensing) from 0°C to 50°C.
Altitude
: Up to 2000 meters
12.
CONSTRUCTION:
Metal die-cast bezel, plastic case. This unit is rated
for NEMA 4/IP65 indoor use. Installation Category II, Pollution
Degree 2.
13.
WEIGHT:
2.1 lbs (0.9 kg)
–42–
Summary of Contents for GEMINI 1000
Page 33: ...GEMINI 1000 BLOCK DIAGRAM...
Page 34: ...GEMINI 2000 BLOCK DIAGRAM...
Page 39: ...GEMINI 1000 CONNECTIONS CONFIGURATION SWITCH SET UPS FOR VARIOUS SENSOR OUTPUTS SEE NOTE 5...
Page 40: ...GEMINI 2000 CONNECTIONS CONFIGURATION SWITCH SET UPS FOR VARIOUS SENSOR OUTPUTS SEE NOTE 5...
Page 53: ...APPENDIX F GEMINI 1000 PROGRAMMING CHART CARD...
Page 54: ...APPENDIX F GEMINI 1000 PROGRAMMING CHART CARD...
Page 55: ...APPENDIX F GEMINI 2000 PROGRAMMING CHART CARD...
Page 56: ...APPENDIX F GEMINI 2000 PROGRAMMING CHART CARD...