red lion CUB5RT Manual Download Page 2

1. 

DISPLAY

: 5 digit LCD 0.48" (12.2 mm) high digits

CUB5RTR0

: Reflective LCD with full viewing angle

CUB5RTB0

: Transmissive LCD with selectable red or green LED backlight,  

viewing angle optimized. Display color change capability with output state 
when using an output module.

2. 

POWER

: Input voltage range is +9 to +28 VDC with short circuit and input 

polarity protection. Must use an RLC model MLPS or a NEC Class 2 or 
Limited Power Source (LPS) rated power supply.

3. 

READOUT

:

Resolution: 1 or 0.1 degrees
Scale: °F or °C
Offset Range: -19999 to 19999 display units

4. 

RTD INPUTS

:

Isolation

:

 

Input and EXC terminals are not electrically isolated from the 

power supply or optional comms cards.

Failed Sensor Display



 or 



Overrange/Underrange Input



/



Overrange/Underrange Display

 : “

.....

”/“-

.....

” 

Maximum Input Voltage

: 30 VDC

Type: 2, 3 or 4 wire
Excitation current: 100 ohm range: 165 

μ

A

                 10 ohm range:  2.5 mA

Lead resistance: 100 ohm range: 10 ohm/lead max.

             10 ohm range: 3 ohms/lead max.

Balanced Lead Resistance: Automatically compensated up to max per lead.
Unbalanced Lead Resistance: Uncompensated.

*After 20 min. warm-up. Accuracy is specified in two ways: Accuracy at 

23°C and 15 to 75% RH environment; and Accuracy over a -35 to 75°C and 
0 to 85% RH (non condensing) environment. Accuracy specified over the -35 
to 75°C operating range includes meter tempco effects. The specification 
includes the A/D conversion errors and linearization conformity. Total system 
accuracy is the sum of meter and probe errors. Accuracy may be improved by 
field calibrating the meter readout at the temperature of interest.

5. 

RESPONSE TIME

:

Display

: 500 msec min.

Output

: 1.25 sec max (with input filter setting of 0)

6. 

USER INPUT (USR):

 Programmable input. Connect terminal to common 

(USR COMM) to activate function. Internal 10K

 pull-up resistor to +9 to 

28 VDC.

Threshold Levels

: V

IL

 = 0.7 V max; V

IH

 = 2.4 V min; V

MAX

 = 28 VDC 

Response Time

: 5 msec typ.; 50 msec debounce (activation and release)

7.

 CERTIFICATIONS AND COMPLIANCES

:

CE Approved

EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
IEC/EN 61010-1
RoHS Compliant

UL Recognized Component: File #E179259
UL Listed: File #E137808
Type 4X Outdoor Enclosure rating (Face only)
IP65 Enclosure rating (Face only)
IP20 Enclosure rating (Rear of unit)

Refer to EMC Installation Guidelines for additional information.

8. 

MEMORY

: Nonvolatile E

2

PROM memory retains all programming 

parameters and max/min values when power is removed.

9. 

CONNECTIONS

: Wire clamping screw terminals

Wire Strip Length

: 0.3" (7.5 mm)

Wire Gage

: 30-14 AWG copper wire

Torque

: 5 inch-lbs (0.565 N-m) max.

10

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range for CUB5RTR0

: -35 to 75 °C

Operating Temperature Range for CUB5RTB0 depends on display color 

and intensity level as per below

:

INTENSITY LEVEL

TEMPERATURE

Red Display

1 & 2

-35 to 75°C

3

-35 to 70°C

4

-35 to 60°C

5

-35 to 50°C

Green Display

1 & 2

-35 to 75°C

3

-35 to 65°C

4

-35 to 50°C

5

-35 to 35°C

Storage Temperature

: -35 to 85 °C

Operating and Storage Humidity

: 0 to 85% max. relative humidity (non-

condensing)

Vibration to IEC 68-2-6

: Operational 5-500 Hz, 5 g

Shock to IEC 68-2-27

: Operational 30 g

Altitude

: Up to 2000 meters

11. 

CONSTRUCTION

: This unit is rated for NEMA 4X/IP65 requirements for 

outdoor use. Installation Category I, Pollution Degree 2. High impact plastic 
case with clear viewing window. Panel gasket and mounting clip included.

12. 

WEIGHT

: 3.2 oz (100 g)

2

G

ENERAL

 M

ETER

 S

PECIFICATIONS

O

RDERING

 I

NFORMATION

MODEL 

NO.

DISPLAY COLOR

INPUT CURRENT

@ 9 VDC WITHOUT 

CUB5RLY0

INPUT CURRENT 

@ 9 VDC WITH 

CUB5RLY0

CUB5RTR0

---

10 mA

40 mA

CUB5RTB0

Red (max intensity)

85 mA

115 mA

CUB5RTB0

Green (max intensity)

95 mA

125 mA

Crimson software is a free download from http://www.redlion.net/

100 ohm Pt 

alpha = .00385

-200 to 850°C

0.4°C

1.6°C

IEC 751

100 ohm Pt 

alpha = .00392

-200 to 850°C

0.4°C

1.6°C

no official 

standard

120 ohm Nickel 

alpha = .00672

-80 to 260°C

0.2°C

0.5°C

no official 

standard

INPUT TYPE

10 ohm Copper 

alpha = .00427

-100 to 260°C

0.4°C

0.9°C

no official 

standard

RANGE

ACCURACY*

(18 to 28

°

C)

ACCURACY*

(0 to 50

°

C)

STANDARD

TYPE

MODEL NO.

DESCRIPTION

PART NUMBER

CUB5

CUB5RT

RTD Meter with Reflective Display

CUB5RTR0

RTD Meter with Backlight Display

CUB5RTB0

Optional Plug-in 

Cards

CUB5RLY

Single Relay Output Card

CUB5RLY0

CUB5SNK

Dual Sinking Output Card

CUB5SNK0

CUB5COM

RS485 Serial Communications Card

CUB5COM1

RS232 Serial Communications Card

CUB5COM2

CUB5USB

USB Programming Card

CUB5USB0

Accessories

MLPS

+12 VDC Micro-Line Power Supply, 85 to 250 VAC source, 400 mA max out

MLPS1000

+24 VDC Micro-Line Power Supply, 85 to 250 VAC source, 200 mA max out

MLPS2000

CBLPROG

RS232 Programming Cable (DB9-RJ11)

CBLPROG0

CBPRO

Crimson PC Configuration Software for Windows 98, ME, 2000, XP 

1

SFCRD200

CBLUSB

USB Programming Cable

CBLUSB00

Summary of Contents for CUB5RT

Page 1: ...this literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it If equipment is used in a manner not specified by...

Page 2: ...es for additional information 8 MEMORY Nonvolatile E2PROM memory retains all programming parameters and max min values when power is removed 9 CONNECTIONS Wire clamping screw terminals Wire Strip Leng...

Page 3: ...Insert the unit into the panel cutout While holding the unit in place push the panel latch over the rear of the unit so that the tabs of the panel latch engage in the slots on the case The panel latch...

Page 4: ...MI suppression devices or equivalent are recommended Fair Rite part number 0443167251 RLC part number FCOR0000 Line Filters for input power cables Schaffner FN2010 1 07 Red Lion Controls LFIL0000 6 To...

Page 5: ...NNECTIONS OSNK1 OSNK2 COM 3 WIRE RTD COMM INP EXC 2 WIRE RTD COMM INP EXC JUMPER CAUTION Power input common and sensor input common are NOT isolated from user input common In order to preserve the saf...

Page 6: ...ges to memory and return the meter to the Display Mode If power loss occurs before returning to the Display Mode verify recent parameter changes PROGRAMMING TIPS It is recommended to start with Module...

Page 7: ...be automatically loaded for the selected type The position of the Input Range Jumper must match the RTD type selected F SCALE TEMPERATURE SCALE Select the temperature scale This selection applies for...

Page 8: ...ess the SEL button Display reads 00r 5 Apply a direct short to terminals INP EXC and COMM using a three wire link Press SEL Display reads CALC for about 15 seconds 6 When the display reads 15 0r apply...

Page 9: ...rogramming Immediate Access Entering Code 222 allows access regardless of security code 6 3 MODULE 3 DISPLAY AND FRONT PANEL BUTTON PARAMETERS 3 dSP SEL Pro Front Panel Display Select Enable Display U...

Page 10: ...Balanced Hys LO bL OUTPUT STATE OFF ON Hys SP SP Hys OFF TRIGGER POINTS High Acting Unbalanced Hys HI Ub 2 HYS n HYSTERESIS VALUE 1 to 59999 Enter desired hysteresis value See Setpoint Output Figures...

Page 11: ...ns Meter Address Abbreviated Printing 5 SEr bAUd dAtA PAr Addr Abbr OPt Pro The Serial Setup Parameters are only active when one of the optional serial communications programming cards is installed in...

Page 12: ...it Only Programming Security Code CodE Display Decimal Point RTD Type tYPE 1 INP Temperature Scale SCALE dECPt USrIN User Input Function Filter Setting Display Offset Value OFSEt FILtr Filter Band bAN...

Reviews: