SETPOINT VALUE

Enter the desired setpoint value. The decimal point position for the setpoint 

and hysteresis values follow the selection set in Module 1.

-9999

   

to

  

99999

6.4  MODULE 4 - S

ETPOINT

 O

UTPUT

 P

ARAMETERS

 (

4-SPt

)

SEL

Setpoint  

Action

Setpoint 

Select

Setpoint 

Value

Output Reset 

Action

Hysteresis 

Value

Off Time 

Delay

On Time 

Delay

Output Reset 

With Display 
Reset Enable

Change Display 

Color with 

Output State

Backlight 

Unit Only

SPSEL

4-SPt

Act-n

SPt-n

HYS-n

tON-n

tOF-n

rSt-n

rEn-n

ChC-n

Pro

Standby 

Operation

Stb-n

brn-n

Probe 

Burn-out

PARAMETER MENU

The Setpoint Output Parameters are only active when an optional output 

module is installed in the meter.

Enter the setpoint (output) to be programmed. The 

n

 in the following 

parameters will reflect the chosen setpoint number. After the chosen setpoint 
is completely programmed, the display will return to 

SPSEL

. Repeat steps for 

each setpoint to be programmed. Select 

NO

 to exit the module. The number of 

setpoints available is setpoint output card dependent.

SETPOINT SELECT

SP-2

SP-1

NO

NO

SPSEL

Select 

YES

 to enable Setpoint 2 and access the setup parameters. If 

NO

 is 

selected, the unit returns to 

SPSEL 

and setpoint 2 is disabled.

SETPOINT 2 ENABLE

NO

YES

NO

Enb-2

Enter the action for the selected setpoint (output). See Setpoint Output 
Figures for a visual detail of each action. 

SETPOINT ACTION

HI-Ub

Act-n

100

SPt-n

LO-Ub

HI-Ub

LO-bL

HI-bL

LO-Ub

 =

HI-Ub

 =

LO-bL

 =

HI-bL

 =

Low Acting, with unbalanced hysteresis

High Acting, with unbalanced hysteresis

Low Acting, with balanced hysteresis

High Acting, with balanced hysteresis

OUTPUT

STATE

OFF

ON

Hys

SP + ½Hys

SP

SP - ½Hys

OFF

TRIGGER POINTS

High Acting (Balanced Hys) = 

HI-bL

OUTPUT

STATE

OFF

ON

Hys

SP + Hys

SP

OFF

TRIGGER POINTS

Low Acting (Unbalanced Hys) = 

LO-Ub

OUTPUT

STATE

OFF

ON

Hys

SP + ½Hys

SP

SP - ½Hys

OFF

TRIGGER POINTS

Low Acting (Balanced Hys) = 

LO-bL

OUTPUT

STATE

OFF

ON

Hys

SP

SP - Hys

OFF

TRIGGER POINTS

High Acting (Unbalanced Hys) = 

HI-Ub

2

HYS-n

HYSTERESIS VALUE

1

   

to

  

59999

Enter desired hysteresis value. See Setpoint Output Figures for visual 

explanation of how setpoint output actions (balanced and unbalanced) are 
affected by the hysteresis. When the setpoint is a control output, usually 
balanced hysteresis is used. For alarm applications, usually unbalanced 
hysteresis is used. For unbalanced hysteresis modes, the hysteresis functions on 
the low side for high acting setpoints and functions on the high side for low 
acting setpoints.

Note: Hysteresis eliminates output chatter at the switch point, while time delay 

can be used to prevent false triggering during process transient events.

0.0

tOF-n

0.0

tON-n

OFF TIME DELAY

ON TIME DELAY

OUTPUT RESET ACTION

LAtCH

Auto

L-dLY

0.0

   

to

  

599.9

 Sec

0.0

   

to

  

599.9

 Sec

Enter the time value in seconds that the output is delayed from turning on 

after the trigger point is reached. A value of 0.0 allows the meter to update the 
output status per the response time listed in the Specifications.

Enter the time value in seconds that the output is delayed from turning off 

after the trigger point is reached. A value of 0.0 allows the meter to update the 
output status per the response time listed in the Specifications.

Enter the reset action of the output. See figure for details.

Auto

 = Automatic action; This action allows the output to automatically reset off 

at the trigger points per the Setpoint Action shown in Setpoint Output 
Figures. The “on” output may be manually reset (off) immediately by the 
front panel 

RST

 button or user input.The output remains off until the trigger 

point is crossed again.

LAtCH

 = Latch with immediate reset action; This action latches the output on at 

the trigger point per the Setpoint Action shown in Setpoint Output Figures. 
Latch means that the output can only be turned off by the front panel 

RST

 

button or user input manual reset, serial reset command or meter power cycle. 

Auto

rSt-n

Summary of Contents for CUB5RT

Page 1: ...this literature or on equipment must be observed to ensure personal safety and to prevent damage to either the instrument or equipment connected to it If equipment is used in a manner not specified by...

Page 2: ...es for additional information 8 MEMORY Nonvolatile E2PROM memory retains all programming parameters and max min values when power is removed 9 CONNECTIONS Wire clamping screw terminals Wire Strip Leng...

Page 3: ...Insert the unit into the panel cutout While holding the unit in place push the panel latch over the rear of the unit so that the tabs of the panel latch engage in the slots on the case The panel latch...

Page 4: ...MI suppression devices or equivalent are recommended Fair Rite part number 0443167251 RLC part number FCOR0000 Line Filters for input power cables Schaffner FN2010 1 07 Red Lion Controls LFIL0000 6 To...

Page 5: ...NNECTIONS OSNK1 OSNK2 COM 3 WIRE RTD COMM INP EXC 2 WIRE RTD COMM INP EXC JUMPER CAUTION Power input common and sensor input common are NOT isolated from user input common In order to preserve the saf...

Page 6: ...ges to memory and return the meter to the Display Mode If power loss occurs before returning to the Display Mode verify recent parameter changes PROGRAMMING TIPS It is recommended to start with Module...

Page 7: ...be automatically loaded for the selected type The position of the Input Range Jumper must match the RTD type selected F SCALE TEMPERATURE SCALE Select the temperature scale This selection applies for...

Page 8: ...ess the SEL button Display reads 00r 5 Apply a direct short to terminals INP EXC and COMM using a three wire link Press SEL Display reads CALC for about 15 seconds 6 When the display reads 15 0r apply...

Page 9: ...rogramming Immediate Access Entering Code 222 allows access regardless of security code 6 3 MODULE 3 DISPLAY AND FRONT PANEL BUTTON PARAMETERS 3 dSP SEL Pro Front Panel Display Select Enable Display U...

Page 10: ...Balanced Hys LO bL OUTPUT STATE OFF ON Hys SP SP Hys OFF TRIGGER POINTS High Acting Unbalanced Hys HI Ub 2 HYS n HYSTERESIS VALUE 1 to 59999 Enter desired hysteresis value See Setpoint Output Figures...

Page 11: ...ns Meter Address Abbreviated Printing 5 SEr bAUd dAtA PAr Addr Abbr OPt Pro The Serial Setup Parameters are only active when one of the optional serial communications programming cards is installed in...

Page 12: ...it Only Programming Security Code CodE Display Decimal Point RTD Type tYPE 1 INP Temperature Scale SCALE dECPt USrIN User Input Function Filter Setting Display Offset Value OFSEt FILtr Filter Band bAN...

Reviews: